500 KVA Green Electric Transformer Box-23.9 / 0.22 KV|Jamaica 2025
Ike: 500 kVA
Voltaji: 23.9GrdY/13.8-0.22/0.11d kV
Njirimara: na ntinye nkwụsịtụ ibu

Tọọ ya wee chefuo ya. Ike na-adịghị agbanwe agbanwe sitere na Pad Pad anyị na-agbanye n'ụzọ atọ.
01 Izugbe
1.1 Nkọwa oru ngo
500 kVA three phase pad mounted transformer e zigara Jamaica na 2024. Ike nke transformer bụ 500 kVA na ONAN jụrụ oyi. The elu voltaji bụ 23.9GrdY / 13.8 kV na ± 2 * 2.5% tapping nso (NLTC), obere voltaji bụ 0.22 / 0.11d kV, ha guzobere vector otu YNd11.
Ihe mgbanaka ahụ{{0}Edogoro n'elu bụ isi nkuku nke nkesa ọkụ eletrik n'okpuru ala ọgbara ọhụrụ, na-ejikọtaghị ọdịiche dị n'etiti ahịrị ịba uru voltaji dị elu yana mkpa dị ala{2} nke ụlọ, azụmahịa, na obodo. Emebere ya maka ntụkwasị obi, nchekwa, na njikọta ihe ịchọ mma, nkeji ndị a siri ike, igwe{4} agbachitere bụ ebe niile na ihe dị egwu na mpaghara mpaghara, plaza azụmahịa, na ogige ụlọ ọrụ mmepụta ihe.
N'adịghị ka okporo osisi ọdịnala - agbakwunyere nkeji , pad - ndị na-ebunye ihe nrụnye ka a na-agbanye n'ala nke ọma ma tinye ya n'obere ihe dị n'ala. Nhazi a na-ebute nchekwa ọha ụzọ site na iji ihe mgbochi- na-eguzogide, mkpuchi akpọchi nke na-echebe ihe ndị dị ndụ pụọ na ohere na-enyeghị ikike na ihe ndị ahụ. Nhazi ha dị ala- na-ebelata mmetụta anya na oghere, na-enye ha ohere ịgwakọta nke ọma n'ime odida obodo ebe ha na-ebuga ike nkeji atọ- ma ọ bụ otu - dị mkpa.
Ewubere ya ka ọ nagide ọnọdụ gburugburu ebe obibi siri ike, pad anyị{0}} ihe nrụnye mgbanaka bụ otu ihe na ịdịte aka yana obere ọrụ nlekọta{{1}. Ha na-anọchite anya ntinye ego dị mkpa na akụrụngwa ike na-agbanwe agbanwe ma na-arụ ọrụ nke ọma, na-eme ka nnyefe ọkụ eletrik dị mma, kwụsie ike na nke a pụrụ ịdabere na ya ozugbo ebe ọ kacha mkpa.
1.2 Nkọwa nka nka
500 kVA mpe mpe akwa akwadoro ụdị nkọwapụta na mpempe data
|
Enyere ya
USA
|
|
Afọ
2024
|
|
Ụdị
Ihe mgbakwasa na mpe mpe akwa
|
|
Ọkọlọtọ
IEEE Std C57.12.34-2022
|
|
Enyere ike
500 kVA
|
|
Ugboro ugboro
60HZ
|
|
Usoro
3
|
|
Nri
Loop
|
|
N'ihu
Nwụrụ anwụ
|
|
Ụdị oyi
ONAN
|
|
Voltaji nke mbụ
23.9GrdY/13.8kV
|
|
Voltaji nke abụọ
0.22/0.11d kV
|
|
Ngwa ikuku
Ọla kọpa
|
|
Otu Vector
YNd11
|
|
Mgbochi
5%
|
|
Ịrụ ọrụ
99.26%
|
|
Pịa Changer
NLTC
|
|
Ọkụ aka
±2*2.5%
|
|
Enweghị mfu ibu
0,725 kW
|
|
Na Ọnwụ Ebu
7,4 kW
|
1.3 Eserese
500 kVA mpe mpe akwa akwadoro eserese eserese na nha.
![]() |
![]() |
02 Nrụpụta
2.1 Isi

Ihe ngbanwe ahụ na-eji kọmpat atọ-fase ise-isi ụkwụ. Nhazi a dị elu na-ebelata mfu magnetik na mkpọtụ ebe ọ na-eme ka nkwụsi ike arụ ọrụ, na-ebuga arụmọrụ dị elu maka mkpa nkesa ike ọgbara ọhụrụ.
2.2 Ikuku
Mpempe akwụkwọ - mgbakwasa ahụ nwere atụmatụ windings composite windings nwere obere-voltaji foil yana ihe nrụpụta waya voltaji dị elu, nke ejiri ọla kọpa dị elu mee-ha abụọ. Nhazi a na-eme ka ọ dị mma na-ekposa ọkụ, nguzogide mkpirisi mkpirisi dị mkpụmkpụ{5}, yana ezigbo ojiji oghere. Sistemụ ikuku ọla kọpa niile- na-ebulite arụmọrụ, mbelata mfu, yana arụrụ ọrụ a pụrụ ịdabere na ya n'ime oge ndụ nke transformer na-arụ ọrụ.

2.3 tank

A na-arụ tankị nke ngbanwe site na nchara dị nro na-adịgide adịgide, na-enye nchebe igwe siri ike na mgbasa ọkụ dị irè maka ihe ndị dị n'ime. Nhazi ya agbadoro agbadoro na-ahụ na mmanụ zuru oke{1} n'iguzosi ike n'ezi ihe ma na-anagide nrụgide gburugburu ebe obibi. Nhazi nke tank ahụ na-agụnye nhịahụ dị jụụ iji kwalite mpaghara elu maka njikwa okpomọkụ, na-ejigide okpomọkụ na-arụ ọrụ n'oge ndụ ọrụ.
2.4 Mgbakọ ikpeazụ
Mkpọkọta ikpeazụ nke mpe mpe akwa{0} agbakwunyere ngbanwe na-ejikọta isi, windings na components n'ime tankị nchara dị nro mechiri emechi, nke na-ejupụta na mmiri dielectric. A na-emecha mgbakọ ahụ site na ịtinye bushes, ngwaọrụ nchebe, na ngwa njikwa na tank ahụ mechiri emechi.

03 Nnwale
Nnwale na-eso ụkpụrụ IEEE dịka IEEE C57.12.00-2021, IEEE Std C57.12.34-2022, na IEEE C57.12.90-2021. Nnwale ndị a na-eme oge niile gụnyere nha nguzogide ikuku, ule voltaji, ule mmekọ-, nnwale mmekọ, mfu enweghị ibu na enweghị ibu dị ugbu a, mfu ibu/voltaji impedance/nnwale arụmọrụ, ule voltaji etinyere, nnwale nnabata voltaji, nnwale ntanye (maka ụdị imi mmiri mmiri), nha mkpuchi mkpuchi, na ule mmanụ ọkụ.
|
Mba. |
Nwale ihe |
Nkeji |
Nnabata Ụkpụrụ |
Ụkpụrụ ndị atụtara |
Mmechi |
|
1 |
Ntụle Nguzogide |
% |
Ọnụego enweghị nguzozi kacha nguzogide |
0.44 |
Gafe |
|
2 |
Nlele oke |
% |
Ngbanwe nke oke voltaji na ọpịpị bụ isi: Ihe na-erughị ma ọ bụ haha 0.5% Akara njikọ: YNd11 |
-0.04% ~ 0.03% |
Gafe |
|
3 |
nkeji -nnwale mmekọ |
/ |
YNd11 |
YNd11 |
Gafe |
|
4 |
Ọ dịghị - ibu mfu na mkpali ugbu a |
/ |
I0 :: nye uru a tụrụ atụ |
0.38% |
Gafe |
|
P0: nye uru a tụrụ atụ (t:20 degrees) |
0,6546 kW |
||||
|
nnabata maka enweghị ibu ibu bụ +10% |
/ |
||||
|
5 |
Ibu na-efunahụ voltaji impedance na arụmọrụ |
/ |
t:85 ogo nnabata maka impedance bụ ± 7.5% Nkwenye maka mkpokọta mfu ibu bụ +6% |
/ |
Gafe |
|
Z%: uru tụrụ |
5.29% |
||||
|
Pk: uru tụrụ |
7.089kW |
||||
|
Pt: uru tụrụ |
7,744 kW |
||||
|
Ịrụ ọrụ adịghị erughị 99.05% |
99.10% |
||||
|
6 |
Nnwale voltaji etinyere |
kV |
HV: 40kV 60s LV: 10kV 60s |
Enweghị ọdịda nke voltaji ule a na-eme |
Gafe |
|
7 |
Nnwale Iguzogide Voltaji butere |
kV |
Voltaji etinyere (KV):2Ur |
Enweghị ọdịda nke voltaji ule a na-eme |
Gafe |
|
Voltaji ebutere (KV): 0.44 |
|||||
|
Ogologo oge (s):40 |
|||||
|
Ugboro (HZ): 150 |
|||||
|
8 |
Ule ntapu |
kPa |
Ntinye nrụgide: 20kPA |
Enweghị ntapu na mba Mmebi |
Gafe |
|
Ogologo oge: 12h |
|||||
|
9 |
Ntụle Nguzogide mkpuchi |
GΩ |
HV -LV n'ala: |
OL |
/ |
|
LV-HV gaa n'ala: |
OL |
||||
|
HV&LV n'ala: |
OL |
||||
|
10 |
Nnwale Dielectric mmanụ |
kV |
Karịrị ma ọ bụ hà nhata 45 |
58.3 |
Gafe |


04 Mbukota na mbupu
4.1 mbukota

A na-akwakọba ihe ngbanwe a na-etinye na pad n'ime igbe osisi siri ike nke e ji plywood rụọ, nke nwere pallet osisi maka ijikwa ya ngwa ngwa. Crate ahụ nwere akara mbupu nwere ntuziaka njikwa (dịka ọmụmaatụ, kwụ ọtọ, chebe mmetụta na mmiri ozuzo, akwakọla) yana mkpado nkọwapụta, na-enye nchebe siri ike maka njem dị anya-.
4.2 Mbupu
A na-ebu ya n'oké osimiri n'okpuru usoro CIF na ọdụ ụgbọ mmiri Kingston. A na-ekpuchi ya site na mkpuchi ụgbọ mmiri megide ihe ize ndụ ndị njem, na mbupu na-agbaso ụkpụrụ mbupu mba ụwa, yana akwụkwọ niile dị mkpa maka nkwụsị nke kọstọm, na-ahụ na ọ rutere n'ọdụ ụgbọ mmiri na-aga n'enweghị nsogbu na ọnọdụ dị mma.

05 Saịtị na nchịkọta
Na nchịkọta, pad a {{0}n'nkwanye ngbanwe na-ejikọta injinịa siri ike, ịrụ ọrụ a pụrụ ịdabere na ya, na ihe owuwu na-adịgide adịgide iji gboo mkpa nke nkesa ọkụ eletrik ọgbara ọhụrụ. Ezubere maka nchekwa, arụmọrụ na ogologo oge-, ọ na-enye azịza ntụkwasị obi maka ịba uru na ngwa ụlọ ọrụ mmepụta ihe. Soro anyị rụkọọ ọrụ maka akụrụngwa ike na-ebupụta ọmarịcha-ugbua na afọ ndị na-abịa.

Ihe nchịkọta dị ọkụ: igbe transformer eletriki green, onye na-emepụta ihe, onye na-eweta, ọnụahịa, ọnụ ahịa
You Might Also Like
2250 kVA Pad na-agbanye ihe ntụgharị-12.47 / 0.6 kV|...
1000 kVA Pad na-agbanye ihe ntụgharị-13.2 / 0.48 kV|...
2000 kVA Pad Mount Transformer-25 / 0.6 kV|Canada 2025
500 KVA Gịnị Bụ Mgbochi Nkwanye Transformer-12.47 / ...
250 KVA Obere mpe mpe akwa na-ebugharị ihe ntụgharị-...
500 KVA Radial Feed Transformer-12.47 * 4.16 / 0.6 K...
Zipu ozi