630 kVA Vacuum Pressure Impregnated Transformer-11 / 0.55 kV|South Africa 2025
Ike: 630kVA
Voltaji: 11/0.55kV
Njirimara: ya na ndị fan na ọkwa mkpuchi H

Nkesa Ike Smart, Ọdịnihu Green - Mepee ndị ntụgharị ikuku na-ekpo ọkụ maka ịdịgide!
01 Izugbe
1.1 Nkọwa oru ngo
The 630 kVA oghere winding akọrọ ụdị transformer e nyefere South Africa na 2025. The gosiri ike nke oghere winding akọrọ ụdị transformer bụ 630 kVA na AN / AF jụrụ, isi voltaji bụ 11 kV na ± 2 * 2.5% tapping nso (NLTC), nke abụọ voltaji bụ 0.55kV, ha guzobere a vector otu.
A na-emezi ihe ngbanwe nke ụdị akọrọ nke imepe emepe maka ịrụ ọrụ dị elu, na-ejikọta teknụzụ dị elu na ihe owuwu siri ike iji gboo mkpa ike ụlọ ọrụ na azụmaahịa na-achọsi ike. N'igosi onye njikwa okpomọkụ nwere ọgụgụ isi, ọ na-eme ka njikwa okpomọkụ kacha mma, ebe e wuru ya{1} na ndị na-eme ka ọ dị jụụ na-akwalite mgbasa ọkụ maka ịrụ ọrụ na-agbanwe agbanwe ọbụlagodi n'okpuru ibu dị arọ.
Emebere ya na mkpuchi klaasị H, ihe ngbanwe a na-anagide gburugburu okpomọkụ{0}, na-akwado ịrị elu okpomọkụ 100K maka ịrụ ọrụ ogologo oge-. Dakọtara na 110V ike ọkọnọ, ọ na-anapụta ike voltaji mgbanwe na ntakiri ike ọnwụ.
Dị mma maka automation ụlọ ọrụ mmepụta ihe, sistemu ume ọhụrụ na akụrụngwa dị oke egwu, igwe ọkụ anyị kpọrọ nkụ{0}ụdị transformer na-enye ọrụ nrụzi{1} n'efu, nchekwa emelitere (enweghị ihe egwu ọkụ), yana arụmọrụ eco{2} (enweghị mmanụ ma ọ bụ ihe nsi). Kwalite ka ọ bụrụ ihe amamihe dị na ya, ike na-agbanwe agbanwe taa!
1.2 Nkọwa nka nka
630 kVA VPI akọrọ ụdị ntụgharị nkọwapụta na mpempe akwụkwọ data
|
Enyere ya
South Africa
|
|
Afọ
2025
|
|
Ụdị
Mepee igwe ngbanwe nke ikuku akọrọ
|
|
Isi ihe
Mpempe akwụkwọ silicon na-adabere na ọka
|
|
Ọkọlọtọ
IEC60076
|
|
Enyere ike
630kVA
|
|
Ugboro ugboro
50HZ
|
|
Otu vector
Dyn11
|
|
Usoro
3
|
|
Ụdị oyi
ONAN/ONAF
|
|
Voltaji nke mbụ
11 kV
|
|
Voltaji nke abụọ
0,55 kV
|
|
Ngwa ikuku
Aluminom
|
|
Mgbochi
6%
|
|
Pịa Changer
NLTC
|
|
Ọkụ aka
± 2 * 2.5% @ akụkụ mbụ site na ịpị njikọ
|
|
Enweghị mfu ibu
1.1KW
|
|
Na Ọnwụ Ebu
8.3KW
|
|
Ọkwa mkpuchi
H
|
1.3 Eserese
630 kVA VPI akọrọ ụdị ihe ngbanwe eserese eserese na nha.
![]() |
![]() |
02 Nrụpụta
2.1 Isi
Igwe ngbanwe ikuku na-emepe-ụdị transformer nwere nnukwu-permeability silicon steel laminated core nke na-enweta ọgwụgwọ nhịahụ nke ọma iji belata mfu sekit magnetik. Isi ihe na-anakwere usoro mkpokọ steepụ nke ọma iji belata mfu ugbu a nke ọma, jikọtara ya na teknụzụ mpịachi pụrụ iche iji hụ na ọ dị jụụ, mkpọtụ{3}} na-arụ ọrụ n'efu.

2.2 Ikuku

Ihe ngbanwe ahụ na-egosi nkenke{0}} wires aluminom merụrụ ahụ nwere mkpuchi mkpuchi ọtụtụ-SHS (Super Heat{2}}Synthetic na-eguzogide), nwere ike iguzogide okpomọkụ ruo ogo 220. Mmepe ikuku ọhụrụ ya- na-eme ka ikpochapụ okpomoku kacha mma ka ọ na-ejigide arụmọrụ Klas H (mbili elu okpomọkụ 100K). Ọdịdị ikuku na-ejikọta nkwụsi ike n'ibu ike yana ike dielectric mara mma, na-enye nguzogide dị elu maka ujo ọkụ, ịma jijiji na mwepu akụkụ.
2.3 Mgbakọ ikpeazụ
1) Precision mounting of SHS-insulated coils onto CRGO cores; 2) Stepped-lamination upper yoke installation with 15-20kN/m clamping force; 3) install cooling fans and PT100 smart temperature controller (150℃ alarm/180℃ trip); 4) install terminal connections passing 5000V insulation tests (>1000MΩ).

03 Nnwale
|
Mba. |
Nwale ihe |
Nkeji |
Ụkpụrụ nnabata |
Ụkpụrụ ndị atụtara |
Mmechi |
|
|
1 |
Ntụle nke winding iguzogide |
/ |
Ọnụego enweghị nguzozi kacha nguzogide Nguzogide ahịrị: Ihe na-erughị ma ọ bụ haha 2% |
HV (akara) |
LV (akara) |
Gafe |
|
0.29% |
0.84% |
|||||
|
2 |
Ntụle nke oke voltaji na nlele nke mbugharị oge |
/ |
Nkwenye nke oke voltaji na ọpịpị bụ isi: ± 1/10 Akara njikọ: Dyn11 |
-0.02% ~ 0.13% Dyn11 |
Gafe |
|
|
3 |
Ntụnye nke Mkpirisi-Mkpirisi okirikiri na mfu ibu |
/ kW kW |
t:145 ogo Z%: uru tụrụ Pk: uru tụrụ Pt: uru tụrụ |
6.22% 4.745 6.485 |
Gafe |
|
|
4 |
Ntụle nke mba- ibu mfu na ugbu a na 90% na 110% nke voltaji e gosiri |
/ kW |
I0 :: nye uru a tụrụ atụ P0: nye uru a tụrụ atụ |
90% Uru |
0.36 0.978 |
Gafe |
|
100% Ur |
0.40 1.087 |
|||||
|
110% Ur |
0.44 1.195 |
|||||
|
5 |
Nnwale voltaji etinyere |
/ |
HV: 35kV 60s LV: 3kV 60s |
Enweghị ọdịda nke voltaji ule a na-eme |
Gafe |
|
|
6 |
Nnwale Nkwụghachi Voltaji butere |
/ |
Voltaji etinyere (kV): 2 Ua Voltaji ebutere (kV): 1.1 Ogologo oge (s):40 Ugboro (HZ): 150 |
Enweghị ọdịda nke voltaji ule a na-eme |
Gafe |
|
|
7 |
Nnwale mgbapu akụkụ |
pC |
Ọkwa kacha nke mwepu akụkụ ga-abụ 10 pC |
<10 |
Gafe |
|


04 Mbukota na mbupu
4.1 mbukota
A na-ejuju ụdị ngbanwe akọrọ{0} n'ime igbe osisi siri ike nwere ihe nkpuchi dị n'ime maka njem adịghị mma. Ngwa niile gụnyere ihe njikwa okpomọkụ na ndị fan, na-abịa tupu etinyere{2} dị ka nkeji zuru oke. Akara mpụta nke ọma na ntuziaka njikwa, na-enye mmiri a pụrụ ịdabere na ya na nchebe ujo maka mbupu ihe ntụgharị ogologo-.

4.2 Mbupu

A ga-ebupu ihe ngbanwe nke ụdị nkụ nke imeghe CIF Durban n'ụjọ-ọkụ osisi na-adịghị ahụkebe. Ọnụ ahịa ahụ na-ekpuchi mkpuchi mmiri na mkpochapụ kọstọm mbupụ, ebe onye nnata ga-edozi usoro mbubata. Mbupu a na-edobe oke iru mmiri/okpomọkụ na nrube isi n'ụkpụrụ mgbochi mba ofesi - maka ibu oke osimiri.
05 Saịtị na nchịkọta
Dị ka ihe ngwọta dị elu{{0} maka nnyefe na nkesa ọkụ, ụdị ihe ngbanwe nke imepe emepe na-ebuga ntụkwasị obi na-adịgide adịgide na mpaghara ụlọ ọrụ mmepụta ihe, ume, na akụrụngwa site na imepe emepe{1} ọhụrụ, njikwa okpomọkụ dị elu, yana mkpuchi siri ike. Na-ejikọta mmezi {{3}free arụmọrụ, eco{4}} ụlọ enyi na enyi na njikwa okpomọkụ, ọ na-eme nke ọma n'ịchọ ngwa ma na-akwado ebumnuche ike na-adigide. Soro anyị na-emekọrịta ihe maka ngwọta ike ntụkwasị obi- ebe teknụzụ na-ezute nchekwa na arụmọrụ, na-enye ike nnyefe ike ka mma.

Ihe nchịkọta dị ọkụ: oghere mgbali impregnated transformer, nrụpụta, soplaya, price, efu
You Might Also Like
500 kVA Pad Mount Transformer-13.8 / 0.48 kV|USA 2025
1000 kVA Vpi Transformer-11 / 0.55 kV|South Africa 2024
630 kVA General Electric Dry Type Transformers-11 / ...
630 kVA Akọrọ Ụdị Nzọụkwụ Down Transformer-11 / 0.55...
630 kVA Ụdị Akọrọ Ike Transformer-11 / 0.55 kV|South...
630 kVA Vpi Ụdị ntụgharị-11 / 0.55 kV|South Africa 2025
Zipu ozi