50 kVA Single Phase Pole Nkwanye nkesa nkesa-13.8 / 0.12 / 0.24 kV|Guyana 2025
Ike: 50kVA
Voltaji: 13.8-0.12/0.24kV
Njirimara: ya na ngwaọrụ enyemaka nrụgide

Ihu igwe -Na-eguzogide, Na-agbanwu mgbe niile – Ogwe{1}} Ndị ngbanwe na-agbago na-edobe ọkụ.
01 Izugbe
1.1 Nkọwa oru ngo
50 kVA single phase pole mounted transformer ka ebugara Guyana na 2025. Akara ikike nke transformer bụ 50 kVA na ONAN jụrụ oyi. The isi voltaji bụ 13.8 kV na ± 2 * 2.5% tapping nso (NLTC), nke abụọ voltaji bụ 0.12 / 0.24 kV, ha guzobere a vector otu Ii0.
Ogwe mgbanaka 50 kVA{1} a na-ekpudo ka emebere ka ọ dabara n'ụkpụrụ IEEE, na-ahụ na arụmọrụ a pụrụ ịdabere na ya na ịdịte aka na ngwa nkesa n'èzí. Ọ na-egosipụta ihe owuwu siri ike nwere ihe ndị dị mkpa dị ka ngwaọrụ enyemaka nrụgide iji kwalite nchekwa site na igbochi ọnọdụ nrụgide karịrị akarị yana mgbanyụ- mgbanwe mgbata okirikiri maka mgbanwe voltaji na-agbanwe iji nabata ihe dị iche iche chọrọ. The transformer nwere anya{5}}ụdị ọnụ (eyelet bushings), na-eme ka njikọ echekwabara na nke ọma na ahịrị elu. Ogwe ya {{7} agbakwunyere n'iwu na-ebuli ojiji oghere ebe ọ na-enye nkesa ike dị irè n'ime ime obodo, ime ime obodo, ma ọ bụ ntọala ụlọ ọrụ mmepụta ihe. Emebere ya maka ịrụ ọrụ na ịdị ogologo ndụ, onye ntụgharị a dabara adaba maka ịba uru na iji azụmaahịa, na-ebuga ike kwụsiri ike n'okpuru ọnọdụ ọrụ dị iche iche.
1.2 Nkọwa nka nka
50 kVA okporo osisi n'ịnyịnya mgbanwe nkọwa ụdị na data mpempe akwụkwọ
|
Enyere ya
Guyana
|
|
Afọ
2025
|
|
Ụdị
Mkpanaka n'agbanyeghi
|
|
Ọkọlọtọ
IEEE&ANSI C57.12.00
|
|
Enyere ike
50 kVA
|
|
Ugboro ugboro
60HZ
|
|
Usoro
1
|
|
Polarity
Mwepu
|
|
Ụdị oyi
ONAN
|
|
Voltaji nke mbụ
13.8 kV
|
|
Voltaji nke abụọ
0.12 / 0.24 kV
|
|
Ngwa ikuku
Ọla kọpa
|
|
Ntugharị akụkụ
Ii0
|
|
Mgbochi
2%
|
|
Pịa Changer
NLTC
|
|
Ọkụ aka
±2*2.5%
|
|
Enweghị mfu ibu
0,16 kW
|
|
Na Ọnwụ Ebu
0,512 kW
|
|
Ngwa ngwa
Nhazi ọkọlọtọ
|
1.3 Eserese
Ihe osise 50 kVA nke etinyere ihe ngbanwe ihe osise na nha.

02 Nrụpụta
2.1 Isi
A na-emerụ eriri igwe silikoni ahụ gburugburu na igwe ikuku CNC iji mepụta akụkụ akụkụ anọ mechiri emechi ma ọ bụ toroidal. A na-ejikwa nlezianya na-achịkwa esemokwu n'oge ikuku iji zere nchekasị{1}} na-ebute mbibi magnetik. A na-eme annealing na ikuku hydrogen na 800 ~ 850 ogo iji belata nrụgide n'ibu ma weghachi ikike magnetik kacha mma. Otu akụkụ nke isi bụ nkenke- iji kwe ka ntinye eriri igwe, na-enwekwa elu ala a kpụrụ akpụ nke ọma ka ibelata nguzogide magnetik. Otu -oghere ogbe- nke a na-etinye ngbanwe nwere cores ọnya na-eweta arụmọrụ dị elu, mfu dị ala, yana ọrụ dị jụụ, na-eme ka ha dị mma maka netwọk nkesa ike ọgbara ọhụrụ. Na ọganihu na ihe dị ka amorphous ọla, ọnya isi transformers ga-ekere òkè ọbụna ukwuu na n'ọdịnihu smart grid usoro.

2.2 Ikuku

Mmanụ -osisi imikpu- ihe nrụnye nrụnye na-ejikarị nhazi ikuku-voltaji (LV) dị ala
• Ikuku LV: foil ọla kọpa kpuchiri ekpuchi (0.1–2mm gbara ọkpụrụkpụ) nwere ntinye akwụkwọ na-ekpo ọkụ, na-enye ihe na-akpata oghere dị elu, nju oyi na-arụ ọrụ nke ọma, yana obere mkpirisi ike dị mkpụmkpụ{2}.
• Ikuku HV: Multi- oyi akwa enameled waya ọla kọpa, jiri akwụkwọ mkpuchi na ọwa mmanụ mesie ike maka ike dielectric na-eme ka ọ dịkwuo mma wee pịa{1}} na-agbanwe mgbanwe.
A na-ahazi windings nke ọma (LV n'ime, HV n'èzí) wee mikpuo ya n'ụzọ zuru ezu na mmanụ transformer, na-eji mmanụ - akwụkwọ mkpuchi maka oyi na ikewapụ ọkụ eletrik.
2.3 tank
A na-esi na igwe oyi kpụọ {{0}Pasese Pole-A na-eji igwe na-ehulata kpụrụ akpụ - nke a na-eme ka ọ bụrụ cylindrical. A na-apịa mgbidi ndị dị n'akụkụ{4} nwere nku mgbịrịgba na-aga n'ihu wee gbado ya nke ọma site na iji mgbado TIG. Ihe mkpuchi tank ahụ bụ flange{6}} ejikọrọ mmanụ{7}} na-egbochi ya ma kpochie ya maka akara. All welds na-enweta ule penetration kerosene yana ule ntapu ikuku 0.05MPa. Ngwọta dị n'elu gụnyere nshịkọ ájá na-esochi ya na eserese abụọ{11}}akwa uwe (epoxy primer + polyurethane topcoat) maka nchebe corrosion n'èzí.

2.4 Mgbakọ ikpeazụ

1. Mgbakọ ikuku:Mia elu {{0}voltaji na obere{1}} voltaji windings na isi, na-ahụ n'ihu na mkpuchi mkpuchi kwesịrị ekwesị, ma chekwaa nkwado ikuku.
2. Njikọ eletrik:Solder ma ọ bụ kpachie ụzọ, jikọọ onye na-agbanwe mgbata, kechie ihe mkpuchi, ma dozie wiwi ahụ n'ebe.
3. Isi -Ikpokoro eriri igwe:Tinye akụkụ a na-arụ ọrụ (isi na windings) n'ime oven akpọnwụ, tinye ọkụ ọkụ iji wepụ mmiri mmiri, wee chọpụta nguzogide mkpuchi na-agbaso ụkpụrụ.
4. Nwụnye tankị:Welite akụkụ a mịrị amị nke na-arụ ọrụ ma jiri nlezianya wetuo ya n'ime tank ahụ, kwekọọ na ntụtụ, ma kechie bolts ntọala.
5. Ngwa mgbakwunye:Ugwu bushes, valve enyemaka nrụgide na ngwa ndị ọzọ, na-emechi nkwonkwo niile.
6. Ndochi mmanụ & akara:Vacuum- dejupụta mmanụ mkpuchi n'ọkwa a kapịrị ọnụ, lelee maka ntapu ma emechaa, ma mechaa mgbakọ ikpeazụ.
03 Nnwale
|
Mba. |
Nwale ihe |
Nkeji |
Ụkpụrụ nnabata |
Ụkpụrụ ndị atụtara |
Mmechi |
|
1 |
Ntụle Nguzogide |
/ |
/ |
/ |
Gafe |
|
2 |
Nlele oke |
/ |
Ngbanwe nke oke voltaji na ọpịpị bụ isi: Ihe na-erughị ma ọ bụ haha 0.5% Akara njikọ: ii0 |
-0.05 |
Gafe |
|
3 |
Nnwale polarity |
/ |
Mwepu |
Mwepu |
Gafe |
|
4 |
Ọ dịghị - ibu mfu na mkpali ugbu a |
% kW |
I0 :: nye uru a tụrụ atụ P0: nye uru a tụrụ atụ nnabata maka enweghị ibu ibu bụ +10% |
0.34 0.121 |
Gafe |
|
5 |
Ngwunye ibu, voltaji impedance, mfu zuru oke na arụmọrụ |
/ kW kW |
t:85 ogo Z%: uru tụrụ Pk: uru tụrụ Pt: uru tụrụ nnabata maka impedance bụ ± 10% Nkwenye maka mkpokọta mfu ibu bụ +6% |
2.12 0.514 0.635 99.06 |
Gafe |
|
6 |
Nnwale voltaji etinyere |
/ |
HV: 34KV 60s LV: 10kV 60s |
Enweghị ọdịda nke voltaji ule a na-eme |
Gafe |
|
7 |
Nnwale Nkwụghachi Voltaji butere |
/ |
Voltaji etinyere (KV): 2 Ua Ogologo oge (s): 48 Ugboro (HZ): 150 |
Enweghị ọdịda nke voltaji ule a na-eme |
Gafe |
|
8 |
Ntụle Nguzogide mkpuchi |
GΩ |
HV -LV gaa n'ala LV-HV gaa n'ala HV&LV ruo Ground |
80.8 63.2 59.7 |
Gafe |
|
9 |
Ule ntapu |
/ |
Ntinye nrụgide: 20kPA Ogologo oge: 12h |
Enweghị ntapu na mba Mmebi |
Gafe |
|
10 |
Nnwale Dielectric mmanụ |
kV |
Karịrị ma ọ bụ hà nhata 45 |
56.96 |
Gafe |


04 Mbukota na mbupu
4.1 mbukota
A na-akwakọba otu {{0}Pasese- transformer n'ime igbe osisi siri ike, iru mmiri{2}}, echekwara ya n'ime ya site na bolts na ụfụfụ na-ekpuchi ya. A na-ekechi ite agba ahụ na ihe nkiri mgbochi{4} static ma dokwa ya n'ebe dị mma n'elu ma ọ bụ n'akụkụ ihe ngbanwe. A na-ekechi akwa ahụ niile na mpempe mmiri nke PVC, yana okpomoku{6}} akwachie akwa na akụkụ apịaji n'okpuru maka mgbochi mmiri ozuzo. Akara mpụga gụnyere akara-nke{9}}ike ndọda, akara ngosi mmiri ozuzo, na ịdọ aka ná ntị ihe nwere ike ire ọkụ. Oghere forklift na eriri igwe na-ewusi ntọala maka njem nchekwa.

4.2 Mbupu

N'okpuru usoro CIF na Georgetown, Guyana, onye na-ere ahịa na-ahazi ụgbọ njem dị n'ime ala, ibu oké osimiri na mkpuchi maka okporo osisi - rịgoro n'elu, bụ nke a ga-ejupụta na ihe na-adịghị emetụ n'ahụ na mmiri- (ya na ndị na-ehicha ihe ma ọ bụrụ na ọ dị mkpa). N'ihi na mmanụ - juru eju, ihe ngbanwe na-achọ nkwupụta ibu dị ize ndụ (MSDS nyere). Onye na-azụ ahịa na-ejikwa ikike mbubata na mbubata n'ime ala, na-achọpụta ikike ebuli Port of Georgetown na oke ibu ụzọ. Oge mbufe bụ ụbọchị 35-50; akwụkwọ ndị bụ isi gụnyere B/L, akwụkwọ ọnụahịa azụmahịa, ndepụta nkwakọ ngwaahịa, amụma mkpuchi, na COO (dịka ọmụmaatụ, Ụdị E).
05 Saịtị na nchịkọta
Otu {{0}pole nke usoro{{1} nrụgidere ngbanwe pụtara dị ka ihe ngwọta dị mma maka netwọk ikesa ike, na-enye arụmọrụ dị elu, nhazi kọmpat, yana nrụnye dị mfe. Anyị na-agba mbọ na-ebuga ngwaahịa ndị a pụrụ ịdabere na ya na nke na-adịgide adịgide, na-akwado site na njikwa mma siri ike na nkà na ụzụ ọhụrụ iji hụ na arụmọrụ kwụsiri ike na gburugburu dị iche iche. Site n'ịhọrọ transformers anyị, ị ga-enweta mmesi obi ike na arụmọrụ pụrụ iche na nkwado zuru oke mgbe{4}}nkwado ọrịre gasịrị, na-enye sistemu ike gị ike na nchekwa na arụmọrụ. Anyị na-atụ anya ka gị na gị na-emekọ ihe iji wuo ọdịnihu ike ka mma!

Ihe nchịkọta dị ọkụ: otu akụkụ okporo osisi mounted nkesa transformer, nrụpụta, soplaya, price, efu
You Might Also Like
50 kVA Utility Pole Transformers-34.5 / 0.12 * 0.24 ...
167 kVA Pole nkesa ntụgharị-14.4 / 0.6 kV|Canada 2024
100 kVA Ntugharị Ogwe Ntugharị-13.8 / 0.24 kV|Guyana...
37.5 kVA Ogwe Ntugharị-2.4 / 0.12 kV|Canada 2025
75 kVA Utility Transformer-24.94 / 0.12 kV|Canada 2025
75 kVA Pole Ụdị ntụgharị-34.5 / 0.12 * 0.24 kV|Canad...
Zipu ozi