2500 kVA Atọ Ngwunye Ntugharị Ntugharị Atọ-25 / 0.6 kV|Canada 2025
Ike: 2500kVA
Voltaji: 25kV-600Y/347V
01 Izugbe
1.1 Ihe ngosi oru ngo

Project Spotlight Mgbe onye ahịa Canada anyị bịakwutere anyị, ha chọrọ mgbanwe mgbanwe nke nwere ike ijikwa ọnọdụ ihu igwe siri ike, ibu dị arọ, na ịrụ ọrụ na-aga n'ihu. Nke ahụ bụ kpọmkwem ihe anyị napụtara: abụọ2500 kVA mpe mpe akwa - atụkwasịrị ihe ngbanweemebere iji nye ike a pụrụ ịdabere na ya, na-agbanwe agbanwe maka netwọk ụlọ ọrụ na azụmahịa. Ngwa ndị a abụghị naanị igwe{1}ha bụ nkwa. Nkwa na ume ga na-aga n'ihu, n'enweghị nsogbu na nke ọma, kwa ụbọchị.
1.2 Haziri maka Ọnọdụ Canada
Anyị haziri ihe ngbanwe ndị a kpọmkwem maka ọnọdụ mpụga Canada siri ike. Site na ikuku aluminom na mmanụ ONAN jụrụ oyi, ha na-akwụsi ike ọbụlagodi mgbe grid na-agbanwe ma ọ bụ ọnọdụ okpomọkụ na-agbanwe nke ukwuu. The loop{2}}Nri nri nwụrụ anwụ- imewe ihu na-eme ka ndị mmadụ nwee nchekwa, ebe ndị otu Dyn1 vector na-eme ka itinye aka na netwọkụ na-anọpụ iche dị mfe. N'ụzọ bụ isi, anyị gbara mbọ hụ na ha ga-eme nke ọma n'agbanyeghị ihe ihu igwe na-atụ ha{{6} ma mee ka ndị ọrụ nwee obi ike mgbe ha nọ na ya.
1.3 Nkọwa nka na ụzụ
2500 kVA atọ na-adọba mpe mpe akwa n'ịnyịnya ntụgharị nkọwapụta na mpempe akwụkwọ data
|
Enyere ya
Canada
|
|
Afọ
2025
|
|
Ụdị
Atọ nke mpe mpe akwa ugwu transformer
|
|
Ọkọlọtọ
CSA C227.4:21
|
|
Enyere ike
2500 kVA
|
|
Ugboro ugboro
60HZ
|
|
Nri
Loop
|
|
N'ihu
Nwụrụ anwụ
|
|
Usoro
Atọ
|
|
Ụdị oyi
ONAN
|
|
Ihe mgbochi mmiri
Mineral Mmanụ
|
|
Voltaji nke mbụ
25 kV
|
|
Voltaji nke abụọ
0,6 kV
|
|
Otu Vector
Dyn1
|
|
Ngwa ikuku
Aluminom
|
|
Mgbochi
5.75%
|
|
Pịa Changer
NLTC
|
|
Ọkụ aka
±2*2.5%
|
|
Enweghị mfu ibu
2500 W
|
|
Na Ibu Mfu
24000 W
|
|
Ngwa ngwa
Nhazi ọkọlọtọ
|
1.4 Ihe osise
2500 kVA atọ nkeji mpe mpe akwa n'ịnyịnya transformers osise na nameplate
![]() |
![]() |
02 Haziri maka Ọnọdụ Canada
Anyị haziri ndị a2500 kVA atọ nkeji mpe mpe akwa n'ịnyịnya transformerskpọmkwem maka ọnọdụ mpụga Canada siri ike. Site na ikuku aluminom na mmanụ ONAN jụrụ oyi, ha na-akwụsi ike ọbụlagodi mgbe grid na-agbanwe ma ọ bụ ọnọdụ okpomọkụ na-agbanwe nke ukwuu. The loop{2}}Nri nri nwụrụ anwụ- imewe ihu na-eme ka ndị mmadụ nwee nchekwa, ebe ndị otu Dyn1 vector na-eme ka itinye aka na netwọkụ na-anọpụ iche dị mfe. N'ụzọ bụ isi, anyị gbara mbọ hụ na ha ga-eme nke ọma n'agbanyeghị ihe ihu igwe na-atụ ha{{6} ma mee ka ndị ọrụ nwee obi ike mgbe ha nọ na ya.
2.1 Core na Magnetic Innovation
![]() |
N'ime obi nke ihe ngbanwe ọ bụla bụ kọmpat, isi ụkwụ atọ{0} nke na-enye ọwa magnetik na-aga nke ọma na nke ọma. Anyị na-eji obere -Slicon steel mpempe akwụkwọ na-efunahụ ya nwere ọgwụgwọ corrosion{3}} na-eguzogide ọgwụ iji belata mfu na mkpọtụ. Ọ bụ isi dị mfe, ee, mana nke anyị mere nke ọma ka ọ dịgide ma rụọ ọrụ nwayọ, na-eme ka sistemụ gị kwụsie ike n'okpuru ụdị ibu niile. |
2.2 Ikuku na njikọ kacha mma
![]() |
N'akụkụ voltaji {{0} dị ala, anyị na-eji ikuku ikuku nwere ụzọ ụgbọ ala ọla kọpa siri ike. Nke a pụtara na sekit dị mkpụmkpụ agaghị eme ka ha daa, na ọkụ na-efesa nke ọma. Akụkụ voltaji {{3} dị elu na-eji akwụkwọ-waya aluminom ewepụghị mkpuchi-kọmpat, ọnụ ahịa- dị irè, yana ntụkwasị obi. Ọnụ, nhọrọ ndị a na-efegharị efegharị na-enye gị nguzozi anyị na-achọ mgbe niile: ịdịte aka, ịrụ ọrụ nke ọma, na njikere maka ogologo oge- ịrụ ọrụ n'èzí. |
2.3 Atụmatụ nchekwa & Nchekwa ọgụgụ isi
![]() |
Nchekwa abụghị ihe e chepụtara echepụta. Anyị gbakwunyere Bay{{1}O-Net fuse na ugbu a- na-amachi fuse ndabere maka nchekwa oyiri, ebe enweghị-mgbanwe mgbata na-enye ohere maka mgbanwe voltaji ±2 × 2.5%. Nke ahụ pụtara mgbe ọnọdụ grid na-agbanwe, ndị na-agbanwe agbanwe nwere ike ime mgbanwe na-enweghị ịkụ egwu. Ọ masịrị anyị iche maka ha dị ka ndị nwere ọgụgụ isi, ndị mmekọ nchebe maka netwọk nkesa gị. |
2.4 Nhazi tank na nguzogide ihu igwe
![]() |
2500 kVA atọ pad na-ebunye ihe ngbanwe tank n'onwe ya bụ nke sitere na nchara dị nro mechiri emechi, gbachiri maka ike ọzọ. A na-agba aja n'elu ọ bụla, gụnye akụkụ ya, wee kpuchie ya na ihu igwe{2}} na UV{3} na epoxy primers na uwe elu. O siri ike ijikwa anyanwụ, snow, na mmiri ozuzo Canada ka ị na-echekwa ihe ndị dị n'ime ahụ ma na-echekwa oke ọkụ. Ị gaghị echegbu onwe gị maka ihe ndị ahụ -ha ekpuchirila ya. |
2.5 Mgbakọ na Nkwenye Ogo
![]() |
Anyị na-agbakọta isi na windings nke ọma, jikọọ ndị na-edu ndú, wụnye tank na ngwa ngwa, jupụta na mmanụ ịnweta mmanụ, ma mechie ya. Mgbe ahụ, anyị na-eme ya site n'ule CSA zuru ezu nke ọkọlọtọ ọkọlọtọ: nguzogide, oke, usoro{2} njikọ, mfu, nkwụsi ike voltaji etinyere na nke butere, nguzogide mkpuchi, ike dielectric, na ule ntapu. N'eziokwu, anyị na-elele ihe niile ugboro abụọ. Ọ bụrụ na ọ gafere, ị nwere ike ịtụkwasị obi na ọ ga-arụ ọrụ nke ọma site na ụbọchị mbụ. |
03 Nnwale


Nnwale oge na ụkpụrụ nnwale
CSA C227.4-21 Atọ-phase, pad{3}} ihe nkesa nkesa nwere njikọ njikọ elu voltaji nwere ikewapụ.
CSA{0}}C802.1{3}}13 (R2022) Uru arụmọrụ kacha nta maka mgbanwe nkesa nke mmiri juru
1. Ntụle Nguzogide
2. Nnwale oke
3. Usoro{1}}Nnwale mmekọrịta
4. Ọ dịghị ibu efu na ọ dịghị ibu ugbu a
5. Ibu ibu, Voltage Impedance na arụmọrụ
6. Nnwale voltaji etinyere
7. Nnwale anabatara voltaji
8. Nleba ule na nrụgide maka ndị na-agbanwe mmiri mmiri: A ga-eme ule nyocha na 50KPa maka 12h na-enweghị nkwụsị. Enweghị nrụrụ na-adịgide adịgide.
9. Ntụle Nguzogide mkpuchi
10. Oil Dielectric Test
Nsonaazụ ule
|
Mba. |
Nwale ihe |
Nkeji |
Ụkpụrụ nnabata |
Ụkpụrụ ndị atụtara |
Mmechi |
|
1 |
Ntụle Nguzogide |
% |
Ọnụego enweghị nguzozi kacha nguzogide |
0.82 |
Gafe |
|
2 |
Nlele oke |
% |
Ngbanwe nke oke voltaji na ọpịpị bụ isi: Ihe na-erughị ma ọ bụ haha 0.5% |
-0.06~-0.05 |
Gafe |
|
3 |
nkeji -nnwale mmekọ |
/ |
Dyn1 |
Dyn1 |
Gafe |
|
4 |
Ọ dịghị - ibu mfu na mkpali ugbu a |
/ |
I0:: nye uru a tụrụ atụ |
0.35% |
Gafe |
|
P0: nye uru a tụrụ atụ |
2.214 kW |
||||
|
Nkwenye maka enweghị ibu ibu bụ +10% |
/ |
||||
|
5 |
Ibu na-efunahụ voltaji impedance na arụmọrụ |
/ |
t:85 ogo Nkwenye maka impedance bụ ± 7.5% Nkwenye maka mkpokọta mfu ibu bụ +6% |
/ |
Gafe |
|
Z%: uru tụrụ |
5.69% |
||||
|
Pk: uru tụrụ |
22.183 kW |
||||
|
Pt: uru tụrụ |
24.397 kW |
||||
|
Ịrụ ọrụ adịghị erughị 99.37% |
99.43% |
||||
|
6 |
Nnwale voltaji etinyere |
kV |
HV: 50kV 60s LV: 10kV 60s |
Enweghị ọdịda nke voltaji ule a na-eme |
Gafe |
|
7 |
Nnwale Iguzogide Voltaji butere |
kV |
Voltaji etinyere (KV): 2 Ua |
Enweghị ọdịda nke voltaji ule a na-eme |
Gafe |
|
Ogologo oge (s):48 |
|||||
|
Ugboro (HZ): 150 |
|||||
|
8 |
Ule ntapu |
kPa |
Ntinye nrụgide: 50kPA Ogologo oge: 12h |
Enweghị ntapu na mba Mmebi |
Gafe |
|
9 |
Ntụle Nguzogide mkpuchi |
GΩ |
HV -LV gaa n'ala |
2.32 |
/ |
|
LV-HV gaa n'ala |
2.83 |
||||
|
HV&LV ruo Ground |
2.10 |
||||
|
10 |
Nnwale mmanụ |
/ |
Ike Dielectric; |
56.1 kV |
Gafe |
|
Ọdịnaya Ọdịnaya |
9.7 mg / kg |
||||
|
Ihe nchụsa |
0.00204% |
||||
|
Nyocha nke Furan |
0.03 |
||||
|
Nyocha chromatography gas |
/ |
04 Mbukota na mbupu


05 Ọkachamara SCOTECH
Na SCOTECH, anyị na-ebuga nde kVA nke ngbanwe kwa afọ, n'ụwa niile. Site na ụkpụrụ CSA ruo IEEE, obere nkeji 100 kVA ruo nnukwu sistemu kVA 5000, ihe ntụgharị ọ bụla na-ebu nkwa anyị maka imepụta, nnwale na ntụkwasị obi. Nkeji abụọ 2500 kVA? Ha bụ ihe atụ zuru oke nke ọkachamara ahụ{5}} arụpụtara iji rụọ ọrụ, wuo ya ka ọ dịgide, yana dịrị njikere idowe grid Canada n'enweghị nbibi.

Ihe nchịkọta dị ọkụ: three phase pad mounted transformers,maker, sopplier, price, cost
You Might Also Like
Mpempe akwụkwọ 300 kVA{1} agbakwunyere Transformer-3...
500 kVA Nwụrụ Anwụ n'ihu Pad na-agbanye Transformer-...
500kVA Pad Mount Transformer-14.4 / 0.208 kV|US 2025
5 MVA Pad Mount Transformers-33 / 0.48 kV|USA 2025
3000 kVA Pad Nkwanye Ntugharị-25 / 0.6 kV|Canada 2025
1000 kVA Pad Mount Transformer-13.8 / 0.46 kV|Guyana...
Zipu ozi