500 kVA pad mounted transformer

Ike ntụkwasị obi, ịrụ ọrụ nke ọma, yana nchekwa site na iji mgbanaka 500 kVA - na-ebunye ọkụ eletrik kwụsiri ike nke atọ{2} maka iji azụmahịa, ebe obibi na ụlọ ọrụ mmepụta ihe.

 

 

01 Izugbe

1.1 Nkọwa oru ngo

N'afọ 2024, SCOTECH wetara 500 kVA atọ -phase pad{3}} nke etinyere na mgbanaka na Canada. Emere ya dịka CSA C227.4: 21 si dị ma wuo ya maka iji ike a pụrụ ịdabere na ya na ụlọ azụmahịa, ụlọ, na obere ụlọ ọrụ.

Mpempe akwụkwọ {{0} agbakwunyere ngbanwe bụ ụdị nkesa nkesa nke etinyere n'ọkwa ala n'elu kọmpụta. A na-emechi ya nke ọma ma na-enwekarị ihe nwuru anwu{2}} n'ihu. Nke a na-edobe akụkụ voltaji dị elu{4} n'ime kabinet akpọchiri akpọchi. Ọ na-echebe ndị ọrụ ọha na ndị ọrụ ịba uru. Ọ na-enye ohere ohere dị mfe maka mmezi. Nkeji ahụ nwere mpe mpe akwa akwachiri{8} ma dọba ya na pad simenti maka ojiji n'èzí adịghị mma. Ọ na-agbanwe voltaji ọkara (12.47 / 4.16 kV) gaa na voltaji dị ala (0.6 kV) ma na-enye ndị ọrụ ike kwụsiri ike na nke ọma.

Ọ na-egosipụta sistemụ jụrụ oyi nke ONAN nwere mkpuchi mmanụ ịnweta mmanụ, na-enye oke ọkụ na-ekpo ọkụ yana ogologo ndụ ọrụ. Ihe ntụgharị na-agba ọsọ na 12.47 / 4.16 kV n'akụkụ nke mbụ yana 0.6 kV n'akụkụ nke abụọ. Ọ na-eji otu vector YNyn0 iji dobe ike nke nkeji atọ{6}. Ọ nwere aluminom windings, 5% impedance, na 99.5% arụmọrụ. Ọ na-arụ ọrụ na obere mfu ma na-eme ka voltaji kwụsie ike n'okpuru ibu zuru oke.

 

 

 

1.2 Nkọwa nka nka

500kVA atọ na-adọba mpe mpe akwa n'ịnyịnya ntụgharị nkọwapụta na mpempe akwụkwọ data

Enyere ya
Canada
Afọ
2024
Ụdị
Atọ nke mpe mpe akwa ugwu transformer
Ọkọlọtọ
CSA C227.4:21
Enyere ike
500KVA
Ugboro ugboro
60HZ
Nri
Loop
N'ihu
Nwụrụ anwụ
Usoro
atọ
Ụdị oyi
ONAN
Mmiri mkpuchi
Mineral Mmanụ
Voltaji nke mbụ
12.47 (4.16) kV
Voltaji nke abụọ
0,6 kV
Otu Vector
YNyn0
Ngwa ikuku
Aluminom
Mgbochi
5%
Ịrụ ọrụ
99.5%
Pịa Changer
NLTC
Ọkụ aka
±2*2.5%
Enweghị mfu ibu
Ihe na-erughị ma ọ bụ hà nhata 1090 W
Na Ibu Mfu
Ihe na-erughị ma ọ bụ hà nhata 5800 W
Ngwa ngwa
Nhazi ọkọlọtọ

 

1.3 Eserese

500kVA atọ akụkụ mpe mpe akwa n'ịnyịnya transformer ịbịaru na nameplate

500 kVA three phase pad mounted transformer 500 kVA pad mounted transformer nameplate

 

 

02 Nrụpụta

2.1 Isi

Nhazi ụkwụ ise- na-enye isi nkwado na nguzozi siri ike. Ọ na-enyere aka ibelata ntapu mmiri na mkpirisi - mgbakasị okirikiri. Ihe owuwu a na-eme ka ihe ngbanwe ahụ dị mma, kwụsie ike ma dịgidere, ọbụlagodi mgbe ọ na-arụ ọrụ na ibu dị arọ ma ọ bụ ọnọdụ dị n'èzí.

 

2.2 Ikuku

Kpọmkwem maka nhazi YNyn0, ndị ọrụ na-etinye uche pụrụ iche na nguzozi na-anọpụ iche na n'oge ikuku iji hụ na itule sekit magnetik atọ{1} na mkpụmkpụ{2}} mgbochi okirikiri. Ntugharị ikuku kọmpat na-ebelata mfu ka ị na-ejigide okpomọkụ kacha mma.

 

2.3 tank

500 kVA pad mounted transformer oil tank

A na-ekpuchi tankị nke na-agbanwe agbanwe na mkpuchi mkpuchi ma jiri ígwè dị nro mee ihe. Ọ nwere ike were nrụgide dị n'ime 50 kPa na-enweghị nkwụsị ọ bụla ma ọ bụ nrụrụ na-adịgide adịgide karịa 0.25% nke diagonal elu. Emebere kabinet ka ọ bụrụ ihe na-emebi emebi{4} na ihu igwe na-eguzogide. A na-eji bolts pentahead dọọrọ n'agha kwekọrọ n'usoro CSA C227.4 chọrọ.

 

2.4 Mgbakọ ikpeazụ

Anyị na-agbaso usoro arụ ọrụ ahaziri ahazi, na-enye nduzi doro anya maka nzọụkwụ ọ bụla nke mgbakọ transformer na ibelata ejighị n'aka nke ọrụ ntuziaka. Ejikọtara ya na sistemu mmepe otu ọkachamara, site na ọzụzụ usoro na usoro nkuzi{1}, anyị na-ahụ na onye ọrụ ọ bụla nwere ike ịrụ ọrụ dị elu{2}. Nke a zuru okè Nchikota usoro na ndị mmadụ na-etolite ntọala nke anyị kasị ike ngwaahịa àgwà.

 

 

03 Nnwale

Nnwale Ọkọlọtọ na Nnwale oge

CSA C227.4-21

Atọ -, pad {{1} 

CSA{0}C802.1-13 (R2022)

Uru arụmọrụ kacha nta maka Liquid{0}}Mgbanwe nkesa juputara

 

1. Ntụle Nguzogide
2. Nnwale oke
3. Nnwale mmekọrịta nke oge
4. Ọ dịghị ibu efu na ọ dịghị ibu ugbu a
5. Ibu efu Impedance voltaji na arụmọrụ
6. Nnwale voltaji etinyere
7. Nnwale anabatara voltaji
8. Nnwale leak na nrụgide maka mgbanwe mgbanwe mmiri mmiri
9. Ntụle Nguzogide mkpuchi
10. Oil Dielectric Test
 

Nsonaazụ ule

500 kVA pad mounted transformer routine test
500 kVA pad mounted transformer test

 

Nwale ihe

Nkeji

Nnabata

Ụkpụrụ

Ụkpụrụ ndị atụtara

Mmechi

1

Ntụle Nguzogide

%

Ọnụego enweghị nguzozi kachasị elu

1.27

Gafe

2

Nlele oke

%

Ngbanwe nke oke voltaji na ọpịpị bụ isi: Ihe na-erughị ma ọ bụ haha ​​0.5%

-0.04-0.10

Gafe

3

nkeji -nnwale mmekọ

/

YNyn0

YNyn0

Gafe

4

Ọ dịghị - ibu mfu na mkpali ugbu a

/

I0 :: nye uru a tụrụ atụ

0.37%

Gafe

P0: nye uru a tụrụ atụ

0.7317kW

nnabata maka enweghị ibu ibu bụ +10%

/

5

Ibu na-efunahụ voltaji impedance na arụmọrụ

/

t:85 ogo

nnabata maka impedance bụ ± 7.5%

Nkwenye maka mkpokọta mfu ibu bụ +6%

/

Gafe

Z%: uru tụrụ

5.35%

Pk: uru tụrụ

4.483kW

Pt: uru tụrụ

5.247kW

Ịrụ ọrụ adịghị erughị 99.05%

99.29%

6

Nnwale voltaji etinyere

kV

HV: 34kV 60s

LV: 10kV 60s

Enweghị ọdịda nke voltaji ule a na-eme

Gafe

7

Nnwale Nkwụghachi Voltaji butere

kV

Voltaji etinyere (KV):

2 Ua

Enweghị ọdịda nke voltaji ule a na-eme

Gafe

Ogologo oge (s):30

Ugboro (HZ): 240

8

Ule ntapu

kPa

Ntinye nrụgide: 20kPA

Ogologo oge: 12h

Enweghị ntapu na mba

Mmebi

Gafe

9

Ntụle Nguzogide mkpuchi

GΩ

LV-HV gaa n'ala

7.8

/

HV&LV ruo Ground

8.0

10

Nnwale mmanụ

/

Ike Dielectric;

51,8kv

Gafe

Ọdịnaya Ọdịnaya

11.5 mg / kg

Ihe nchụsa

0.00298%

Nyocha nke Furan

Ihe na-erughị ma ọ bụ hà nhata 0.1

Nyocha chromatography gas

/

 

 

04 Mbukota na mbupu

500 kVA three-phase pad-mounted transformer packing
500 kVA pad-mounted transformer packing
500 kVA three-phase pad-mounted transformer shipping

 

05 Saịtị na nchịkọta

500 kVA three-phase pad-mounted transformer

Anyị 500 kVA atọ -pase pad{2}} mgbanaka mgbanaka na-enye ike a pụrụ ịdabere na ya na ịrụ ọrụ nke ọma maka netwọk nkesa Canada. Ọ na-ezute ụkpụrụ CSA C227.4:21. Ihe ngbanwe ahụ nwere isi ụkwụ- siri ike na ikuku aluminom. A na-emechi tankị ahụ na enweghị ihu igwe. Ndị ọrụ nwere nkà na-achịkọta ngalaba nke ọ bụla nke ọma. Ihe ngbanwe ahụ na-edobe ike nke nkeji atọ{11} ma na-eji obere mfu. Ọ na-eji ONAN jụrụ ma na-enye voltaji kwụsiri ike n'okpuru ibu zuru oke.

 

Ihe nchịkọta dị ọkụ: Kedu ihe bụ ihe nkwụnye ọkụ, onye nrụpụta, onye na-eweta ihe, ọnụahịa, ọnụ ahịa

Zipu ozi