1000 kVA Pad Mount Transformer-13.8 / 0.46 kV|Guyana 2025
Ike: 1000kVA
Voltaji: 13.8kV-460Y/266V
Njirimara: ELSP dị ugbu a - na-amachi fuses ndabere

1000 kVA pad mount transformer -Smart ike maka ụlọ ọrụ azụmahịa, nwere ihe abụọ{2}} fuse nchedo na ntụkwasị obi 13.8kV ka 460Y/266V
01 Izugbe
1.1 Nkọwa oru ngo
N'April 2025, otu onye n'ime ndị ahịa anyị ogologo oge{1} na Guyana nyere iwu maka transformer abụọ: 1000kVA 13.8kV–460Y/266V atọ{{6}phase pad- nke etinyere na transformer na 400kVA 460–220/127VPIakọrọ{0}ụdị transformer.
1000 kvampe mpe akwa transformerarụnyere na IEEE Std C57.12.34-ụkpụrụ 2022 yana njiri atụmatụ nri loop nwere ihe nrụnye ihu n'ihu-. Ọ na-anabata ONAN (Oil Natural Air Natural) jụrụ oyi ma were mmanụ ịnweta kpuchie ya. Isi voltaji bụ 13.8kV, na voltaji nke abụọ bụ 460Y/266V, yana otu Dyn11 vector na 5.75% impedance.
Ihe ngbanwe ahụ nwere fuses Bayonet atọ yana ELSP atọ ugbu a- na-amachi fiusi ndabere. Bayonet Fuse na-enye nchebe maka obere mmejọ dị ugbu a. ELSP Fuse na-ebipụ ngwa ngwa ma na-amachi ike arc mgbe sekit dị mkpụmkpụ dị ugbu a na-eme. Mgbe ejikọtara ya, ọ na-ekpuchi oke nchedo mmejọ site na ala ruo ugbu a dị elu. Ọ dabara nke ọma maka mkpa nke nchekwa, kwụsiri ike, dị mfe idowe yana ọnụ ahịa -sistemụ nkesa ike dị irè.
1000 kVA three{1}phase pad mount transformer dabara adaba maka nnukwu ụlọ ahịa & ebe azụmahịa{2}}kV ejikọrọ na netwọk nkesa obodo, yana 460V ka a na-eji maka ikuku ikuku, ọkụ, igwe mbuli elu na ibu ndị ọzọ. N'ihi na ngwa ngwa dị iche iche nke ngwa azụmahịa chọrọ ọkụ ọkụ atọ{5} nke kwụsiri ike, nrụpụta ngbanwe nke 460Y/266V ezuola. Nchedo fuse ugboro abụọ na-eme ka ọkwa nchekwa dịkwuo mma ma na-ebelata mfu ihe onwunwe nke mmejọ kpatara.
1.2 Nkọwa nka nka
1000kVA atọ na-adọ mpe mpe akwa ndokwasa transformer nkọwa na data mpempe akwụkwọ
|
Enyere ya
Guyana
|
|
Afọ
2025
|
|
Ụdị
Atọ nke mpe mpe akwa ugwu transformer
|
|
Ọkọlọtọ
IEEE Std C57.12.34-2022
|
|
Enyere ike
1000 kVA
|
|
Ugboro ugboro
60HZ
|
|
Nri
Loop
|
|
N'ihu
Nwụrụ anwụ
|
|
Usoro
Atọ
|
|
Ụdị oyi
ONAN
|
|
Ihe mgbochi mmiri
Mineral Mmanụ
|
|
Voltaji nke mbụ
13.8 kV
|
|
Voltaji nke abụọ
0,46 kV
|
|
Otu Vector
Dyn11
|
|
Ngwa ikuku
Ọla kọpa
|
|
Mgbochi
5.75%
|
|
Pịa Changer
NLTC
|
|
Ọkụ aka
±2*2.5%
|
|
Ịrụ ọrụ
99.15%
|
|
Enweghị mfu ibu
1600 W
|
|
Na Ibu Mfu
11800 W
|
|
Ngwa ngwa
Nhazi ọkọlọtọ
|
1.3 Eserese
1000kVA atọ na-adọ mpe mpe akwa ndokwasa transformer nameplate na ịbịaru
![]() |
![]() |
02 Nrụpụta
2.1 Isi
Isi nke atọ{{0}phase three- ụkwụ ụkwụ na-anakwere nkwonkwo zuru oke, na-eji oyi{2}}oka ọka{3}}Slicon steel ibé akwụkwọ agbadoro anya iji belata enweghị ibu- ma nwekwaa ikike ndọta nke ọma. Site na iji nkwonkwo mitered zuru oke, flux magnetik na-anọgide na-adaba na ntụgharị nchara nke igwe, si otú a na-ebelata isi mfu. Otú ọ dị, usoro njikọ a dị mgbagwoju anya karị, a pụkwara ibelata iguzosi ike n'ezi ihe nke isi ihe a kpọkọtara.

2.2 Ikuku

The transformer adopter obere voltaji foil winding na elu voltaji waya winding Ọdịdị. The elu voltaji winding adopts 1.5 × 4 mm akụkụ anọ ọla kọpa eduzi. Ngwakọta a na-enye arụmọrụ okpomọkụ dị mma, nhazi kọmpat na njirimara eletrik a pụrụ ịdabere na ya.
2.3 tank
Ihe ngbanwe ahụ na-egosi tankị mechiri emechi nwere mkpuchi gbachiri emechi, nke emere site na igwe dị nro dị oke elu-. A na-ejikọta radiators n'akụkụ abụọ na azụ nke tank ahụ iji kwalite mgbasa ọkụ. Nhazi nke tank ahụ na-eme ka ike na-arụ ọrụ siri ike yana oyi dị mma maka ọrụ mmiri mmiri{3}}emikpu. Iji hụ na a pụrụ ịdabere na ya, tank ahụ bụ nrụgide- nwalere na 50 kPa maka awa 24 na-enweghị nkwụsị ma ọ bụ nrụrụ.


Anyịatọ - pad - ndokwasịrị ngbanwenabata Eaton's ELSP current- na-amachi fuse ndabere, jikọtara ya na Bay{1}O{{2}Net fuse iji mepụta sistemu nchekwa abụọ. Fiusi a nwere nnukwu arụmọrụ na-ebelata arụmọrụ dị ugbu a, na-ebelata mmetụta nke ikuku na-adịghị mma na akụrụngwa, ma dabara adaba maka iji mmanụ ihe nrụpụta.
1. Core na Winding Assembly
Kpọkọtanụ akụkụ nọ n'ọrụ (isi na winding). A na-akwado ụzọ ndị egosiri na foto a maka ịgbado ọkụ.
2. Isi nwụnye tank
3. Ngwa ntinye
Nke a 1000 kva pad mount transformer na-eji nchikota Bay{1}O{2}Net fuse na ELSP ugbu a{3}} na-amachi ndabere fuse, nke bụ atụmatụ nchekwa nchekwa maka mmanụ-mikpu nkesa nkesa na North America.
4. Mmanụ na-ejuputa na akara
Jupụta ihe ngbanwe ahụ na mmanụ mkpuchi ma mechie tank.
5. Njikọ eletrik na nyocha
6. Nleba anya n'ọdịdị ikpeazụ na akara aha

03 Nnwale


Nnwale oge na ụkpụrụ nnwale
1. Ntụle Nguzogide ikuku: Dabere na IEEE C57.12.90-2021 Nkeji 5
2. Ntụle Voltage Ratio: Dị ka IEEE C57.12.90-2021 Nkeji edemede 7 siri dị.
3. Nnwale Ntugharị Oge: Dị ka IEEE C57.12.90-2021 Nkeji edemede 6 si dị.
4. Mba - ibu mfu na mba - ibu ihe nlere ugbu a: Dị ka IEEE C57.12.90-2021 Nkeji 8 siri dị
5. Mfu ibu, Voltaji impedance, na Ntụle arụmọrụ: Dị ka IEEE C57.12.90-2021 Nkeji edemede 9 na CSA-C802.1-13 Nkeji edemede 6 siri dị.
6. Nnwale voltaji etinyere: Dabere na IEEE C57.12.90-2021 Nkeji 10.6
7. Nnwale Nkwụghachi voltaji na-ebute: Dị ka IEEE C57.12.90-2021 Nkeji edemede 10.5.1
8. Nnwale ntapu na nrụgide maka Liquid{1}}Mgbanwe imikpu: A ga-eme ule ntapu na 50KPa maka awa 24 na-enweghị ntapu. Enweghị nrụrụ na-adịgide adịgide.
9. Ntụle Nguzogide mkpuchi
10. Dielectric Strength Test of Transformer Mmanụ
Nsonaazụ ule
|
Mba. |
Nwale ihe |
Nkeji |
Ụkpụrụ nnabata |
Ụkpụrụ ndị atụtara |
Mmechi |
|
1 |
Ntụle Nguzogide |
% |
Ọnụego enweghị oke nguzogide na-erughị ma ọ bụ haha 5% |
1.68 |
Gafe |
|
2 |
Nlele oke |
% |
Ngbanwe nke oke voltaji na ọpịpị bụ isi: Ihe na-erughị ma ọ bụ haha 0.5% Akara njikọ: Dyn11 |
-0.09%~-0.08% |
Gafe |
|
3 |
nkeji -nnwale mmekọ |
/ |
Dyn11 |
Dyn11 |
Gafe |
|
4 |
Ọ dịghị - ibu mfu na mkpali ugbu a |
/ |
I0 :: nye uru a tụrụ atụ |
0.77% |
Gafe |
|
P0: nye uru a tụrụ atụ (t:20 degrees) |
1.465kW |
||||
|
nnabata maka enweghị ibu ibu bụ +10% |
/ |
||||
|
5 |
Ibu na-efunahụ voltaji impedance na arụmọrụ |
/ |
t:85 ogo nnabata maka impedance bụ ± 7.5% Nkwenye maka mkpokọta mfu ibu bụ +6% |
/ |
Gafe |
|
Z%: uru tụrụ |
5.62% |
||||
|
Pk: uru tụrụ |
11.085 kW |
||||
|
Pt: uru tụrụ |
12.550 kW |
||||
|
Ịrụ ọrụ adịghị erughị 99.15% |
99.21% |
||||
|
6 |
Nnwale voltaji etinyere |
kV |
HV: 34kV 60s LV: 10kV 60s |
Enweghị ọdịda nke voltaji ule a na-eme |
Gafe |
|
7 |
Nnwale Iguzogide Voltaji butere |
kV |
Voltaji etinyere (KV):2Ur |
Enweghị ọdịda nke voltaji ule a na-eme |
Gafe |
|
Voltaji ebutere (KV): 27.6 |
|||||
|
Ogologo oge (s):48 |
|||||
|
Ugboro (HZ): 150 |
|||||
|
8 |
Ule ntapu |
kPa |
Ntinye nrụgide: 50kPA |
Enweghị ntapu na mba Mmebi |
Gafe |
|
Ogologo oge: 24h |
|||||
|
9 |
Ntụle Nguzogide mkpuchi |
GΩ |
HV -LV n'ala: |
48.4 |
/ |
|
LV-HV gaa n'ala: |
65.5 |
||||
|
HV&LV n'ala: |
51.9 |
||||
|
10 |
Nnwale Dielectric mmanụ |
kV |
Karịrị ma ọ bụ hà nhata 45 |
56.5 |
Gafe |
04 Saịtị na nchịkọta

SCOTECHna-ebuga ihe karịrị 12,000,000 kVA transformers n'ofe ụwa kwa afọ, na-akwado ọtụtụ ụlọ na azụmahịa. Anyị nwere ahụmahụ bara ụba n'ichepụta ma na-emepụta ihe mgbanaka nke okpukpu atọ. Ma ọ bụ ọkọlọtọ CSA ma ọ bụ IEEE Standard, anyị nwere ọtụtụ ikpe. Enyere ikike sitere na 100 kVA ruo 5000 KVA. Anyị na-ahụ na ngalaba ọ bụla na-enweta ule nnabata zuru oke. Na-atụ anya inweta ntụkwasị obi gị.
Ihe nchịkọta dị ọkụ: 1000 kva mpe mpe akwa ugwu transformer, emeputa, soplaya, price, efu
You Might Also Like
75 kVA 3 Ngbanwe nkesa nkesa-13.8 / 0.208 kV|Canada ...
300 kVA Mmanụ jupụtara ngbanwe-13.2 / 0.48 kV|Guyana...
750 kVA Pad Nkwanye Ntugharị-13.2 / 0.48 kV|US 2024
1250 kVA Pad Nkwanye Ntugharị-12.47 / 0.6 kV|US 2025
1000 kVA Nwụrụ Anwụ n'ihu Transformer-24 / 0.48 kV|U...
500 kVA Pad Nkwanye Ntugharị-13.2 / 0.48 kV|USA 2025
Zipu ozi