2250 kVA Pad na-agbanye ihe ntụgharị-12.47 / 0.6 kV|USA 2025

2250 kVA Pad na-agbanye ihe ntụgharị-12.47 / 0.6 kV|USA 2025

Obodo: America 2025
Ike: 2250kVA
Voltaji: 12.47GrdY/7.2-0.6Y/0.347kV
Njirimara: Na mmanụ FR3
Zipu ozi

 

 

2250 kva pad mounted transformer-front-door-open

2250 kVA pad mounted transformer{1}} arụpụtara maka ugbo anyanwụ, nke e wuru maka nchekwa, arụmọrụ, yana ọdịnihu ike ndụ ndụ.

 

01 Izugbe

1.1 Ihe ndabere oru ngo

Iji kwado mgbasawanye nke sistemu ike anyanwụ n'ahịa US, anyị wetara 2250 kVA three-phase pad- mounted transformer nke ahaziri maka ịba uru-scale photovoltaic (PV) ngwa. Ejiri usoro isi isi ụkwụ ise siri ike- na nwụrụ anwụ{8}}ihu, loop{9}} nhazi ndepụta, nkeji a na-eme ka nchekwa, ntụkwasị obi, na mgbanwe sistemu na gburugburu ike mmeghari ohuru.

Nke a2250 kva mpe mpe akwa n'elu transformerna-arụ ọrụ na voltaji mbụ nke 12.47 GrdY / 7.2 kV na voltaji nke abụọ nke 0.6Y / 0.347 kV, na-eme ka ọ dị mma maka ịmekọrịta na ndị na-atụgharị anyanwụ na netwọk nkesa ala. Otu vector YNyn0 na-eme ka ala dị mma ma na-eme ka njikọ dị ala{6}}voltaji atọ- na-arụ ọrụ n'ugbo anyanwụ. Na aluminom windings, unit na-enye nguzozi n'etiti arụmọrụ na ọnụ ahịa arụmọrụ.

Built with FR3 natural ester fluid, the transformer achieves a high level of environmental sustainability and fire safety, thanks to its high flash point (>300 degrees) na biodegradability. Nhazi nke KNAN (ikuku eke {{2} jụrụ oyi) na-ebelata ịdị mgbagwoju anya na mkpa nrụzi ma na-ahụ na arụmọrụ ọkụ dị mma.

A na-ebunye ya na nhazi oge, transformer na-enye aka ozugbo na mgbasawanye akụrụngwa nke anyanwụ nke onye ahịa, na-akwado ebumnuche mba sara mbara nke decarbonization na imeziwanye grid. Ọ na-egosipụta ike anyị nwere ike ịrụ ọrụ dị elu{1}, arụmọrụ, ngwa ọrụ{2}ngwaọrụ ọkwa maka mkpa mgbanwe nke ngalaba ume ọhụrụ.

 

 

1.2 Nkọwa nka nka

2250 kVA mpe mpe akwa agbakwunyere nkọwapụta na mpempe data

Enyere ya
America
Afọ
2025
Ụdị
Atọ nke mpe mpe akwa ugwu transformer
Ọkọlọtọ
IEEE Std C57.12.34-2022
Enyere ike
2250 kVA
Ugboro ugboro
60HZ
Nri
Loop
N'ihu
Nwụrụ anwụ
Usoro
Atọ
Ụdị oyi
KNAN
Ihe mgbochi mmiri
Mmanụ FR3
Voltaji nke mbụ
12.47 kV
Voltaji nke abụọ
0,6 kv
Otu Vector
YNyn0
Ngwa ikuku
Aluminom
Mgbochi
5.75%
Ịrụ ọrụ
99.52%
Pịa Changer
NLTC
Ọkụ aka
±2*2.5%
Enweghị mfu ibu
2.4 kW
Na Ibu Mfu
15.79 kW
Ngwa ngwa
Nhazi ọkọlọtọ

 

1.3 Eserese

2250 kVA mpe mpe akwa akwadoro akụkụ ntụgharị na nkọwa ịdị arọ

2250 kva pad mounted transformer diagram 2250 kva pad mounted transformer nameplate

 

 

02 Nrụpụta

2.1 Isi

Nhazi isi isi ụkwụ ise ahụ- na-eme ka njikwa kacha mma nke efu{1}} usoro nfegharị na ọnọdụ nbudata na-ezighi ezi, bụ nke a na-ahụkarị na sistemu ike ekesa. Loop ya -nri na ndị nwụrụ anwụ- ihe owuwu n'ihu dabara n'ụkpụrụ nchekwa US ma na-enye aka nrụnye dị mma n'ubi anyanwụ, ọdụ ụgbọ ala, na ebe ọhaneze- nnweta.

2250 kva pad mounted transformer five leg core

 

2.2 Ikuku

2250 kva pad mounted transformer

Nke a 2250 kva pad mounted transformer nwere nnukwu -voltaji winding nwere waya-ọnya imewe, na-enye ọnụ ọgụgụ dị elu nke ntụgharị iji hụ na nkesa voltaji otu na ịrụ ọrụ mkpuchi dị mma. Obere ikuku-voltaji na-eji ihe owuwu foil iji jikwaa mmiri dị elu nke ọma ma na-ebelata mfu. Nhazi otu vector YNyn0 na-akwado nnọpụiche gbadoro ụkwụ na ma akụkụ voltaji dị elu na nke dị ala, na-eme ka nchekwa sistemu na nkwụsi ike - isi ihe achọrọ maka ngwa fotovoltaic. Na mgbakwunye, ọnụọgụ abụọ - voltaji dị ala na-enye ohere njikọ mgbanwe na nhazi ibu dị iche iche, na-eme ka ntụkwasị obi zuru oke nke sistemu na ngbanwe na ọrụ ike anyanwụ.

 

2.3 tank

Ihe ngbanwe nke 2250 kva na-ekpudo ihe na-agụnye tank mmanụ mechiri emechi nke ejiri igwe dị nro, kpuchie ya na ntụ ntụ ọcha siri ike (RAL 9003) iji kwalite nguzogide corrosion. Ihe mkpuchi kpuchiri ekpuchi na-eme ka akara dị mma, na-echebe mmanụ mkpuchi n'ime.

Ihe ngbanwe a na-egosi radiators corrugated jikọtara n'akụkụ abụọ na azụ nke tank mmanụ, nke na-eje ozi dị ka ihe na-eme ka ọ dị jụụ site n'ịbawanye ebe dị n'èzí maka ikuku ikuku. Igwe ọkụ ọkụ ndị a na-agbado nke ọma wee mechie - na nnukwu tankị iji hụ na ọ na-agbapụta{2}} n'efu n'okpuru ịgba ígwè ọkụ. Ịgbado ọkụ nkenke na interface ahụ na-eme ka ike arụ ọrụ na mmanụ- guzosiri ike, ebe na-enye ohere maka mgbasawanye ọkụ na-emebighị nkwụsi ike nhazi ma ọ bụ ịrụ ọrụ jụrụ oyi.

2250 kva pad mounted transformer sealed oil tank

 

2.4 Mgbakọ ikpeazụ

2250 kva pad mounted transformer finall assembly

N'ọgbakọ ikpeazụ, nke a 2250 kVA pad - mgbanaka mgbanaka emebere maka ngwa ike anyanwụ nwere nnukwu osisi HV nke nwere ike kewapụrụ 200A, ahịhịa na-anọpụ iche (H0) raara onwe ya nye, na resin{4}}cast spade{5} ụdị LV bushings nke nwere ọdụ oghere iri na abụọ.

Sistemu nchekwa nke ihe ngbanwe na-agụnye fuses bayonet atọ, nke dị ugbu a -limiting fuses (CLF), na elbow{1} ụdị ọkụ na-ejide ọkụ nwere varistors metal oxide nke na-agbaso ụkpụrụ IEEE 386, na-eme ka ọ gbasie ike na nchebe mmejọ na nhazi ihu.

Ngwunye ala etinyere n'akụkụ abụọ HV na LV na-eme ka nchekwa nrụnye na ntụkwasị obi rụọ ọrụ.

 

 

03 Nnwale

Nnwale oge na ụkpụrụ nnwale

1. Ntụle Nguzogide: Dị ka IEEE C57.12.90-2021 Nkeji 5 si kwuo.

2. Nnwale oke: Dị ka IEEE C57.12.90-2021 Nkeji edemede 7 siri dị.

3. Usoro{1}}Nnwale mmekọrịta: Dị ka IEEE C57.12.90-2021 Nkeji edemede 6 siri dị

4. Enweghị mfu ibu na enweghị ibu dị ugbu a: Dị ka IEEE C57.12.90-2021 Nkeji edemede 8 si kwuo.

5. Ntufu ibu, Voltaji impedance na arụmọrụ: Dị ka IEEE C57.12.90-2021 Nkeji edemede 9 si kwuo.

6. Nnwale voltaji etinyere: Dabere na IEEE C57.12.90-2021 Nkeji 10.6

7. Nnwale Nkwụghachi voltaji na-ebute: Dị ka IEEE C57.12.90-2021 Nkeji edemede 10.5.1

8. Ntụle Nguzogide mkpuchi

9. Nleba ule na nrụgide maka ndị na-agbanwe mmiri mmiri: A ga-eme ule nyocha na 20KPa maka 12h na-enweghị nkwụsị. Enweghị nrụrụ na-adịgide adịgide.

 

Nsonaazụ ule

Mba.

Nwale ihe

Nkeji

Ụkpụrụ nnabata

Ụkpụrụ ndị atụtara

Mmechi

1

Ntụle Nguzogide

%

Ọnụego enweghị nguzozi kacha nguzogide

1.97

Gafe

2

Nlele oke

%

Ngbanwe nke oke voltaji na ọpịpị bụ isi: Ihe na-erughị ma ọ bụ haha ​​0.5%

Akara njikọ: YNyn0

-0.14% ~ 0.11%

Gafe

3

nkeji -nnwale mmekọ

/

YNyn0

YNyn0

Gafe

4

Ọ dịghị - ibu mfu na mkpali ugbu a

/

I0:: nye uru a tụrụ atụ

0.22%

Gafe

P0: nye uru a tụrụ atụ (t:20 degrees)

2.200kW

Nkwenye maka enweghị ibu ibu bụ +10%

/

5

Ibu na-efunahụ voltaji impedance na arụmọrụ

/

t:85 ogo

Nkwenye maka impedance bụ ± 7.5%

Nkwenye maka mkpokọta mfu ibu bụ +6%

/

Gafe

Z%: uru tụrụ

5.88%

Pk: uru tụrụ

14.325 kW

Pt: uru tụrụ

16,525 kW

Ịrụ ọrụ adịghị erughị 99.52%

99.52%

6

Nnwale voltaji etinyere

kV

HV /: 34kV 60s

LV /: 10kV 60s

Enweghị ọdịda nke voltaji ule a na-eme

Gafe

7

Nnwale Iguzogide Voltaji butere

kV

Voltaji etinyere (KV):2Ur

Enweghị ọdịda nke voltaji ule a na-eme

Gafe

Ogologo oge (s):48

Ugboro (HZ): 150

8

Ule ntapu

kPa

Ntinye nrụgide: 20kPA

Enweghị ntapu na mba

Mmebi

Gafe

Ogologo oge: 12h

9

Ntụle Nguzogide mkpuchi

GΩ

HV -LV n'ala:

2.01

/

LV-HV gaa n'ala:

1.66

HV&LV ruo Ground

1.03

 

2250 kva pad mounted transformer test
2250 kva pad mounted transformer testing
2250 kva pad mounted transformer routine test
2250 kva pad mounted transformer leakage test

 

 

04 Mbukota na mbupu

2250 kva pad mounted transformer packing
2250 kva pad mounted transformer shipping
 

05 Saịtị na nchịkọta

Nke a 2250 kVA atọ -pase pad{2}}nrụgidere ngbanwe bụ nke a haziri maka ịba uru -ụkpụrụ PV nke anyanwụ n'ahịa US. Ọ na-akwado nkesa ike kwụsiri ike yana nchekwa yana atụmatụ dabara ụkpụrụ nchekwa US, na-ahụ na ntinye ntụkwasị obi n'ime ugbo anyanwụ na sistemu ike mmeghari ohuru.

N'ịbụ onye ejiri mkpuchi mkpuchi dị elu yana jụrụ oyi, ọ na-ewepụta arụmọrụ eco{0} nke ọma maka ngwa ike dị ọcha. Ihe nchekwa siri ike na-eme ka ọrụ nchekwa dị na gburugburu mpụta siri ike.

A na-emezi igwe ngbanwe anyị iji gboo ihe na-eto eto nke ngalaba ume ọhụrụ nke US. Kpọtụrụ anyị maka ngwọta ahaziri ahazi iji mee ka ọrụ ike anyanwụ gị dị ike.

2250 kva pad mounted transformer-right-45-degree-view

 

Ihe nchịkọta dị ọkụ: 2250 kva mpe mpe akwa n'ịnyịnya transformer, onye nrụpụta, soplaya, price, efu