2000 kVA Pad Nkwanye Ntugharị-24 / 0.48 kV|USA 2024

2000 kVA Pad Nkwanye Ntugharị-24 / 0.48 kV|USA 2024

Obodo nzipu: USA 2024
Ike: 2000kVA
Voltaji: 24000-480GrdY/277 V
Njirimara: DOE 2016 arụmọrụ
Zipu ozi

 

 

2000 kva pad mounted transformer

Ọdịmma, nchekwa, na grid{0} dị njikere - Scotech's 2000 kVA pad{3}} na-agbanye mgbanaka na-eme ka akụrụngwa ọgbara ọhụrụ nwee ntụkwasị obi.

 

 

01 Izugbe

1.1 Nkọwa oru ngo

Nke a bụ 2000 kVAmpe mpe akwa - ihe nrụnye nrụnyena-ezute ụkpụrụ US kachasị ọhụrụ, gụnyere IEEE C57.12.34-2022 na DOE 2016 chọrọ arụmọrụ. Ọ na-agbada voltaji ọrụ mbụ site na 24 kV gaa na mmepụta nke abụọ nke 480GrdY/277 V.

Na-egosipụta windings ọla kọpa na otu Dyn1 vector, jụrụ oyi KNAN ya na-eme ka arụ ọrụ siri ike. Nkwalite gburugburu ebe obibi na nchekwa dị ịrịba ama na-abịa site na iji mmiri mmiri FR3 - ịkwalite nzere ụlọ akwụkwọ ndụ akwụkwọ ndụ ebe ọ na-ebelata ihe ize ndụ ọkụ, na-eme ka ọ dị mma maka akụrụngwa dị oke egwu na ntọala obodo mepere emepe.

Site na ịrụ ọrụ ntanetịime loop, transformer na-ejikọta ngwa ngwa n'ime mgbanaka{0}}ụdị nkesa sistemu, na-eme ka ntụkwasị obi sistemụ na-ekwe ka mmezi oge na-enweghị nkwụsị ọrụ. Ihe nwuru anwu{2} n'ihu na-akwalite nchekwa ndị ọrụ.

A na-etinye nke ọma na nkesa ọkụ eletrik, ihe ngbanwe a na-agbada elu dị elu{0}} ntinye voltaji maka njikọta na sistemu njikwa ike yana akụrụngwa ike ụlọ ọrụ n'okpuru ala.

 

 

 

1.2 Nkọwa nka nka

2000kVA atọ na-adọ mpe mpe akwa ndokwasa transformernkọwa na mpempe akwụkwọ data

Enyere ya
USA
Afọ
2024
Ụdị
Atọ nke mpe mpe akwa ugwu transformer
Ọkọlọtọ
IEEE Std C57.12.34-2022
Enyere ike
2000 kVA
Ugboro ugboro
60HZ
Nri
Loop
N'ihu
Nwụrụ anwụ
Usoro
Atọ
Ụdị oyi
KNAN
Ihe mgbochi mmiri
Mmanụ FR3
Voltaji nke mbụ
24 kV
Voltaji nke abụọ
0,48 kV
Otu Vector
Dyn1
Ngwa ikuku
Ọla kọpa
Mgbochi
5.75%
Standardkpụrụ arụmọrụ na mfu
DOE 2016
Pịa Changer
NLTC
Ọkụ aka
±2*2.5%
Enweghị mfu ibu
1.420 kW
Na Ibu Mfu
15.600 kW
Ngwa ngwa
Nhazi ọkọlọtọ

 

 

1.3 Eserese

2000kVA atọ agba mpe mpe akwa n'ịnyịnya transformer ịbịaru na nameplate

2000 kva pad mounted transformer drawing 2000 kva pad mounted transformer nameplate

 

 

02 Nrụpụta

2.1 Isi

Ejiri ọtụtụ{{0}Sliconic steel laminations nke ejiri varnish ma ọ bụ resin kpuchie ya, cores SCOTECH na-egbochi mmiri ozuzo nke ọma ma belata mfu na-ekesa. Nhazi nke a kpara akpa na-ebelatakwa mfu hysteresis, ọkachasị n'oge ndọta ugboro ugboro. Ọ na-eme ka arụmọrụ dị elu ma gbasaa ndụ ọrụ nke transformer.

2000 kva pad mounted transformer iron core

 

2.2 Ikuku

2000 kva pad mounted transformer copper winding

Ihe ngbanwe a nke 2000 kVA Dyn1 nwere njiri ọla kọpa nwere nrụnye foil n'akụkụ LV yana ọtụtụ - oyi akwa cylindrical winding n'akụkụ HV. Nhazi ahụ na-eme ka nguzogide mkpirisi ike dị mkpụmkpụ{4}, mwepu akụkụ dị ala, yana ezigbo ọkụ maka ịrụ ọrụ kwụsiri ike n'okpuru ntinye ike 24 kV.

 

2.3 tank

Ejiri ngwaọrụ dị ka valvụ enyemaka nrụgide, ihe nrịba ọkwa mmanụ, na igwe oghere, tank ahụ na-enye ohere nleba anya{{0} oge maka ọnọdụ dị n'ime. Atụmatụ ndị a na-akwado mgbochi mmejọ ma melite nchekwa n'oge ọrụ ntụgharị.

2000 kva pad mounted transformer oil tank

 

2.4 Mgbakọ ikpeazụ

2000 kva pad mounted transformer-inside-view

Scotech na-ahụ na a na-amata nke ọma na ihe ntụgharị ọkụ niile ewepụtara na akara dịka ụkpụrụ nke ngalaba 26 "Electrical Identification". N'oge echichi, anyị na-akwado ka agbatị njikọ eletrik niile na ọnụ n'otu UL 486A na UL 486B iji hụ na ntụkwasị obi ogologo-.

 

 

03 Nnwale

Nnwale oge na ụkpụrụ nnwale

1. Ntụle Nguzogide dịka IEEE C57.12.90-2021 Nkeji edemede 5 siri dị.

2. Usoro{1}}Nnwale mmekọrịta dịka IEEE C57.12.90-2021 Nkeji edemede 6 siri dị.

3. Nnwale oke dịka IEEE C57.12.90-2021 Nkeji edemede 7 siri dị.

4. Enweghị mfu ibu na enweghị ibu dị ugbu a dịka IEEE C57.12.90-2021 Nkeji edemede 8

5. Ntufu ibu, Voltaji impedance na arụmọrụ dị ka IEEE C57.12.90-2021 Nkeji edemede 9 si dị.

6. Nnwale Nkwụghachi voltaji dị ka IEEE C57.12.90-2021 Nkeji edemede 10.5.1 siri dị.

7. Nnwale voltaji etinyere dịka IEEE C57.12.90-2021 Nkeji edemede 10.6 siri dị.

8. Nnwale ntanye na nrụgide maka ndị na-eme mgbanwe mmiri mmiri - a ga-eme ule ntapu na 15 kPa maka awa 12 na-enweghị ntapu. Enweghị nrụrụ na-adịgide adịgide.

9. Ntụle Nguzogide mkpuchi

10. Oil Dielectric Test

 

2000 kva pad mounted transformer testing
2000 kva pad mounted transformer factory test

 

Nsonaazụ ule

Mba.

Nwale ihe

Nkeji

Ụkpụrụ nnabata

Ụkpụrụ ndị atụtara

Mmechi

1

Ntụle Nguzogide

%

Ọnụego enweghị nguzozi kacha nguzogide

0.356

Gafe

2

Nlele oke

%

Ngbanwe nke oke voltaji na ọpịpị bụ isi: Ihe na-erughị ma ọ bụ haha ​​0.5%

Akara njikọ: Dyn1

-0.02%

Gafe

3

nkeji -nnwale mmekọ

/

Dyn1

Dyn1

Gafe

4

Ọ dịghị - ibu mfu na mkpali ugbu a

%

kW

I0:: nye uru a tụrụ atụ

P0: nye uru a tụrụ atụ

Nkwenye maka enweghị ibu ibu bụ +0%

0.18%

0.985

Gafe

5

Ibu na-efunahụ voltaji impedance na arụmọrụ

%

kW

kW

t:85 ogo

Z%: uru tụrụ

Pk: uru tụrụ

Pt: uru tụrụ

Nkwenye maka impedance bụ ± 7.5%

Nkwenye maka mkpokọta mfu ibu bụ +0%

Ịrụ ọrụ adịghị erughị 99.43%

5.61%

7.740

8.725

99.46%

Gafe

6

Nnwale voltaji etinyere

kV

HV: 40kV 60s

LV: 10kV 60s

Enweghị ọdịda nke voltaji ule a na-eme

Gafe

7

Nnwale Iguzogide Voltaji butere

kV

Voltaji etinyere (KV):

0.960

Ogologo oge (s):40

Ugboro (HZ): 180

Enweghị ọdịda nke voltaji ule a na-eme

Gafe

8

Ule ntapu

kPa

Ntinye nrụgide: 15kPA

Ogologo oge: 12h

Enweghị ntapu na mba

Mmebi

Gafe

9

Ntụle Nguzogide mkpuchi

GΩ

HV -LV n'ala:

LV-HV gaa n'ala:

HV&LV n'ala:

2.51

2.60

3.88

/

10

Nnwale Dielectric mmanụ

kV

Karịrị ma ọ bụ ha nhata 40

52.0

Gafe

 

 

04 Mbukota na mbupu

2000 kva pad mounted transformer packaging
2000 kva pad mounted transformer shipping

05 Saịtị na nchịkọta

Ebere igwe mgbanaka 2000 kVA nke Scotech{1}} ka o wee zute ụkpụrụ US kachasị ọhụrụ, gụnyere IEEE C57.12.34-2022 na DOE 2016 chọrọ ịrụ ọrụ nke ọma. Ọ na-agbadata 24 kV isi voltaji gaa na 480GrdY / 277 V mmepụta nke abụọ, na-egosipụta ikuku ọla kọpa na otu Dyn1 vector na KNAN jụrụ oyi iji hụ na a pụrụ ịdabere na ya, arụmọrụ kwụsiri ike. Ojiji mmiri mmiri FR3 na gburugburu ebe obibi na-ebelata ihe egwu ọkụ ma na-akwado ụkpụrụ ụlọ akwụkwọ ndụ akwụkwọ ndụ, na-eme ka ọ dị mma maka akụrụngwa dị egwu na gburugburu obodo.

Tank igwe siri ike na-agụnye valvụ enyemaka nrụgide, ihe nrịbama ọkwa mmanụ, yana nlele oghere maka nleba anya oge n'ezie na mmụba nchekwa ọrụ. Scotech na-agbaso akara nrịbama na ụkpụrụ nwụnye iji hụ na a pụrụ ịdabere na ya, nnyefe dị elu na ogologo oge-.

Dịka onye nrụpụta ntụkwasị obi nke igwe nkesa igwe{0}voltaji, Scotech na-agba mbọ ịnye igwe ngbanwe dị mma, nchekwa yana nchekwa gburugburu{1} iji kwado igwe ọkụ ọgbara ọhụrụ na ngwa nrụpụta.

2000 kva pad mounted transformer-left-view

 

Ihe nchịkọta dị ọkụ: 2000 kva mpe mpe akwa n'ịnyịnya transformer, onye nrụpụta, soplaya, price, ọnụ