1500 KVA Transformers Igbe eletriki-4.16 / 0.48 KV|USA 2025

1500 KVA Transformers Igbe eletriki-4.16 / 0.48 KV|USA 2025

Obodo: USA 2024
Ike: 1500 kVA
Voltaji: 4.16D-0.48Y/0.277 kV
Njirimara: ya na valvụ Schrader
Zipu ozi

 

image001

Mpempe akwụkwọ- Ndị ngbanwe atụkwasịgoro: Ụkpụrụ ọgbara ọhụrụ maka ike ekesa.

 

 

01 Izugbe

1.1 Nkọwa oru ngo

1000 kVA three phase pad mounted transformer e zigara America na 2024. Ike nke ihe ngbanwe bụ 1500 kVA na ONAN jụrụ oyi. Igwe ọkụ dị elu bụ 4.16D kV na ± 2 * 2.5% tapping range (NLTC), obere voltaji bụ 0.48Y / 0.277 kV, ha guzobere otu vector nke Dyn1.

Emebere ya maka ntụkwasị obi na nchekwa na netwọkụ nkesa ọkụ eletrik, Pad anyị {{0}Mounted Transformer bụ isi nkuku nke sistemu ike n'okpuru ala ọgbara ọhụrụ. Ezubere maka ntinye enweghị nkebi n'ime ebe obibi, azụmahịa, na ụlọ ọrụ mmepụta ihe, ọ na-ewepụta arụmọrụ siri ike ma na-ebute nchekwa ọha na ezi uche.

Akụkụ bụ isi na-enye aka na ịdịte aka ya pụrụiche na ogologo oge{{0} ntụkwasị obi bụ ojiji nke nnukwu osisi poselin voltaji -. N'ịbụ ndị a ma ama n'ihi ike ọrụ ha dị elu, ihe ndị dị mma dielectric, yana nguzogide nbibi gburugburu ebe obibi, osisi ndị a na-ahụ maka poselin na-eme ka ebe njikọ dị nchebe ma kwụsie ike maka eriri igwe eletrik- voltaji. Ihe owuwu ha siri ike na-enye arụmọrụ pụtara ìhè n'okpuru nrụgide ọkụ na ọkụ eletrik dị iche iche, na-ekwe nkwa iguzosi ike n'ezi ihe kemgbe ọtụtụ iri afọ nke ọrụ.

N'ịbụ nke etinyere n'ime ihe mgbochi- na-eguzogide, nchara akpọchi akpọchi, transformer a na-agwakọta ọmarịcha arụmọrụ nke oge{1}} ihe anwalela dị ka poselin nwere nnukwu isi na teknụzụ coil. Ọ na-eguzo dị ka nchekwa echekwabara, dị ala-profaịlụ, yana ngwọta a pụrụ ịdabere na ya nke ukwuu maka iweda ike nke ọma site na grid ngwa ruo na njedebe- onye ọrụ.

 

 

 

1.2 Nkọwa nka nka

1500 kVA mpe mpe akwa akwadoro ụdị nkọwapụta na mpempe data

Enyere ya
USA
Afọ
2024
Ụdị
Ihe mgbakwasa na mpe mpe akwa
Ọkọlọtọ
IEEE Std C57.12.34-2022
Enyere ike
1500 kVA
Ugboro ugboro
60HZ
Usoro
3
Nri
Loop
N'ihu
Nwụrụ anwụ
Ụdị oyi
ONAN
Voltaji nke mbụ
4.16D kV
Voltaji nke abụọ
0.48Y/0.277 kV
Ngwa ikuku
Aluminom
Otu Vector
Dyn1
Mgbochi
5.75%
Ịrụ ọrụ
99.48%
Pịa Changer
NLTC
Ọkụ aka
±2*2.5%
Enweghị mfu ibu
1.545 kW
Na Ọnwụ Ebu
10.54 kW

 

1.3 Eserese

1500 kVA mpe mpe akwa akwadoro eserese eserese na nha.

image003 image005

 

 

02 Nrụpụta

2.1 Isi

image007

Isi anyị na-ebelata enweghị - ibu mfu site na 70%, na-ebuga oke nchekwa ike yana obere ụgwọ ndụ ndụ maka ROI kacha elu. Ewuru ya maka ntụkwasị obi yana ịrụ ọrụ dị jụụ, ọ bụ ego kacha ogologo oge-.

 

2.2 Ikuku

Ihe ngbanwe nke mpempe akwụkwọ anyị na-egosipụta HV foil aluminum a pụrụ ịdabere na ya na ikuku LV waya. Nhazi a na-eme ka ike mkpirisi ike dị mkpụmkpụ{1} na arụmọrụ ọkụ, na-enye gị oge kachasị elu na ọnụ ala dị ala karịa ọla kọpa ọzọ.

image009

 

2.3 tank

image011

Ejiri igwe na-enweghị nkebi, corrosion - na-eguzogide tankị, a nwalere nke ọma iji kwe nkwa na ọ ga-enweta akara mgbapụta{1} maka ndụ. Nke a na-ewepụ nchegbu mmezi yana mkpochapụ gburugburu ebe obibi dị oke ọnụ, na-enye ntụkwasị obi zuru oke yana obere ọnụ ahịa ogologo oge-.

 

2.4 Mgbakọ ikpeazụ

Mgbakọ ikpeazụ nke mpe mpe akwa anyị{0} agbakwunyere ngbanwe na-ejikọta isi, coils, na tank na nhazi ziri ezi yana usoro egosipụtara. Nke a na-ahụ maka ịrụ ọrụ kachasị mma, mbelata mkpọtụ na ịma jijiji, yana ogologo oge nhazi nhazi ogologo{{2}. Ị na-enweta transformer nke na-arụ ọrụ nwayọ na ntụkwasị obi site na ụbọchị mbụ, na-akwado site na njikwa mma anyị siri ike yana ahụmịhe ubi buru ibu.

image013

 

 

03 Nnwale

Maka 1500kVA anyị atọ -pase pad - mounted transformer (4160Δ{12}}480Y/277V), nnwale na-elekwasị anya na ihe ndị ị na-ebute ụzọ: ọnụ ala dị ala, enweghị oge nkwụsị. Anyị na-ekerịta data doro anya: 2.83% ikuku na-adịghị mma (na-ezere ikpo ọkụ), -0.23% ~ 0.15% ntụgharị (ike kwụsiri ike), mkpuchi 18.2-18.6GΩ (mmejọ ole na ole), 12h na-akwụghị ụgwọ (enweghị ụgwọ mmanụ), 56.4kV mmanụ ike (ọrụ nchekwa), na 8% effici.s. Metiriks niile na-emezu nkwa.

Mba.

Nwale ihe

Nkeji

Nnabata

Ụkpụrụ

Ụkpụrụ ndị atụtara

Mmechi

1

Ntụle Nguzogide

%

Ọnụego enweghị nguzozi kacha nguzogide

2.83

Gafe

2

Nlele oke

%

Ngbanwe nke oke voltaji na ọpịpị bụ isi: Ihe na-erughị ma ọ bụ haha ​​0.5%

-0.12

Gafe

3

Usoro{0}}Nnwale mmekọrịta

/

Dyn1

Dyn1

Gafe

4

Ọ dịghị - ibu mfu na mkpali ugbu a

%

I0 :: nye uru a tụrụ atụ

0.26

Gafe

kW

P0: nye uru a tụrụ atụ (ogo 20)

1.567

/

nnabata maka enweghị ibu ibu bụ ± 10%

/

5

Mfu ibu , impedance voltaji, ngụkọta mfu na arụmọrụ

/

t:85 ogo

nnabata maka impedance bụ ± 7.5%

nnabata maka ngụkọta ibu ọnwụ bụ ± 6%

/

Gafe

%

Z%: uru tụrụ

5.67

kW

Pk: uru tụrụ

10.475

kW

Pt: uru tụrụ

12.042

%

Ịrụ ọrụ adịghị erughị 99.48%

99.48

6

Nnwale voltaji etinyere

/

HV: 19kV 60s

LV: 10kV 60s

Enweghị ọdịda nke voltaji ule a na-eme

Gafe

7

Nnwale Iguzogide Voltaji butere

/

Voltaji etinyere (KV): 0.96

Enweghị ọdịda nke voltaji ule a na-eme

Gafe

Ogologo oge (s):48

Ugboro (HZ): 150

8

Ntụle Nguzogide mkpuchi

HV -LV n'ala:

18.2

/

LV-HV gaa n'ala:

18.6

HV&LV n'ala:

18.5

9

Ule ntapu

/

Ntinye nrụgide: 20kPA

Enweghị ntapu na mba

Mmebi

Gafe

Ogologo oge: 12h

10

Nnwale mmanụ

kV

Ike Dielectric

56.4

Gafe

mg/kg

Ọdịnaya Ọdịnaya

9.9

%

Ihe nchụsa

0.00247

mg/kg

Nyocha nke Furan

/

/

Nyocha chromatography gas

/

 

image015
image017

 

04 Mbukota na mbupu

4.1 mbukota

image019

Mpempe mpe mpe mpe mpe akwa{0}phase{1} anyị atọkwasara - na-eji ihe nchekwa abụọ: akpa oghere{2}}achiri n'ime akpa foil aluminum nwere ihe nchara (na-akwụsị nchara, ndị asọmpi na-eleghara anya), wee kechie ya na ihe nchekwa nkuku wee tinye ya na igbe osisi siri ike. N'adịghị ka igbe ndị ọzọ na-enweghị akara, nke anyị nwere forklift/center-nke{5}}ike ndọda maka njikwa dị mfe{6}}n'ịhụ na transformer gị erutela emebibeghị, dị njikere iji.

 

4.2 Mbupu

N'okpuru usoro CIF anyị na Port of Los Angeles, anyị na-ewere ọrụ zuru oke maka ọnụ ahịa, mkpuchi, na ibu nke mbupu gị. Mmekọrịta anyị na ndị na-ebu ọkwa dị elu{1} na atụmatụ ngwa ngwa ngwa ngwa na-eme ka ngbanwe gị bịarute n'oge yana n'ọnọdụ zuru oke. Nke a na-ewepụ mgbagwoju anya na ihe ize ndụ nke mbupu mba ụwa maka gị, na-enye ọnụahịa ego na udo nke uche.

image021

 

 

05 Saịtị na nchịkọta

Mgbe ị kọwapụtara igwe mgbanaka mgbanaka anyị {{0}phase pad atọ, ị na-ahọrọ karịa ngwaahịa - ị na-etinye ego n'ime ọtụtụ iri afọ nke arụmọrụ a pụrụ ịdabere na ya. Site na ikuku aluminom siri ike na ntapu- tankị na-egosi na nkwakọ ngwaahịa echekwara na nnyefe a na-achịkwa, a na-ahazi nkọwa niile iji belata ụgwọ ndụ gị na ihe egwu arụ ọrụ. Anyị na-ebuga ntụkwasị obi egosipụtara nke na-edobe ọrụ gị na nhazi oge yana ike obodo gị, kwa afọ.

image023

 

Ihe nchịkọta dị ọkụ: igbe ọkụ eletrik, onye nrụpụta, onye na-eweta, ọnụahịa, ọnụ ahịa

Zipu ozi