750 kVA Pad Mount Transformer-25 / 0.6 kV|Canada 2025
Ike: 750 kVA
Voltaji: 25D-0.6Y/0.347 kV
Njirimara: ya na mgbanaka nkwụsị ibu

Ike a pụrụ ịdabere na ya, Nhazi kọmpat - ihe ngbanwe ihe mkpuchi maka grid smart!
01 Izugbe
1.1 Nkọwa oru ngo
750 kVA three phase pad mounted transformer e zigara Canada na 2025. Ike nke transformer bụ 750 kVA na ONAN jụrụ oyi. Isi voltaji bụ 25D kV na ± 2 * 2.5% tapping range (NLTC), nke abụọ voltaji bụ 0.6y / 0.347 kV, ha guzobere vector otu Dyn1.
CSA -pad gbagoro agbaze{1}nke ndị nrụnye mgbanaka na-ezute ụkpụrụ siri ike nke Canadian Standards Association (CSA) setịpụrụ maka ịrụ ọrụ eletrik, ịdịte aka na nkwụghachi gburugburu. Mpempe akwụkwọ - ihe nrụnye n'elu bụ nke siri ike, kọmpat na nke dị oke mma nkesa ọkụ eletrik emere maka ntinye n'èzí n'ogo ala. Edebere n'okirikiri na-adịgide adịgide, nke na-emebi emebi{5}, ihe ngbanwe ndị a na-enye ngbanwe ike dị mma na ntụkwasị obi maka ngwa ime obodo, ime obodo na ụlọ ọrụ mmepụta ihe. Oghere ha -ichekwa imewe na-ebelata akara ukwu ma na-ahụ na ọ dị mfe maka mmezi.
Site na mkpuchi dị elu, nguzogide corrosion na ihe nrụpụta ihu igwe, mpe mpe akwa{0}nrụnye ngbanwe na-ebuga arụmọrụ na-agbanwe agbanwe na gburugburu dị iche iche{1}site na smart grids na sistemu ume ọhụrụ gaa na ogige azụmahịa na netwọk ọrụ. Emebere ya maka nchekwa, arụmọrụ, na ogologo ndụ, ha bụ nhọrọ a tụkwasịrị obi maka nkesa ike ọgbara ọhụrụ.
1.2 Nkọwa nka nka
1500 kVA mpe mpe akwa akwadoro ụdị nkọwapụta na mpempe data
|
Enyere ya
Jamaica
|
|
Afọ
2025
|
|
Ụdị
Ihe mgbakwasa na mpe mpe akwa
|
|
Ọkọlọtọ
CSA 2.1-06
|
|
Enyere ike
750 kVA
|
|
Ugboro ugboro
60HZ
|
|
Usoro
3
|
|
Nri
Loop
|
|
N'ihu
Nwụrụ anwụ
|
|
Ụdị oyi
ONAN
|
|
Voltaji nke mbụ
25D kV
|
|
Voltaji nke abụọ
0.6Y/0.347 kV
|
|
Ngwa ikuku
Aluminom
|
|
Ntugharị akụkụ
Dyn1
|
|
Mgbochi
4.75%
|
|
Pịa Changer
NLTC
|
|
Ọkụ aka
±2*2.5%
|
|
Enweghị mfu ibu
1.4 kW
|
|
Na Ibu Mfu
8.03 kW
|
|
Ngwa ngwa
Nhazi ọkọlọtọ
|
1.3 Eserese
750 kVA mpe mpe akwa akwadoro eserese eserese na nha.
![]() |
![]() |
02 Nrụpụta
2.1 Isi
Nke a 750kVA mpe mpe akwa - mgbakwasa transformer na-eji elu{2}}ọkwa CRGO isi laminations na a nkenke atọ-phase, three- nhazi ọkwa. Nzọụkwụ - n'apata chịkọtara lamination na-egosipụta nkwonkwo mitred ogo 45 yana njikọ epoxy iji belata mfu ma hụ nkwụsi ike nhazi. Nhazi lamination a kachasị mma na-enye arụmọrụ dị elu, na-ezute ụkpụrụ CSA, yana nhọrọ igwe amorphous maka ngwa ultra- dị elu. Ihe owuwu siri ike na-ekwe nkwa ịrụ ọrụ a pụrụ ịdabere na ya na gburugburu akụrụngwa na-achọsi ike.

2.2 Ikuku

Nke a 3 winding transformer nwere nkenke -Ejikere ikuku ikuku HV/LV na-eji igwe aluminom nwere ihe mkpuchi. The HV winding na-eji oyi akwa{3}}ọnya, ebe LV na-eji foil/helical wuo maka ikike dị ugbu a. Nhazi nke ikuku 3 na-eme ka mgbanwe voltaji na-agbanwe agbanwe. Axial/radial bracing na-eguzogide ike gburugburu- dị mkpụmkpụ.
2.3 tank
Ihe ngbanwe eco{0}enyi na enyi na-enwe mmetụta corrosion{1}na-eguzogide, ntụ ntụ{2}}ihe mkpuchi nchara nwere ntụ-n'efu, na-enye nchebe UV na nchekwa gburugburu ebe obibi. Ntupu 100%-ichepụta tankị akwụkwọ ndụ akwụkwọ ndụ na-egbochi mmetọ ala ma na-akwado mmiri mmiri FR3 nwere ike imebi. Emebere ya maka nkwado na arụmọrụ, ọ na-arụ ọrụ dị jụụ (<65dB) and includes reinforced lifting points with optional seismic bracing.

2.4 Mgbakọ ikpeazụ

1. Mgbakọ winding & isi stacking
Tinye ikuku HV/LV na isi ụkwụ, na-ahụ na ntinye mkpuchi kwesịrị ekwesị.
Fanye yoke laminations wee machie isi iji mepụta sekit magnetik zuru oke.
2. Njikọ eletrik
Jikọọ ụzọ site na ịgbado ọkụ ma ọ bụ bolting, ndị na-agbanwe waya, osisi, na ọnụ ụzọ ndị ọzọ; nyochaa mkpochapụ.
3. Akụkụ na-arụ ọrụ ihicha
Nyefee akụkụ na-arụ ọrụ (isi + windings) n'ime oven maka agụụ{1}}na-ekpo ọkụ{2}} ikuku ihicha ruo mgbe ọdịnaya mmiri ruru ụkpụrụ.
4. Ntinye tankị
Weba akụkụ ahụ a mịrị amị na-arụ ọrụ n'ime tankị ahụ, kwụ n'ahịrị, ma chekwaa ya na ihe mgbochi; mechie mkpuchi tank.
5. Ngwa mgbakwunye
Wụnye ngwa dị ka bushes, ngwaọrụ enyemaka nrụgide, igwe mmanụ, bayonet fuse, na wiring njikwa.
6. Ndochi mmanụ & akara
Vacuum- juputara na mmanụ mkpuchi ruo ọkwa akọwapụtara. Mgbe edozichara, nwalee ike dielectric mmanụ na ọdịnaya mmiri; mee nyocha nlele ikpeazụ.
03 Nnwale
|
Mba. |
Nwale ihe |
Nkeji |
Ụkpụrụ nnabata |
Ụkpụrụ ndị atụtara |
Mmechi |
|
1 |
Ntụle Nguzogide |
% |
Ọnụego enweghị nguzozi kacha nguzogide |
0.81 |
Gafe |
|
2 |
Nlele oke |
% |
Ngbanwe nke oke voltaji na ọpịpị bụ isi: Ihe na-erughị ma ọ bụ haha 0.5% |
0.00 |
Gafe |
|
3 |
nkeji -nnwale mmekọ |
/ |
Dyn1 |
Dyn1 |
Gafe |
|
4 |
Ọ dịghị - ibu mfu na mkpali ugbu a |
/ |
I0 :: nye uru a tụrụ atụ |
0.53% |
Gafe |
|
P0: nye uru a tụrụ atụ |
1.197kW |
||||
|
nnabata maka enweghị ibu ibu bụ +10% |
/ |
||||
|
5 |
Ibu na-efunahụ voltaji impedance na arụmọrụ |
/ |
t:85 ogo nnabata maka impedance bụ ± 7.5% Nkwenye maka mkpokọta mfu ibu bụ +6% |
/ |
Gafe |
|
Z%: uru tụrụ |
4.55% |
||||
|
Pk: uru tụrụ |
7.325kW |
||||
|
Pt: uru tụrụ |
8.522 kW |
||||
|
Ịrụ ọrụ adịghị erughị 99.15% |
99.25% |
||||
|
6 |
Nnwale voltaji etinyere |
kV |
HV: 50kV 60s LV: 10kV 60s |
Enweghị ọdịda nke voltaji ule a na-eme |
Gafe |
|
7 |
Nnwale Nkwụghachi Voltaji butere |
kV |
Voltaji etinyere (KV): 2 Ua |
Enweghị ọdịda nke voltaji ule a na-eme |
Gafe |
|
Ogologo oge (s):48 |
|||||
|
Ugboro (HZ): 150 |
|||||
|
8 |
Ule ntapu |
kPa |
Ntinye nrụgide: 20kPA Ogologo oge: 12h |
Enweghị ntapu na mba Mmebi |
Gafe |
|
9 |
Ntụle Nguzogide mkpuchi |
GΩ |
HV -LV gaa n'ala |
10.6 |
/ |
|
LV-HV gaa n'ala |
10.4 |
||||
|
HV&LV ruo Ground |
9.12 |
||||
|
10 |
Nnwale mmanụ |
/ |
Ike Dielectric; |
57,3 kV |
Gafe |
|
Ọdịnaya Ọdịnaya |
9.9 mg / n'arọ |
||||
|
Ihe nchụsa |
0.00247% |
||||
|
Nyocha nke Furan |
0.03 |
||||
|
Nyocha chromatography gas |
/ |


04 Mbukota na mbupu
4.1 mbukota
Mpempe akwụkwọ - ngwungwu mgbanaka mgbanaka na-eji igbe osisi siri ike ejiri eriri igwe mesie ike, na-egosipụta oghere forklift ma ọ bụ ihe ebuli elu maka njikwa. A na-echekwa unit ahụ na skids osisi dị n'ime oghere ahụ, ma jiri ụfụfụ ma ọ bụ akwa rọba mee ka ọ banye n'ọgba aghara. A na-akwakọba ngwa ngwa iche iche n'ime akwa akwa akwa. A na-ekpuchi elu ahụ na mpempe akwụkwọ mmiri na-adịghị mmiri ma na-agụnye akpa ndị na-adịghị mma, ebe akara ngosi na-egosi etiti ike ndọda, nchebe mmiri, "Edola Tilt," na nkọwa nka. Ngwungwu ihe ngbanwe a na-eme ka ọ ghara ịma jijiji, iru mmiri{5}na-eguzogide, yana ogologo oge{6}} nchebe n'èzí, ewepụtara ya n'ọnọdụ akpọchiri nke ọma maka mfe na- nyocha na nrụnye saịtị.

4.2 Mbupu

A ga-ebufe ihe nfefe ahụ{{0}Mounted Transformer n'okpuru usoro CIF na Port of Vancouver, Canada. Onye na-ere ahịa na-ahazi njem njem na mkpuchi isi, na-enye ISPM 15-mkpụrụ ọkụ osisi dabara adaba (ígwè{4}nke nwere akpata oyi n'ahụ-ihe na-amịkọrọ ihe) na ijikwa akwụkwọ mwepu mbupụ (akwụkwọ ọnụahịa azụmahịa, ndepụta nkwakọ ngwaahịa, akwụkwọ ikike sitere, wdg). Mbupu na-eji igbe dị elu 40ft mepere emepe ma ọ bụ akwa dị larịị, na-eji mgbanaka ihe mgbaka ọkụ maka nchekwa, yana nleba anya ọnọdụ okpomọkụ n'oge njem niile. mkpuchi mkpuchi. Ọdụ ụgbọ mmiri Vancouver chọrọ nkwuwapụta n'ihu nke ụdị mmanụ transformer (na-agbaso ụkpụrụ Canada EPA), asambodo CSA (ọ bụrụ na ọdabara), na nhazi oge windo tide maka ibutu. Akwụkwọ ga-agụnye Bill of Lading (ya na Canada Customs CCN) na mkpuchi mmanụ MSDS.
05 Saịtị na nchịkọta
Dị ka isi nkuku nke sistemu ikesa ọkụ, Pad a{0}Mounted Transformer na-ebuga ntughari ume nke a pụrụ ịdabere na ya, dị mma yana eco{1} enyi na enyi maka ụlọ ọrụ mmepụta ihe, azụmahịa na akụrụngwa ọha. Emebere ya site na ezigbo oyi -Slicon steel na ihe owuwu mechiri emechi, ọ na-eme ka mfu dị ala{4}}, ịrụ ọrụ dị jụụ ka ọ na-ezute nchedo IP67 na ụkpụrụ zuru ụwa ọnụ. Nhazi tankị kọmpat na-ebuli ohere, yana nleba anya smart smart na-eme ka njikwa dịpụrụ adịpụ. CSA/UL kwadoro maka nnabata nke North America, ọ na-ekwe nkwa ịrụ ọrụ na-adịgide adịgide na oke ihu igwe yana nnukwu ọnọdụ - na-eme ka ọ bụrụ nhọrọ kacha mma maka akụrụngwa grid ọgbara ọhụrụ.

Ihe nchịkọta dị ọkụ: 750 kva mpe mpe akwa ugwu transformer, onye nrụpụta, soplaya, price, efu
You Might Also Like
75 kVA 3 Ngbanwe nkesa nkesa-13.8 / 0.208 kV|Canada ...
150 kVA Pad Nkwanye Ntugharị-34.5 / 0.208 kV|USA 2024
300 kVA Pad Mount Transformer-12.47 / 0.48 kV|USA 2024
500 kVA Pad Nkwanye ebe obibi Transformer-34.5 / 0.4...
2500 kVA Pad Mount Transformer-12.47 / 0.48 kV|USA 2025
1500 kVA Pad Mount Transformer-13.8 / 0.46 kV|Guyana...
Zipu ozi