50 kVA Single Phase Pad Nkwanye Mgbanwe nkesa -24 * 12 / 0.24 kV|Jamaica 2024
Ike: 50kVA
Voltaji: 24 * 12-0.24 / 0.12kV
Njirimara: ya na voltaji isi abụọ

Otu -Phase Pad-Enyanye Transformer – Kọmpat & Silent, Zuru okè maka grids Obodo!
01 Izugbe
1.1 Nkọwa oru ngo
50 kVA single phase pad mounted mounted transformers na Jamaica n'afọ 2025. Akara ikike nke transformer bụ 50 kVA na ONAN jụrụ oyi. The isi voltaji bụ 24GrdY / 13.8 * 12GrdY / 6.9 kV na ± 2 * 2.5% tapping nso (NLTC), nke abụọ voltaji bụ 0,24 / 0.12 kV, ha guzobere vector otu YNyn0.
Nke a 50 kVA otu -phase pad - nkwụnye mgbanaka ka emebere maka ịrụ ọrụ dị iche iche na ntụkwasị obi na sistemu nkesa voltaji, na-egosipụta 24GrdY/13.8 kV na 12GrdY/6.9 kV nhazi izizi nwere ihe nrụpụta sekọndịrị 0.24/0.12 kV. Sistemu nchekwa ya siri ike na-agụnye fuses bayoneti na nke dị ugbu a{11}} na-amachi fiusi maka nkwusi mmejọ emelitere, yana ndị na-ejide ndị na-awa ahụ iji chebe megide voltaji na-agafe agafe. Ihe nchọta mmejọ nke ime (IFD) na-enye ezigbo{13}}nlebanya oge, ebe igwe ngbanwe ihu igwe{14}} na-enyere ngbanwe enweghị nkebi n'etiti voltaji izizi. Maka mgbanwe ọrụ, mgbanyụ-mgbanwe mgbata okirikiri na-enye ohere mgbanwe voltaji, yana mgba ọkụ nbibi na-ahụ maka ịnọpụ iche n'oge mmezi.
Atụmatụ nchekwa agbakwunyere gụnyere ngwaọrụ enyemaka nrụgide iji belata ihe egwu oke nrụgide dị n'ime yana nlele ọkwa mmanụ maka nlekota mmiri dielectric. Ewubere maka ịdịte aka na ịdị mfe nke nrụzi, ihe ngbanwe a dị mma maka ịba uru, azụmahịa, na ngwa ụlọ ọrụ na-achọ ihe ngwọta nkesa ike na-agbanwe agbanwe.
1.2 Nkọwa nka nka
50 kVA mpe mpe akwa akwadoro ụdị nkọwapụta na mpempe data
|
Enyere ya
Jamaica
|
|
Afọ
2024
|
|
Ụdị
Ihe mgbakwasa na mpe mpe akwa
|
|
Ọkọlọtọ
IEEE StdC57.12.34-2022
|
|
Enyere ike
50 kVA
|
|
Ugboro ugboro
50HZ
|
|
Usoro
1
|
|
Nri
Loop
|
|
N'ihu
Nwụrụ anwụ
|
|
Ụdị oyi
ONAN
|
|
Voltaji nke mbụ
24GrdY/13.8*12GrdY/6.9 kV
|
|
Voltaji nke abụọ
0.24/0.12kV
|
|
Ngwa ikuku
Ọla kọpa
|
|
Ntugharị akụkụ
Ii0
|
|
Mgbochi
4%
|
|
Pịa Changer
NLTC
|
|
Ọkụ aka
±2*2.5%
|
|
Enweghị mfu ibu
0,116 kW
|
|
Na Ibu Mfu
0,445 kW
|
|
Ngwa ngwa
Nhazi ọkọlọtọ
|
1.3 Eserese
50kVA mpe mpe akwa akwadoro eserese eserese na nha.
![]() |
![]() |
02 Nrụpụta
2.1 Isi
Transformer nwere atụmatụ isi ọnya ọnya toroidal dị elu, nke arụrụ ya site na ọnya na-aga n'ihu, nnukwu-permeability, obere-ọka mfu -mkpụrụ osisi silicon ígwè gbadoro ụkwụ ka ọ bụrụ ihe nrụnye na-enweghị nkebi mechiri emechi{3}}. Isi ọnya ahụ na-eji njirimara ntụzịaka ọka nke igwe silicon, na-ahazi ntụzịaka magnetik na ntụgharị ntụgharị, ebe mkpuchi mkpuchi n'elu na-ebelata mfu efu ugbu a. Ọ na-enye uru dị ukwuu, gụnyere enweghị obere ibu- (mbelata 20-30% ma e jiri ya tụnyere cores laminated nke ọdịnala), arụ ọrụ dị jụụ, arụmọrụ dị elu (isi ihe njupụta karịa 95%), yana ike ọrụ dị mma.

2.2 Ikuku

Ihe ngbanwe a na-egosipụta atụmatụ ikuku ngwakọ na-ejikọta obere-voltaji foil na elu{1}} ịrụ ọrụ waya voltaji maka ịrụ ọrụ kacha mma. 0.24/0.12kV dị ala-voltaji winding na-eji foil ọla kọpa dị larịị nke ejiri akwụkwọ mkpuchi kpuchie, na-enye ike mkpirisi dị mkpụmkpụ{6}, mgbasa ọkụ na-arụ ọrụ nke ọma, yana nhazi kọmpat. 24kV/12kV dị elu{10}voltaji winding na-eji waya ọla kọpa okirikiri/rectangular nwere mkpuchi mkpuchi, na-ahụ na nkesa voltaji dị elu, mgbanwe mgbanwe nhazi nke mbu, yana nguzogide mwepu akụkụ. Ngwakọta nke foil ọla kọpa (LV) na waya ọla kọpa (HV) na-eweta arụmọrụ dị elu site na mfu eddy ugbu a, nkwụsi ike n'ụzọ siri ike iji guzogide nrụgide okpomọkụ na mkpụmkpụ{13}, yana oghere{14}}ngwugwu dị mma maka pad{15}} ngwa nkesa etinyere.
2.3 tank
Tank nke ngbanwe ahụ nwere ihe nrụnye agbadoro nke ọma nke arụnyere site na 4-6mm dị elu-ezigbo igwe dị nro dị nro, nke a na-esikwa na aja aja (ọkwa Sa2.5), ịkpụ CNC (±0.5mm ndidi), yana ịgbado ọkụ MAG na-akpaghị aka. Ọ na-agafe ule nrụgide 20kPa/30min, yana akara okpukpu abụọ (rubber gasket + sealant) yana flanges igwe anaghị agba nchara iji hụ na ntapu{10}} na-arụ ọrụ. A na-eji mkpuchi na-ekpo ọkụ{12}} itinye zinc (Karịrị ma ọ bụ hà nhata 80μm) yana agba mgbochi corrosion nke okpukpu abụọ{13}}. Site na nguzogide nrụgide 100kPa na ọkwa corrosion C5-M (ISO9001 kwadoro), ọ na-emezu ihe niile achọrọ n'èzí hermetic ọrụ.

2.4 Mgbakọ ikpeazụ

1. Mgbakọ ikuku:Kpọnye nke ọma ikuku HV/LV na isi ọnya ahụ, na-ahụ na ntinye mkpuchi kwesịrị ekwesị na ntinye igwe.
2. Njikọ eletrik:Ihe na-ere ahịa ma ọ bụ bolt winding na-eduga na ndị na-agbanwe mgbata, ohia, na ndị nduzi ndị ọzọ, wee chọpụta nguzogide kọntaktị.
3. Isi -Ikpokoro eriri igwe:Debe akụkụ ahụ na-arụ ọrụ n'ime oven ihicha, na-etinye oghere na okpomọkụ iji wepụ mmiri mmiri ruo mgbe nguzogide mkpuchi na-agbaso ụkpụrụ.
4. Ntinye tankị:Jiri akụrụngwa na-ebuli elu jiri nlezianya wetuo akụkụ ahụ a mịrị amị n'ime tank, chekwaa ya ka ịzenarị ọgụ.
5. Ngwa mgbakwunye:Wụnye bushes, valvụ enyemaka nrụgide, IFD, njide ịwa ahụ, wdg, na-etinye sealant n'elu gasket maka ịgbapụta-.
6. Njuputa mmanu mmanu:Jupụta mmanụ n'okpuru oghere ruo ọkwa a kapịrị ọnụ, degas, ma hapụ ya ka ọ kwụrụ maka awa 24+ tupu ule ikpeazụ dielectric na DGA.
03 Nnwale
|
Mba. |
Nwale ihe |
Nkeji |
Ụkpụrụ nnabata |
Ụkpụrụ ndị atụtara |
Mmechi |
|
1 |
Ntụle Nguzogide |
/ |
/ |
/ |
Gafe |
|
2 |
Nlele oke |
/ |
Ngbanwe nke oke voltaji na ọpịpị bụ isi: Ihe na-erughị ma ọ bụ haha 0.5% Akara njikọ: ii0 |
A:-0.03 B:-0.05 |
Gafe |
|
3 |
Nnwale polarity |
/ |
Mwepu |
Mwepu |
Gafe |
|
4 |
Ọ dịghị - ibu mfu na mkpali ugbu a |
% kW |
I0 :: nye uru a tụrụ atụ P0: nye uru a tụrụ atụ nnabata maka enweghị ibu ibu bụ +10% |
0.35 0.095 |
Gafe |
|
5 |
Ngwunye ibu, voltaji impedance, mfu zuru oke na arụmọrụ |
/ kW kW |
t:85 ogo Z%: uru tụrụ Pk: uru tụrụ Pt: uru tụrụ nnabata maka impedance bụ ± 7.5% Nkwenye maka mkpokọta mfu ibu bụ +6% |
4.28 0.432 0.527 99.23 |
Gafe |
|
6 |
Nnwale voltaji etinyere |
/ |
LV: 10kV 60s |
Enweghị ọdịda nke voltaji ule a na-eme |
Gafe |
|
7 |
Nnwale Nkwụghachi Voltaji butere |
/ |
Voltaji etinyere (KV): 40 Ogologo oge: 40 Ugboro (HZ): 150 |
Enweghị ọdịda nke voltaji ule a na-eme |
Gafe |
|
8 |
Ntụle Nguzogide mkpuchi |
GΩ |
LV-HV gaa n'ala |
28.2 |
/ |
|
9 |
Ule ntapu |
/ |
Ntinye nrụgide: 20kPA Ogologo oge: 12h |
Enweghị ntapu na mba Mmebi |
Gafe |
|
10 |
Nnwale Dielectric mmanụ |
kV |
Karịrị ma ọ bụ hà nhata 45 |
59.40 |
Gafe |


04 Mbukota na mbupu
4.1 mbukota
Usoro nkwakọ ngwaahịa maka otu {{0}phase pad{1}} transformer agụnyere ihicha, nchekwa ime, nkwado mpụga, na ịde aha. Nke mbụ, a na-ehichapụ ihe ntụgharị nke ọma, na-enyocha ọkwa mmanụ na akara; maka njem, enwere ike igbapu mmanụ ma dochie ya na nitrogen kpọrọ nkụ (0.02-0.03 MPa) iji gbochie mmiri ịbanye, ma ọ bụ debe ya na oghere niile mechie. N'èzí, a na-etinye ihe mgbochi - (ụdọ ma ọ bụ bolted base fixation), ebe a na-echekwa ihe ndị dị mkpa (bushings, IFD, etc.) na mmetụta{8}} mkpuchi na-eguzogide, na a na-eji mgbochi- nchara na-agwọ elu igwe. A na-ekechikwa unit ahụ na ihe nkiri plastik na-adịghị mmiri nke nwere akwa mkpuchi (emelitere maka mbupu ụgbọ mmiri). A na-akwakọba ngwongwo ndị ahụ n'ụdị osisi (nwere ihe na-awụ akpata oyi n'ahụ n'ime) dịka usoro njem chọrọ. Ejikọnyere akara doro anya (ịdị arọ, ebe ebuli elu, ihe egwu) na akwụkwọ (ndepụta nkwakọ ngwaahịa, akụkọ nnwale), na-ahụ na nnabata na mmiri{14}} proof, shockproof, na ụkpụrụ IP56 maka njem ụgbọ mmiri.

4.2 Mbupu

A na-ebufe otu {{0}phase pad- nke a na-ebunye transformer site na njem ụgbọ mmiri nwere akpaghị aka n'ime ụgbọ mmiri ZIM SAMMY OFER (Voyage 8E) n'okpuru Bill of Lading 177PNBNBNL8580A, na-esi Ningbo Chuanshan Port gawa Jamaica. Echebere n'ime akpa 40'HC nwere ígwè-osisi mgbochi-base vibration na foam{9}}ihe ndị dị oké egwu, unit ahụ juputara na 0.02{11}}0.03MPa kpọrọ nkụ nitrogen maka mgbochi mmiri ma kpuchie ya na mmanụ mgbochi{13}}. Atụmatụ mbupu a mechiri-njikwa akpa, ezigbo oge GPS nsuso, yana nleba anya nrịbama nitrogen (Karịrị ma ọ bụ nhata 0.01MPa). Mgbe ọ bịarutere, nlebanya gụnyere nkwenye nke iguzosi ike n'ezi ihe, nyocha anya, na ule mkpuchi, tinyere nrubeisi nke B/L na nkwakọ foto iji hụ na nrube isi n'ụkpụrụ ụgbọ mmiri mba ụwa maka nchekwa mmiri na ujo.
05 Saịtị na nchịkọta
Dị ka isi nkuku nke netwọkụ nkesa ike, otu{0}pase pad{1} nke a na-agbanye n'ọkụ na-ejikọta ihe nrụpụta ọhụrụ yana nka dị elu iji wepụta ntụkwasị obi enweghị atụ maka ọnọdụ ọkọnọ ike dị iche iche. Site na nhazi kọmpat ya, arụmọrụ ike dị elu, yana njiri nleba anya smart nhọrọ, ọ na-egbo mkpa siri ike nke grids ọgbara ọhụrụ maka nchekwa, akụ na ụba na nkwado gburugburu ebe obibi. Site na obodo mepere emepe ruo na mpaghara dịpụrụ adịpụ, site na nkesa a na-emekarị ruo na ntinye ume ọhụrụ, anyị na-agba mbọ ịnye ngwọta eletrik dị mfe, dị nchebe na nke na-adigide site na ngwaahịa a ejiri nlezianya rụọ ọrụ. Ịhọrọ transformer anyị pụtara itinye ego n'ọdịnihu ike a pụrụ ịdabere na ya.

Ihe nchịkọta dị ọkụ: otu nkeji mpe mpe akwa akwadoro nkesa nkesa, onye nrụpụta, onye na-eweta, ọnụahịa, ọnụ ahịa
You Might Also Like
2500 kVA Pad Nkwanye Ntugharị-13.2 / 0.48 kV|Canada ...
50 kVA Pad na-agbanye ihe ntụgharị-24.94 / 0.24 * 0....
167 kVA Pad Mount Transformer-24 * 12 / 0.24 kV|Jama...
100 kVA Pad Mount Transformer-24 / 0.24 kV|Jamaica 2024
400 kVA Padmount Transformer-23 / 0.4 kV|Chile 2024
630 kVA Atọ nke Akọrọ Ụdị Ntugharị-10 / 0.4 kV|Georg...
Zipu ozi