50 kVA Single Phase Pad Nkwanye Transformer-24 / 0.24 kV|Jamaica 2024

50 kVA Single Phase Pad Nkwanye Transformer-24 / 0.24 kV|Jamaica 2024

Obodo nzipu: Jamaica 2024
Ike: 50kVA
Voltaji: 24GrdY/13.8-0.24/0.12 kV
Njirimara: Onye njide ịwa ahụ
Zipu ozi

 

 

50 kVA single phase pad mounted transformer

Na-ebunye ndị obodo ike kwụsiri ike n'otu oge ọ bụla na-etinye ihe nkwụnye ọkụ

 

 

01 Izugbe

1.1 Nkọwa oru ngo

N'afọ 2024,scotechewepụtara 10 nkeji nke 50 kVAotu - pad phase {{1} agbakwunyere ngbanwenye onye ahịa na Jamaica. Emebere ma wuo ihe ngbanwe ọ bụla ka ọ dabara ụkpụrụ IEEE. Ha na-enye arụmọrụ a pụrụ ịdabere na ya na ogologo ndụ ọrụ.

Ha na-eje ozi dị ka ndị na-eme mgbanwe{{0}voltaji nkesa n'ime sistemụ nkesa ike n'okpuru ala. Ejiri voltaji ikuku nke isi nke 24GrdY / 13.8 kV yana voltaji ikuku nke abụọ nke 0.24 / 0.12 kV, na-enye 50 kVA nke ike mmepụta.

Ndị nwụrụ anwụ{{0}transformers n'ihu na-egosipụta njikọ eletrik na ihe mejupụtara ya nke ọma, na-enweghị akụkụ ndụ ma ọ bụ ọnụ ụzọ ekpughere mgbe emepere ụzọ. Nhazi loop{2}} na-akwalite nchekwa, ntụkwasị obi na mgbanwe na netwọkụ nkesa.

Ejiri igwe mkpuchi ọla kọpa wuo 50 kVA otu pad pad na-agbanye n'ọkụ maka ịrụ ọrụ eletrik siri ike. Ihe ngbanwe ahụ nwere sistemu jụrụ oyi nke ONAN nke ọma, nke ejiri mmanụ ịnweta mmanụ dị elu- na ọkwa PCB dị ala gbakwunyere, si otú a na-ahụ na ọrụ adịghị mma na gburugburu ebe obibi. Ọzọkwa, uru mfu - na-anọgide n'okpuru 0.35 kW, yana uru mfu - anaghị agafe 0.13 kW.

Banyere usoro nchebe, ndị a na-agbanwe agbanwe nwere bayonet fuse, fuse na-egbochi ugbu a (CLF), na ngwaọrụ enyemaka nrụgide. Akụkụ ndị a na-enye nchebe pụọ na nfefe ma na-ebelata ohere nke mmebi site na sekit dị mkpirikpi ma ọ bụ mmejọ ndị ọzọ.

 

 

 

1.2 Nkọwa nka nka

50 kVA otu pad pad na-agbanye nkọwapụta na mpempe data

Enyere ya
Jamaica
Afọ
2024
Ụdị
Otu akụkụ mpe mpe akwa ugwu transformer
Ọkọlọtọ
IEEE Std
Enyere ike
50kVA
Ugboro ugboro
50HZ
Nri
Loop
N'ihu
Nwụrụ anwụ
Ụdị oyi
ONAN
Ihe mgbochi mmiri
Mineral Mmanụ
Voltaji nke mbụ
24GrdY/13.8
Voltaji nke abụọ
0.24/0.12 KV
Otu Vector
Ii0
Polarity
Mwepu
Ngwa ikuku
Ọla kọpa
Mgbochi
4%
Pịa Changer
NLTC
Ọkụ aka
±2*2.5%
Enweghị mfu ibu
0.13 kW
Na Ibu Mfu
0.35 kW
Ngwa ngwa
IFD, onye njide ịwa ahụ

 

 

1.3 Eserese

50kVA otu pad na-etinye ihe ngbanwe na eserese na aha aha

50 kVA single phase pad mounted transformer drawing 50 kVA single phase pad mounted transformer nameplate

 

 

02 Nrụpụta

2.1 Isi

A ga-akụchi ma kwadoo cores iji guzogide mgbagha kpatara nrụgide mkpirisi mkpirisi mkpirisi ma ọ bụ njikwa njem na iji gbochie mgbanwe nke isi laminations.
A ga-eji gade dị elu wuo kọlụm{0}, ọka gbakwasara ala, lamination steel silicon steel lamination nke oyi, nwere ikike ndọta dị elu. Isi ihe owuwu ga-agụnye ndokwa na-ebelata isi mfu, ọkwa mkpali ugbu a na mkpọtụ mkpọtụ.

50kVA-single-phase-pad-mounted-transformer-iron-core-grain-oriented-cold-rolled-silicon-steel

 

2.2 Ikuku

Anyị 50 kVA otu pad na-enyanye ihe ntụgharị windings na-eji elu{1}} ịdị ọcha enamed gburugburu waya ọla kọpa, na-egosipụta ọmarịcha ọkụ eletrik yana mkpuchi kọmpat. Mgbakwunye enamel siri ike na-eme ka ịdịte aka ma na-eyi nguzogide.
Ụdị waya a bụ nke a na-eji n'ọtụtụ ebe n'obere ma ọ bụ nke na-ajụ - ndị na-agbanwe agbanwe na ngwaọrụ eletrọnịkị n'ihi mgbanwe ya, ịdị mfe nke ikuku, yana ọnụ ahịa ya- ịrụ ọrụ nke ọma.

50kva single phase pad mounted transformer-copper-wire-winding

 

2.3 tank

50kva single phase pad mounted transformer-mild-steel-oil-tank

A na-eji ígwè dị nro rụọ ebe nchekwa niile ma nwee ntụ ntụ{0}} iji nye elu na-adịgide adịgide ma na-emebi emebi{1}. A ga-etinye tray a kapịrị ọnụ, nke emebere iji jide 100ml nke mmiri na-ekpuchi mmiri ma gbochie mmiri ahụ ịfesa na mgbidi tank ma ọ bụ n'elu ngwa, n'okpuru ebe fuse ọ bụla nwere ike iwepụ. Scotechmpe mpe akwa - n'agbanyeghi ihe ngbanwena-anagide ma ọnyà na ihu igwe siri ike, na-eme ka ha dị mma maka ntinye na mpaghara ọha.

 

2.4 Mgbakọ ikpeazụ

A ga-echekwa ihe ngbanwe a site na sistemu nchekwa fuse abụọ- nwere mmanụ bayonet{1}}emikpu, fuse nchụpụ n'usoro jiri mmanụ-emikpu, akụkụ akụkụ{3}oke, nke dị ugbu a- na-egbochi fuse. Njikọ Bayonet fuse ga-ahụ ma nnukwu mmiri mmiri na oke mmanụ ọkụ iji nye nchebe ọkụ na transformer.
Hazie nchedo transformer site na iji fiusi mwepu na-ekpochapụ obere- mmejọ dị ugbu a yana{1}} na-amachi mmejọ fiusi dị elu{2}} dị ugbu a karịa ọkwa nkwụsị nke fiusi nchụpụ. Iji kpochapụ ma ọ bụ ibelata mwụfu mmanụ, mgbakọ bayonet fuse ga-agụnye valvụ njide mmanụ n'ime ụlọ nke na-emechi mgbe ewepụsịrị fuse, na ọta ntapu nke mpụga. Nhazi n'ozuzu nke nkwụsị ibu na ngwaọrụ nchebe ga-ekwe ka nri akaghị aka na transformer ma gbochie mmechi nke ngbanwe na mmejọ nke ime.

50 kVA single phase pad mounted transformer active part

 

 

03 Nnwale

Nnwale oge niile

1. Ntụle Nguzogide

2. Nnwale oke

3. Nnwale polarity

4. Ọ dịghị ibu efu na ọ dịghị ibu ugbu a

5. Ibu Ibu na Voltage Mgbochi

6. Nnwale voltaji etinyere

7. Nnwale anabatara voltaji

8. Ntụle Nguzogide mkpuchi

9. Nnwale ntanye na nrụgide maka mgbanwe mgbanwe mmiri mmiri

10. Oil Dielectric Test

 

50 kVA single phase pad mounted transformer leak testing
50 kVA single phase pad mounted transformer testing

 

Nsonaazụ ule

Mba.

Nwale ihe

Nkeji

Ụkpụrụ nnabata

Ụkpụrụ ndị atụtara

Mmechi

1

Ntụle Nguzogide

/

/

/

Gafe

2

Nlele oke

/

Ngbanwe nke oke voltaji na ọpịpị bụ isi: Ihe na-erughị ma ọ bụ haha ​​0.5%

Akara njikọ: ii0

A: -0.05

B: -0.05

Gafe

3

Nnwale polarity

/

Mwepu

Mwepu

Gafe

4

Ọ dịghị - ibu mfu na mkpali ugbu a

%

kW

I0 :: nye uru a tụrụ atụ

P0: nye uru a tụrụ atụ

nnabata maka enweghị ibu ibu bụ +10%

0.24

0.099

Gafe

5

Ibu efu na voltaji impedance

/

kW

kW

t:85 ogo

Z%: uru tụrụ

Pk: uru tụrụ

Pt: uru tụrụ

nnabata maka impedance bụ ± 7.5%

Nkwenye maka mkpokọta mfu ibu bụ +6%

3.71

0.330

0.429

99.31

Gafe

6

Nnwale voltaji etinyere

/

LV: 10kV 60s

Enweghị ọdịda nke voltaji ule a na-eme

Gafe

7

Nnwale Iguzogide Voltaji butere

/

Voltaji etinyere (KV):

2 Ua

Ogologo oge (s):40

Ugboro (HZ): 150

Enweghị ọdịda nke voltaji ule a na-eme

Gafe

8

Ntụle Nguzogide mkpuchi

LV-HV gaa n'ala

33.9

/

9

Ule ntapu

/

Ntinye nrụgide: 20kPA

Ogologo oge: 12h

Enweghị ntapu na mba

Mmebi

Gafe

10

Nnwale Dielectric mmanụ

kV

Karịrị ma ọ bụ hà nhata 45

60.4

Gafe

 

 

04 Mbukota na mbupu

4.1 mbukota

1. Osisi crate Packaging: Transformers na-emekarị ngwugwu na sturdy osisi crates, nke ọma na-echebe megide mpụga nrụgide n'oge njem. A na-ejikarị ụfụfụ ma ọ bụ sponge kpuchie ime nke akpa ahụ iji nweta mmetụta.

2. Ihe ndị na-egbochi mmiri: Nkwakọ ngwaahịa mmiri na-adịghị mkpa karịsịa n'oge njem ụgbọ mmiri. A na-ejikarị ihe nkiri na-adịghị ekpuchi mmiri ma ọ bụ mmiri kpuchie ndị na-eme mgbanwe{2} iji gbochie iru mmiri na ncha n'oge njem.

3. Akụrụngwa Nkwalite: A na-eji ígwè ígwè ma ọ bụ okpokolo agba na-eme ka ndị na-eme mgbanwe dị nro dịkwuo mma iji gbochie mmebi site na nkukota na ịkụpịa n'oge njem.

4. Labeling and Labeling: A ga-edobe nkwakọ ngwaahịa ahụ na akara mbupu ama ama, dị ka "Fragile," "Arọ," ma ọ bụ "Nọgide na-eguzo ọtọ," iji chetara ndị na-ebu ụgbọ ala ka ha jiri nlezianya mee ihe.

50 kVA single phase pad mounted transformer packing

 

4.2 Mbupu

50 kVA single phase pad mounted transformer shipping

1. Nbudata na nbudata: A na-eji ngwá ọrụ na-ebuli elu na-eme ka ọ bụrụ na ọ dịghị ihe ọzọ na-arụ ọrụ n'oge a na-ebufe ihe ntụgharị.

2. Edoziri: N'oge njem, ọ dị mkpa ka a dozie ihe ntụgharị ahụ nke ọma iji gbochie nkwụsị ma ọ bụ nkukota, na-akpata mmebi ígwè.

3. Nchedo: Ọ dị mkpa ka e mee ihe iji kpuchido akụkụ mkpuchi nke transformer na ihe dị n'èzí iji gbochie mmetọ ma ọ bụ mmebi.

 

 

05 Saịtị na nchịkọta

Nke a 50kVA otu pad na-ekunye ihe ngbanwe bụ nke ejiri ọla kọpa windings na tankị ígwè siri ike mee. Isi ihe na-eji ígwè silicon dị elu{2}ọkwa, nke na-eme ka mfu na mkpọtụ dị ala. Usoro jụrụ oyi nke ONAN na mmanụ ịnweta mmanụ na-enyere ngalaba ahụ aka ịgba ọsọ n'enweghị nsogbu ma dị ogologo.

O nwere ihe nwuru anwu{0}} n'ihu, loop{1}} nhazi ndepụta. Ngalaba ahụ nwere fuses, ngwaọrụ enyemaka nrụgide, ma nwee ike ịgụnye akụkụ ndị ọzọ dị ka ndị na-ejide ịwa ahụ na ihe nchọpụta mmejọ. Ndị a na-enye nchebe dị mma megide mmejọ ma mee ka unit ahụ bụrụ nke a pụrụ ịdabere na ya.

Ihe ngbanwe a dị mma, siri ike na nke ọma. Ọ na-enye ụlọ na azụmaahịa dị na Jamaica ike na-adịgide adịgide. Ọ bụ ezigbo nhọrọ maka iji ike ogologo oge-.

50kva single phase pad mounted transformer-left-view

 

Ihe nchịkọta dị ọkụ: otu nkeji mpe mpe akwa akwanye transformer, onye nrụpụta, onye na-eweta, ọnụahịa, ọnụ ahịa