75 kVA Utility Transformer-24.94 / 0.12 kV|Canada 2025
Ike: 75 kVA
Voltaji: 24.94GrdY/14.4-0.12/0.24kV
Njirimara: ya na IFD

01 Izugbe
1.1 Ihe ndabere oru ngo
N'afọ 2025, a75 kVA otu -osisi n'usoro{2}} n'agbanyere ngbanwee zigara Canada maka ọrụ nkesa n'elu. Emebere ya na mpaghara ime obodo dị jụụ iji zụọ ọtụtụ ụlọ na obere azụmaahịa mpaghara site na ahịrị 14.4 kV. Mpaghara ahụ na-echekarị oyi na-atụ oyi na oke mmiri mberede, yabụ na igwe ngbanwe ihe dị 75 kVA kwesịrị ịdị ike nke ukwuu iji mee ka ike kwụsie ike n'agbanyeghị ihu igwe.
Ngalaba ahụ na-agbaso ụkpụrụ CSA C2.2{9}}06 ma na-agba na 24.94GrdY/14.4 kV ruo 120/240 V, 60 Hz. Ọ na-eji ONAN jụrụ oyi na aluminom windings, yana mgbochi 3% maka ụkpụrụ voltaji siri ike. Enweghị - ihe na-agbanwe ihe mgbata (± 2×2.5%) na-eme ka ọ dị mfe imezi{17}}imezi mmepụta mgbe achọrọ ya. Site na mfu nke 141 W yana mfu nke 1,160 W, transformer na-arụ ọrụ nke ọma n'iji ya eme ihe kwa ụbọchị{18}.
Ọ na-abịakwa na nkwado njide abụọ na onye nchọpụta ihe kpatara nsogbu (IFD) nke na-enye mgbaama anya ngwa ngwa ma ọ bụrụ na ihe ọ bụla na-adaba n'ime, ya mere ndị ọrụ nlekọta nwere ike ime ihe ozugbo. Kọmpat, siri ike ma dị mfe iji wụnye, ihe ngbanwe akụrụngwa a dabara nke ọma na mpaghara ebe obibi, netwọk ime obodo, na sistemụ ọkụ ọha, na-ebuga ike nchekwa na ntụkwasị obi n'ofe Canada.
1.2 Nkọwa nka nka
75 kVA okporo osisi n'ịnyịnya utility transformer ụdị na data mpempe akwụkwọ
|
Enyere ya
Canada
|
|
Afọ
2025
|
|
Ụdị
Mkpanaka n'agbanyeghi
|
|
Ọkọlọtọ
CSA C2.2-06
|
|
Enyere ike
75 kVA
|
|
Ugboro ugboro
60HZ
|
|
Usoro
1
|
|
Ọnụọgụ nke ikuku
2
|
|
Polarity
Ihe mgbakwunye
|
|
Ụdị oyi
ONAN
|
|
Voltaji nke mbụ
24.94GrdY/14.4 kV
|
|
Voltaji nke abụọ
120/240 kV
|
|
Ngwa ikuku
Aluminom
|
|
Ntugharị akụkụ
Ii6
|
|
Mgbochi
3%
|
|
Pịa Changer
NLTC
|
|
Ọkụ aka
±2*2.5%
|
|
Enweghị mfu ibu
141 kW
|
|
Na Ibu Mfu
1160 kW
|
|
Ngwa ngwa
Nkwado njide 1 & IFD 1
|
1.3 Eserese
75kVA okporo osisi agbakwunyere ihe ngbanwe ihe osise na nha.
![]() |
![]() |
02 Nrụpụta
2.1 Isi
Utility transformer core nakweere nhazi isi ọnya dị elu{0}, na-eme ka sekit magnetik kọmpat yana mbelata mfu. Nrụpụta nkenke na silicon steel lamination na-arụpụta ezigbo arụmọrụ{2}}ọ dịghị- ibu mfu tụrụ na 0.128 kW (nke a tụrụ), 0.145 kW (voltaji 105%), na mkpali dị ugbu a dị obere ka 0.18%, na-egosi arụmọrụ pụtara ìhè.

2.2 Ikuku

Ihe ngbanwe ngwa ngwa 75 kVA na-ewere usoro abụọ-ikuku, otu{2}} nwere polarity mgbakwunye (vector group Ii6). Igwe ikuku - voltaji dị ala na-eji foil aluminom, na-enye ọmarịcha mkpirisi ike mkpirisi na ikpo ọkụ, ebe ọ na-ahụkwa na owuwu dị fechaa. A na-eji waya okirikiri ọla kọpa mee ikuku-voltaji dị elu, na-eme ka omume dị elu, ike igwe, na nkwụsi ike ọkụ ruo ogologo oge- ntụkwasị obi.
2.3 tank
A na-eji ihe niile dị na tank mmanụ emepụta ihe<1mm tolerance, using flat, rust-free steel plates that meet national standards. Welds are continuous, clean, and defect-free. Inner and outer splatter is thoroughly removed, especially around radiator bases and lifting lugs. Each transformer tank undergoes a 12-hour airtight test at 20kPa, ensuring no leakage. Structural strength and sealing performance meet or exceed quality requirements.

2.4 Mgbakọ ikpeazụ

1. Nkwadebe
Hichaa ebe ahụ wee lelee ihe niile: isi ọnya, mkpuchi HV/LV, tank na ngwa.
2. Core & Coil Assembly
Kpọkọtanụ isi na eriri igwe, wụnye ihe mkpuchi, jikọọ na mgbanaka mgbanaka na bushes, wee chekwaa ya na mgbachi.
3. Ịkwọ ụgbọ mmiri
Debe akụkụ ahụ a mịrị amị na-arụ ọrụ n'ime tank ma dozie ya na bọtịnụ ntọala.
4. Ihe mkpuchi mkpuchi & Ngwa
Wụnye gaskets, mkpuchi, na ngwa (ọkwa aha, PRD, IFD, ndị njide), wee jikọọ ụzọ dị n'ime.
5. Mgbochi mmanụ na-ekpo ọkụ
Tinye oghere dị elu iji wepụ mmiri/gas, wee jupụta na mmanụ mkpuchi ma gbanye.
6. Akara & Nnwale
Mee nnwale ikuku nke awa 12, 20kPa. Gbanwee mmanụ ma mee ule eletrik niile oge niile.
7. Mmecha & mbukota
Dị ọcha, agba, mechie, wụnye ihe nchekwa, tinye efere aha, na mkpọ maka nchekwa.
03 Nnwale

Nnwale oge niile
1. Ntụle Nguzogide
2. Nnwale oke
3. Nnwale polarity
4. Ọ dịghị ibu efu na ọ dịghị ibu ugbu a
5. Ibu Ibu na Voltage Mgbochi
6. Nnwale voltaji etinyere
7. Nnwale anabatara voltaji
8. Ntụle Nguzogide mkpuchi
9. Nnwale ntanye na nrụgide maka mgbanwe mgbanwe mmiri mmiri
10. Nnwale mmanụ
Ọkọlọtọ nnwale
CSA C2.2-06(R2022) Single-usoro na atọ- ihe ngbanwe nkesa mmiri juru na agba
CSA C802.1-13(R2022) ụkpụrụ arụmọrụ kacha nta maka ihe nkesa nkesa mmiri mmiri juru.
Nsonaazụ ule
|
Mba. |
Nwale ihe |
Nkeji |
Ụkpụrụ nnabata |
Ụkpụrụ ndị atụtara |
Mmechi |
|
1 |
Ntụle Nguzogide |
/ |
/ |
/ |
Gafe |
|
2 |
Nlele oke |
/ |
Ngbanwe nke oke voltaji na ọpịpị bụ isi: Ihe na-erughị ma ọ bụ haha 0.5% Akara njikọ: ii6 |
-0.02 |
Gafe |
|
3 |
Nnwale polarity |
/ |
Ihe mgbakwunye |
Ihe mgbakwunye |
Gafe |
|
4 |
Ọ dịghị - ibu mfu na mkpali ugbu a |
% |
I0 :: nye uru atụpụtara (100%) |
0.18 |
Gafe |
|
kW |
P0: nye uru tụrụ (100%) |
0.128 |
|||
|
% |
I0 :: nye uru atụpụtara (105%) |
0.37 |
|||
|
kW |
P0: nye uru tụrụ (105%) |
0.145 |
|||
|
/ |
Nkwenye maka enweghị ibu ibu bụ +15% |
/ |
|||
|
5 |
Ngwunye ibu, voltaji impedance, mfu zuru oke na arụmọrụ |
/ |
t:85 ogo Nkwenye maka impedance bụ ± 7.5% Nkwenye maka mkpokọta mfu ibu bụ +8% |
/ |
Gafe |
|
% |
Z%: uru tụrụ |
3.20 |
|||
|
kW |
Pk: uru tụrụ |
1.104 |
|||
|
kW |
Pt: uru tụrụ |
1.232 |
|||
|
% |
Ịrụ ọrụ adịghị erughị 98.94% |
99.00 |
|||
|
6 |
Nnwale voltaji etinyere |
/ |
LV: 10kV 60s |
Enweghị ọdịda nke voltaji ule a na-eme |
Gafe |
|
7 |
Nnwale Iguzogide Voltaji butere |
/ |
Voltaji etinyere (KV):2Ur |
Enweghị ọdịda nke voltaji ule a na-eme |
Gafe |
|
Ogologo oge (s):48 |
|||||
|
Ugboro (HZ): 150 |
|||||
|
8 |
Ntụle Nguzogide mkpuchi |
GΩ |
LV-HV gaa n'ala |
3.64 |
Gafe |
|
9 |
Ule ntapu |
/ |
Ntinye nrụgide: 20kPA |
Enweghị ntapu na mba Mmebi |
Gafe |
|
Ogologo oge: 12h |
|||||
|
10 |
Nnwale mmanụ |
kV |
Ike Dielectric |
54.8 |
Gafe |
|
mg/kg |
Ọdịnaya Ọdịnaya |
9.5 |
|||
|
% |
Ihe nchụsa |
0.00237 |
|||
|
mg/kg |
Nyocha nke Furan |
0.03 |
|||
|
/ |
Nyocha chromatography gas |
/ |
04 Mbukota na mbupu


05 nwụnye chọrọ
Nchekwa dị n'osisi -Nwụnye Transformer
Nchekwa abụghị naanị iwu - ọ bụ mmalite nke ihe niile. Ịwụnye okporo osisi - n'elu ihe ngbanwe pụtara ịrụ ọrụ n'ebe dị elu, ijikwa akụrụngwa dị arọ, na ijikọ eriri ọkụ dị ndụ. Nzọụkwụ ọ bụla na-ebu ihe ize ndụ nke ya. Ọ bụ ya mere na-akpachapụ anya na nhazi na nchekwa anaghị ahọrọ-ha dị mkpa.
Ngwa nchekwa nkeonwe (PPE):
Malite na isi ihe. Okpu agha. uwe aka. Anya igwe. Uwe nchebe. Dị mfe, mana ndụ{5} na-azọpụta. Ịwụpụ ọbụna otu ibe, nanị otu ugboro, nwere ike ịkpata nnukwu nsogbu.
Soro ụkpụrụ nchekwa:
Iwu nwere ike iyi ihe siri ike, mana ha dị maka ihe kpatara ya. Edere ahịrị ọ bụla dị na koodu nchekwa mgbe mmadụ merụrụ ahụ. Ịgbaso ụkpụrụ nwere ike ịdị gị nwayọ, mana ọ bụ ụzọ kachasị ọsọ iji gbochie ihe mberede.
Ọzụzụ kwesịrị ekwesị:
Ọzụzụ na-ewulite ntụkwasị obi{0} ma na-azọpụta ndụ. Otu a zụrụ nke ọma{2} maara ihe ha ga-eme, ọbụlagodi mgbe ihe na-adaghị. Ha na-emeghachi omume ngwa ngwa, nọrọ jụụ, na-ejikwa njikwa. Nke ahụ na-eme mgbanwe niile.
Nyocha akụrụngwa:
Lelee ihe niile. Cable, nko na ihe mkpuchi. Eriri rụrụ arụ ma ọ bụ waya gbajiri agbaji nwere ike ịdị obere, mana ọ nwere ike ịgbanwe ihe niile. Nkeji ole na ole nke nyocha na-echebe awa ọrụ nchekwa.
Ihe ịrịba ama ịdọ aka ná ntị na mgbochi:
Kaa mpaghara ahụ akara. teepu na-egbuke egbuke, ihe ịrịba ama doro anya, ihe mgbochi siri ike. Ha na-echekwa ndị na-ekiri ihe nchebe ma na-echetara ndị ọrụ ka ha mụrụ anya. Mmata dị jụụ, mana ọ na-echebe onye ọ bụla.
06 Saịtị na nchịkọta
Nke a 75kVA otu -Ogwe osisi - mgbakwasa transformer bụ ebumnuche{3}} ewuru iji gboo mkpa nke netwọk nkesa North America, na-akwado nke ọma na ụkpụrụ CSA C2.2-06. Emebere ya maka ngwa n'elu, ọ na-ewepụta mmepụta 0.347 kV kwụsiri ike site na ntinye 24.94GrdY/14.4 kV-nke dị mma maka ọkụ ọkụ azụmahịa, ọkọnọ ike ụlọ ọrụ na sistemụ nkesa obodo.
Site na nju oyi ONAN siri ike, ikuku aluminom/ọla kọpa a pụrụ ịdabere na ya, yana njiri nchekwa agbakwunyere dị ka Internal Fault Detector (IFD), ihe ngbanwe a na-ahụ maka nchekwa, obere ọrụ nlekọta{{0}. Ogwe kọmpat - agbakwunyere nrụnye na-eme ka nrụnye dị mfe, na-ebelata mkpa oghere, ma na-akwado imelite grid nke ọma.
Ma ebusara ya maka nkwalite okporo osisi bara uru, sistemu ọkụ ọha, ma ọ bụ mgbasawanye akụrụngwa, ihe ngbanwe akụrụngwa a na-enye ihe a pụrụ ịdabere na ya na ọnụ ahịa{0} dị irè maka ịkwalite nrụpụta ike na nkwụsi ike na gburugburu azụmahịa Canada.

Ihe nchịkọta dị ọkụ: Utility transformer, emeputa, soplaya, price, efu
You Might Also Like
75 kVA Transformer Na eriri ọkụ-12.4 * 24.94 / 0.12 ...
50 kVA Transformer Utility Pole-13.8 / 0.24 kV|Guyan...
500 kVA Ogwe Ntugharị Ntugharị-24.94 / 0.6 kV|Canada...
167 kVA Pole Nkwanye nkesa nkesa-24.94 / 0.12 / 0.24...
50 kVA Transformer Na Ogwe Ike-7.97 / 0.12 / 0.24 kV...
100 kVA Pole Ugwu Ntugharị-24.94 / 0.347 kV|Canada 2024
Zipu ozi