75 kVA Powerline Transformer-13.8 / 0.24 kV|Guyana 2025
Ike: 75kVA
Voltaji: 13.8kV-240/120V

01 Izugbe
1.1 Ihe ndabere oru ngo
N'ịzaghachi maka mkpa ume na-eto eto n'ime ime obodo na peri{0}} obodo Guyana, onye ahịa anyị debere 2025 - n'usoro maka nkeji iri atọ nke 75 kVA otu -osisi prọfesọ- na-agbanye mgbanaka. Usoro a na-ewulite n'ịzụta mbụ nke ụdị kVA 50 wee gosipụta mkpa ha nwere maka ngwa ike dị elu{9} iji kwado mgbasawanye ebe obibi, mmepe ugbo, na ọrụ ime ọkụ ime obodo. Njikọ aka na-aga n'ihu na-egosi ntụkwasị obi etinyere na ngwaahịa anyị iji wepụta ngwọta nkesa ike kwụsiri ike na nke ọma.
A na-ewu ihe ngbanwe ọkụ eletrik 75 kVA ndị a na ụkpụrụ IEEE & ANSI C57.12.00, na-egosipụta voltaji bụ isi nke 13,800 V na nke abụọ nke abụọ nke 120/240 V, na ikuku ọla kọpa, 2% impedance, yana ± 2 × 2.5% enweghị- ngbanwe mgbanwe mgbanwe ọkụ maka voltaji. Na-arụ ọrụ na 60 Hz na ONAN jụrụ oyi, ha dabara nke ọma maka ịgbago n'osisi nkesa na mpaghara nwere akụrụngwa na-agbasawanye yana ohere dị nta na ọdụ ụgbọ ala.
1.2 Nkọwa nka nka
75kVA powerline transformer nkọwa na mpempe akwụkwọ data
|
Enyere ya
Guyana
|
|
Afọ
2025
|
|
Ụdị
Otu akụkụ okporo osisi etinyere ngbanwe
|
|
Ọkọlọtọ
IEEE & ANSI C57.12.00
|
|
Enyere ike
50 kVA
|
|
Ugboro ugboro
60HZ
|
|
Polarity
Mwepu
|
|
Otu vector
Ii0
|
|
Voltaji nke mbụ
13800V
|
|
Voltaji nke abụọ
120/240V
|
|
Ngwa ikuku
Ọlapa
|
|
Mgbochi
2%
|
|
Usoro jụrụ oyi
ONAN
|
|
Pịa Changer
NLTC
|
|
Ọkụ aka
±2X2.5%(Ngụkọta oke=10%)
|
|
Enweghị mfu ibu
214W
|
|
Na Ọnwụ Ebu
713W
|
|
Ngwa ngwa
Nhazi ọkọlọtọ
|
1.3 Eserese
75kVA powerline transformer akụkụ na nkọwa ibu

02 Nrụpụta
2.1 Isi
Iji kwalite arụmọrụ ike yana ntụkwasị obi arụ ọrụ, usoro usoro a na-anakwere ike{0}} na-echekwa ọnya ọnya mara maka mfu dị ala, mkpọtụ dị ala, na ịdịte aka. A na-ekpuchi isi elu maka mgbochi - mmiri na mgbochi - nchedo corrosion, na-eme ka arụmọrụ kwụsiri ike na gburugburu mpụga.

2.2 Ikuku

Igwe ikuku HV na-anakwere teknụzụ foil ọla kọpa iji belata mwepu akụkụ ma melite mgbasa ọkụ. A na-eji waya ọla kọpa emechiri emechi emechi nke LV nke nwere akwa siri ike iji bulie ike igwe. Nhazi eriri igwe anyị na-ebute ihe mkpuchi mkpuchi na arụmọrụ ọkụ maka ogologo oge{2}} ntụkwasị obi n'èzí.
2.3 tank
Ụgbọ mmiri ahụ nwere ihe eji eme ihe nke na-agafe ule nyocha siri ike iji hụ na a na-ekpuchi ya nke ọma, na-egbochi nkwụsị mmanụ na mmiri mmiri. Emere ya site na nchara dị nro nke nwere mkpuchi agba epoxy, ọ na-enye nkwalite nguzogide corrosion. Ejiri radiators corrugated n'akụkụ abụọ ahụ, tank ahụ na-eme ka nrụpụta ọkụ na-arụ ọrụ nke ọma, na-eme ka ọrụ ntụgharị kwụsiri ike.

2.4 Mgbakọ ikpeazụ

Mgbakọ ikpeazụ na-amalite site n'itinye isi ọnyá na mkpuchi n'ime tank ahụ mechiri emechi ma jupụta na mmanụ mkpuchi. A na-atụkwasị ihe ndị dị na mpụga- gụnyere bushes, valvụ enyemaka nrụgide, onye na-agbanwe mgbata, akụkụ ala, na ntù jụrụ oyi{2}}. A na-ehicha akụkụ ahụ, na-enyocha elu elu, wee nyochaa akara, ọnụ ọnụ na data efere aha.
03 Nnwale
Nnwale oge niile
1. Ntụle Nguzogide
2. Nnwale oke
3. Nnwale polarity
4. Ọ dịghị ibu efu na ọ dịghị ibu ugbu a
5. Ibu Ibu na Voltage Mgbochi
6. Nnwale voltaji etinyere
7. Nleba anya na-eguzogide voltaji
8. Ntụle Nguzogide mkpuchi
9. Oil Dielectric Test
10. Nnwale ntanye na nrụgide maka mgbanwe mgbanwe mmiri mmiri


Ọkọlọtọ nnwale
• IEEE C57.12.20-2017
IEEE Standard maka n'elu -Ụdị nkesa nkesa 500 kVA na nta; Voltaji dị elu, 34500 V na N'okpuru; Voltaji dị ala, 7970/13 800YV na N'okpuru
• IEEE C57.12.90-2021
IEEE Standard Test Code maka Liquid -Nkesa, Ike, na Ngbanwe Nhazi
• CSA C802.1-13 (R2022)
Uru arụmọrụ kacha nta maka Liquid{0}}Mgbanwe nkesa juputara
Nsonaazụ ule nke otu okporo osisi - rịgoro ngbanwe site na batch 30-unit
|
Mba. |
Nwale ihe |
Nkeji |
Ụkpụrụ nnabata |
Ụkpụrụ ndị atụtara |
Mmechi |
|
1 |
Ntụle Nguzogide |
/ |
/ |
/ |
Gafe |
|
2 |
Nlele oke |
/ |
Ngbanwe nke oke voltaji na ọpịpị bụ isi: Ihe na-erughị ma ọ bụ haha 0.5% Akara njikọ: ii0 |
-0.06 |
Gafe |
|
3 |
Nnwale polarity |
/ |
Mwepu |
Mwepu |
Gafe |
|
4 |
Ọ dịghị - ibu mfu na mkpali ugbu a |
% kW |
I0 :: nye uru a tụrụ atụ P0: nye uru a tụrụ atụ nnabata maka enweghị ibu ibu bụ +10% |
1.66 0.185 |
Gafe |
|
5 |
Ibu ibu, voltaji impedance, ngụkọta ọnwụ na arụmọrụ |
/ kW kW |
t:85 ogo Z%: uru tụrụ Pk: uru tụrụ Pt: uru tụrụ nnabata maka impedance bụ ± 10% Nkwenye maka mkpokọta mfu ibu bụ +6% |
2.08 0.714 0.899 99.08 |
Gafe |
|
6 |
Nnwale voltaji etinyere |
/ |
HV: 34KV 60s LV: 10kV 60s |
Enweghị ọdịda nke voltaji ule a na-eme |
Gafe |
|
7 |
Nnwale Nkwụghachi Voltaji butere |
/ |
Voltaji etinyere (KV): 2 Ua Ogologo oge: 40(50HZ)/48(60HZ) Ugboro (HZ): 150 |
Enweghị ọdịda nke voltaji ule a na-eme |
Gafe |
|
8 |
Ntụle Nguzogide mkpuchi |
GΩ |
HV -LV gaa n'ala LV-HV gaa n'ala HV&LV ruo Ground |
101.7 36.1 42.0 |
Gafe |
|
9 |
Ule ntapu |
/ |
Ntinye nrụgide: 20kPA Ogologo oge: 12h |
Enweghị ntapu na mba Mmebi |
Gafe |
|
10 |
Nnwale Dielectric mmanụ |
kV |
Karịrị ma ọ bụ hà nhata 45 |
56.71 |
Gafe |
04 Mbukota na mbupu


05 Saịtị na nchịkọta
Nke a bụ 75 kVA ọkụ eletrik e mere iji gboo mkpa ike na-eto eto n'ime ime obodo na peri{1}} obodo Guyana. Ọ dabara nke ọma{{3} maka ịgbasa akụrụngwa nkesa, ọkụ eletrik na ime obodo na mmepe ọrụ ugbo. Usoro ikwugharị onye ahịa na 2025 na-egosipụta ntụkwasị obi siri ike na nkwụsi ike na arụmọrụ nke ngwaahịa anyị.
N'ikwekọ n'ụkpụrụ North America, usoro ihe ngbanwe a na-enye arụmọrụ ike dị elu yana ngbanwe gburugburu ebe obibi siri ike, na-eme ka ọ dị mma maka itinye n'osisi nkesa na mpaghara ndị dị ala-. Isi ihe na-egosi obere mfu, ike- ịchekwa imewe maka ntụkwasị obi arụ ọrụ ka mma, ebe a na-ahazi usoro eriri igwe maka mkpuchi na mkpofu okpomọkụ, na-ahụ na arụmọrụ kwụsiri ike na ọnọdụ dị n'èzí. Tank a mechiri emechi na-enye ezigbo mgbochi ntapu na nguzogide corrosion, ma nweekwa radiators iji kwalite mma.
Site na imewe lekwasịrị anya na nkwụsi ike ogologo oge na obere mmezi obere{{0}, igwe ọkụ ọkụ a dị mma maka mpaghara nwere oke mkpuchi grid yana ohere ike etiti, na-akwado ọkọnọ na mmepe akụrụngwa n'ime ime obodo na mpaghara na-emepe emepe.

Ihe nchịkọta dị ọkụ: powerline transformer, emeputa, soplaya, price, efu
You Might Also Like
50 kVA Ntugharị Ogwe eletriki-13.8 / 0.347 kV|Canada...
50 kVA Utility Pole Transformers-34.5 / 0.12 * 0.24 ...
167 kVA Pole nkesa ntụgharị-14.4 / 0.6 kV|Canada 2024
167 kVA Cooper Pad Nkwanye ngbanwe-13.8 / 0.24 kV|Gu...
50 kVA Transformer Power Line-13.8 / 0.12 * 0.24 kV|...
50 kVA Transformer Na Ogwe Ike-7.97 / 0.12 / 0.24 kV...
Zipu ozi