2000/2300kVA Ntugharị ihe ntanetị eletriki-13.8 / 0.48 kV|US 2025

2000/2300kVA Ntugharị ihe ntanetị eletriki-13.8 / 0.48 kV|US 2025

Obodo: America 2025
Ike: 2000/2300 kVA
Voltaji: 13.8-0.48GrdY/0.277kV
Njirimara: ya na mmanụ FR3 na CT
Zipu ozi

 

 

2300kVA electrical substation transformer

Obodo na-enye ike, ụlọ ọrụ na ndị ọzọ - Elu-Mgbanwe ntinye nrụpụta arụmọrụ maka grid smart.

 

 

01 Izugbe

1.1 Nkọwa oru ngo

2000/2300 kVA substation transformer e zigara America na 2025. The gosiri ike nke transformer bụ 2000/2300 kVA na KNAN/KNAF jụrụ. The isi voltaji bụ 13.8 kV na ± 2 * 2.5% tapping nso (NLTC), nke abụọ voltaji bụ 0.48GrdY / 0.277 kV, ha guzobere vector otu Dyn1.

Na-ewebata 2000/2300 kVA ihe ntụgharị ọkụ ọkụ siri ike emebere maka ngwa na-achọ na njikwa ike ọkụ (APC), High Airflow Facilities (HAF), High-Load Substations (HLSB), na Wagon Loading Systems. Ihe ngbanwe a dị elu- nwere njiri ihe mgbochi 5A na-anọpụ iche maka nchebe mmejọ emelitere, ihe ngbanwe 5:5 nkenke ugbu a maka nleba anya ziri ezi, yana ọkwa mkpirisi C10{10} iji guzogide nrụgide ọkụ eletrik.

Ezubere maka ntụkwasị obi na akụrụngwa dị oke mkpa, ọ na-ebuga nkesa ike kwụsiri ike maka sistemu njikwa akpaaka, nnukwu gburugburu ebe jụrụ oyi, nnukwu ọdụ ụgbọ mmiri{{1} na ọrụ ụgbọ oloko. Site na nrụnye arụrụ arụ yana atụmatụ nchekwa dị elu, gụnyere mmachi mmejọ dị ugbu a na mkpirisi mkpirisi ike na-adịgide adịgide, transformer a na-ahụ maka ọrụ anaghị akwụsị akwụsị ebe ogo ike na nchedo sistemu kacha mkpa. Nhazi nhọrọ gụnyere ike nleba anya n'ime obodo yana ngwọta jụrụ oyi ahaziri iji zute ihe achọrọ arụ ọrụ.

 

 

 

1.2 Nkọwa nka nka

2000/2300 kVA substation transformer ụdị nkọwa na mpempe akwụkwọ data

Enyere ya
America
Afọ
2025
Ụdị
Ihe ntụgharị ọdụ ụgbọ mmiri
Ọkọlọtọ
ANSI/IEEE C57.12.00
Enyere ike
2000/2300 kVA
Ugboro ugboro
60HZ
Usoro
3
Ụdị oyi
KNAN/KNAF
Voltaji nke mbụ
13.8 kV
Voltaji nke abụọ
0.48GrdY/0.277 kV
Ngwa ikuku
Ọla kọpa
Ntugharị akụkụ
Dyn1
Mgbochi
6%
Pịa Changer
NLTC
Ọkụ aka
±2*2.5%
Enweghị mfu ibu
Ihe na-erughị ma ọ bụ hà nhata 2.36kW
Na Ọnwụ Ebu
Ihe na-erughị ma ọ bụ hà 17kW

 

 

1.3 Eserese

2000/2300 kVA substation transformer eserese na nha.

2000/2300 kVA substation transformer diagram 2000/2300 kVA substation transformer nameplate

 

 

02 Nrụpụta

2.1 Isi

Isi laminated bụ akụkụ dị oke egwu nke usoro mgbanwe atọ{{0}, atọ{1}, na-enye ụzọ enweghị mmasị maka ndọta ndọta - dị ala ma na-ebelata mfu efu ugbu a. Ewubere site na laminations silicon steel ekpokọtara, isi nwere atụmatụ kọlụm atọ- na-ebuli nkesa magnetik maka ịrụ ọrụ n'usoro atọ kwesịrị ekwesị{{5}. Ọdịdị ya siri ike na-eme ka ọ dị elu, na-ebelata ọ dịghị - mfu ibu, yana ịrụ ọrụ a pụrụ ịdabere na ya n'okpuru ọnọdụ ibu dị iche iche. Nhazi nke laminated na-akwalitekwa nkwụsi ike ọkụ yana ike igwe, na-eme ka ọ dị mma maka ngwa ọdụ ụgbọ mmiri dị elu-.

 

2.2 Ikuku

substation transformer winding

Ikuku LV:Ejiri foil ọla kọpa mee ya, na-enye kọmpat n'ígwé, oyi oyi na-agbanwe agbanwe, yana ike mkpirisi dị mkpụmkpụ{0}.

Ikuku HV:Multi- oyi akwa helical winding nwere ihe mkpuchi agbakwunyere, nke kachasị n'etiti - ntụgharị maka nkwụsi ike voltaji dị elu -.

 

2.3 tank

Tank nke ngbanwe na-arụ ọrụ dị ka ebe nchekwa nchekwa maka isi ihe ngbanwe, nke ejiri efere igwe welded dị elu- were rụọ ya n'ụdị mechiri emechi. Tankị ahụ na-enweta ule nrụgide siri ike iji hụ na arụmọrụ a pụrụ ịdabere na ya n'okpuru mgbanwe nrụgide mmanụ na-arụ ọrụ na ọnọdụ mmejọ nke ime. A na-enye ọtụtụ oghere flanged maka ahịhịa, ihe ngosi ọkwa mmanụ, na ngwaọrụ nleba anya. Ihe dị n'ime ime na-enweta ọgwụgwọ mgbochi - ma gụnye ihe mkpuchi magnetik iji belata mfu efu. Nhọrọ omenala gụnyere mgbochi - ihe mkpuchi corrosion ma ọ bụ ihe owuwu igwe anaghị agba nchara maka gburugburu na-achọsi ike.

sealed design oil tank of substation transformer

 

2.4 Mgbakọ ikpeazụ

2300kVA electrical substation transformer finall assembly

Mgbakọ ihe ngbanwe nke substation gụnyere isi stacking, winding installing (foil LV + wire HV), nhazi akụkụ nke na-arụ ọrụ, njikọ ọnụ, mkpuchi tank, na ntinye ngwa ngwa, yana ndochi mmanụ na-ejuputa mmanụ na ule ụlọ ọrụ (ratio, impedance, ịrị elu okpomọkụ, wdg) iji hụ na nnabata. Nhazi modular na-enyere aka njem na mmezi dị mfe.

 

 

03 Nnwale

Mba.

Nwale ihe

Nkeji

Ụkpụrụ nnabata

Ụkpụrụ ndị atụtara

Mmechi

1

Ntụle Nguzogide

%

Ọnụego enweghị nguzozi kacha nguzogide

4.55

Gafe

2

Nlele oke

%

Ngbanwe nke oke voltaji na ọpịpị bụ isi: Ihe na-erughị ma ọ bụ haha ​​0.5%

-0.07~0.12

Gafe

3

Usoro{0}}Nnwale mmekọrịta

/

Dyn1

Dyn1

Gafe

4

Ọ dịghị - ibu mfu na mkpali ugbu a

%

I0 :: nye uru a tụrụ atụ

0.35

Gafe

kW

P0: nye uru a tụrụ atụ

2.096

/

nnabata maka enweghị ibu ibu bụ +0%

/

5

Mfu ibu , impedance voltaji, ngụkọta mfu na arụmọrụ

/

t:85 ogo

nnabata maka mgbochi bụ +7.5%

Nkwenye maka mkpokọta mfu ibu bụ +0%

/

Gafe

%

Z%: uru tụrụ

6.38

kW

Pk: uru tụrụ

16.642

kW

Pt: uru tụrụ

18.738

%

Ịrụ ọrụ adịghị erughị 99.27%

99.30

6

Nnwale voltaji etinyere

/

HV: 34kV 60s

LV: 10kV 60s

Enweghị ọdịda nke voltaji ule a na-eme

Gafe

7

Nnwale Nkwụghachi Voltaji butere

/

Voltaji etinyere (kV): 0.96

Enweghị ọdịda nke voltaji ule a na-eme

Gafe

Ogologo oge (s):40

Ugboro (HZ): 180

8

Ntụle Nguzogide mkpuchi

GΩ

HV -LV n'ala:

6.50

/

LV-HV gaa n'ala:

7.12

HV&LV n'ala:

5.05

9

Ule ntapu

/

Ntinye nrụgide: 50kPA

Enweghị ntapu na mba

Mmebi

Gafe

Ogologo oge: 12h

10

Nnwale mmanụ

kV

Ike Dielectric

51.6

Gafe

mg/kg

Ọdịnaya Ọdịnaya

176.8

%

Ihe nchụsa

3.205

mg/kg

Nyocha nke Furan

/

/

Nyocha chromatography gas

/

 

2300kVA electrical substation transformer testing
2000kVA electrical substation transformer testing

 

 

04 Mbukota na mbupu

4.1 mbukota

Ihe ngbanwe ọdụ ụgbọ ala na-anakwere nchara agbachichara nke ọma{0}}osisi mejupụtara nkwakọ ngwaahịa. A na-eji ígwè ọwa welded siri ike rụọ nnukwu fremu, nke nwere ihe mgbochi ime{3}} nkwado ịma jijiji. Ngwongwo ahụ nwere akpa ebuli elu agbakwunyere maka njikwa nchekwa na cranes ma ọ bụ forklifts ma tinye ya nke ọma na ịdọ aka ná ntị (dịka, "Na-emebi emebi," "Kwụsị Akọrọ"). A na-echekwa akwụkwọ ndị dị mkpa (ndepụta nkwakọ ngwaahịa, akụkọ nnwale mgbanwe) na obere akpa mmiri na-adịghị n'ime nkwakọ ngwaahịa.

 

4.2 Mbupu

A na-ebuga n'ọdụ ụgbọ mmiri n'ọdụ ụgbọ mmiri na nnukwu ụgbọala na-adọkpụ-, kedebere ya nke ọma iji gbochie mgbanwe. N'ọdụ ụgbọ mmiri ahụ, a na-ebuba ya n'ime akpa, na-enwe nkwado nkwado kwesịrị ekwesị na nchekwa mmiri. A na-ebufe akpa ahụ mechiri emechi site n'ụgbọ mmiri nke nwere ezigbo nsochi oge-. A kwadebere akwụkwọ kọstọm n'ihu maka mkpochapụ nke ọma.

 

 

05 Saịtị na nchịkọta

Dị ka akụkụ dị oke mkpa na akụrụngwa ike, ndị na-eme mgbanwe ọdụ ụgbọ ala anyị na-ebuga arụmọrụ a pụrụ ịdabere na ya, ihe owuwu siri ike, na ike{0}} ịrụ ọrụ nke ọma. N'ịbụ ndị e mepụtara iji mezuo ụkpụrụ ụwa, ha na-ahụ na nnyefe ọkụ eletrik kwụsiri ike maka ngwa ụlọ ọrụ mmepụta ihe, azụmahịa na ngwa ọrụ. Site na nhọrọ nwere ike ịhazi ya yana njikwa mma siri ike, anyị na-enye azịza ahaziri dabere na ihe grid gị chọrọ. Kpọtụrụ anyị ka anyị jiri ntụkwasị obi rụọ ọrụ gị.

2300kVA electrical substation transformer usa

 

Ihe nchịkọta dị ọkụ: eletriki substation transformer, emeputa, soplaya, price, efu