862 kVA nkeji Substation-13.8/0.48 kV|USA 2025

862 kVA nkeji Substation-13.8/0.48 kV|USA 2025

Obodo: America 2025
Ike: 750/862 kVA
Voltaji: 13.8-0.48/0.277kV
Njirimara: ya na mmanụ FR3
Zipu ozi

 

 

image001

Ike Smart, Nchekwa Kasị Elu. Anyị Unit Substation Transformers.

 

 

01 Izugbe

1.1 Nkọwa oru ngo

750/862 kVA unit substation transformer ka ebugara Canada na 2025. Akara ikike nke transformer bụ 750/862 kVA na KNAN/KNAF jụrụ oyi. Isi voltaji bụ 13.8 kV na ± 2 * 2.5% tapping range (NLTC), nke abụọ voltaji bụ 0.48 / 0.277 kV, ha guzobere a vector otu Dyn1.

Emebere ya maka ịrụ ọrụ dị elu yana ntụkwasị obi, igwe ngbanwe nke 750/{1}} kVA na-ebunye ngwọta ike zuru oke ahaziri maka ngwa azụmahịa na ụlọ ọrụ na-achọsi ike. Ọ na-egosipụta FR3® eke ester mmiri maka nchekwa ọkụ na-abawanye na ndụ mkpuchi ogologo, yana arụ ọrụ ọkụ kachasị mma (Op mmanụ: 45K, Winding Avg: 50K, Hot Spot: 63K) iji hụ na arụmọrụ na ịdịte aka n'okpuru ọnọdụ ibu dị elu. The transformer bụ nkwụsi ike - n'ala maka mma usoro nchebe na-abịa n'ụzọ zuru ezu ngwa mgbakwunye -gụnyere CT kabinet maka metering na nchedo, ikewapụ radiators nwere fan jụrụ oyi, wiil maka mfe n'ọnọdu, ngwa ngwa ịrị elu ịrị elu maka ime mgbochi mmejọ, na ọkụ ọkụ na-ejide maka ịwa ahụ nchebe{10}na-enye ike dị njikere maka ịwụnye,{11} nchekwa, ntụkwasị obi, na ịdị mfe nke mmezi.

 

 

1.2 Nkọwa nka nka

750/862 kVA unit substation transformer ụdị nkọwa na mpempe akwụkwọ data

Enyere ya
America
Afọ
2025
Ụdị
Ihe ntụgharị ọdụ ụgbọ mmiri
Ọkọlọtọ
ANSI C57.12.00
Enyere ike
750 862 kVA
Ugboro ugboro
60HZ
Usoro
3
Ụdị oyi
KNAN/KNAF
Voltaji nke mbụ
13.8 kV
Voltaji nke abụọ
0.48/0.277 kV
Ngwa ikuku
Ọla kọpa
Ntugharị akụkụ
Dyn1
Mgbochi
6%
Pịa Changer
NLTC
Ọkụ aka
±2*2.5%
Enweghị mfu ibu
Ihe na-erughị ma ọ bụ hà nhata 1.16kW
Na Ọnwụ Ebu
Ihe na-erughị ma ọ bụ haha ​​7.08kW

 

1.3 Eserese

750/862 kVA unit substation transformer eserese na nha.

image003 image005

 

 

02 Nrụpụta

2.1 Isi

Isi ya bụ nkenke{0}}jiri elu-ọkwa, oyi -oka ọka akpọrela -silịlịlị ígwè gbadoro ụkwụ na ya. Ihe a, yana imewe akwa akwa dị elu, na-ebelata mfu magnetik yana ike dị ugbu a. Ihe owuwu ya siri ike na-eme ka ụda mkpọtụ dị ala na ike arụ ọrụ, na-enye ụzọ ndọta kwụsiri ike ma dị mma nke bụ isi maka ntụkwasị obi na arụmọrụ nke transformer.

 

2.2 Ikuku

A na-arụ windings nke ọma maka ịrụ ọrụ na ntụkwasị obi. Igwe ikuku dị ala -voltaji na-eji ụdị ọnyà-, na-enye ike n'ịrụ ọrụ dị oke mma, mkpọsa ọkụ dị elu, yana nnukwu mkpirisi ike iguzogide gburugburu{{3}. Na-emeju ya, elu{5} voltaji winding na-eji ezigbo oyi akwa{6}}ọnya nwere mkpuchi mkpuchi siri ike{7}, na-eme ka mgbanwe voltaji dị na ya na nkwalite ike dielectric. Ngwakọta egosipụtara na-enye arụmọrụ pụrụ iche, nkwụsi ike na ịdịte aka.

image007

 

2.3 tank

image009

Ihe owuwu nke tank ahụ bụ ihe siri ike, nke ejiri welded emebere maka ịdịte aka na ịrụ ọrụ. Ọ na-eje ozi dị ka ebe nchekwa maka isi na windings, na-enye ebe nchekwa mkpuchi maka ikpuchi mmiri mmiri, na-egosipụtakwa radiators maka ịgbasa ọkụ dị mma. Emebere ya ka ọ nagide nrụgide gburugburu ebe obibi na arụ ọrụ, tankị ahụ na-ahụ na ogologo oge na ntụkwasị obi nke transformer-.

 

2.4 Mgbakọ ikpeazụ

Mgbakọ ikpeazụ bụ njikọ ziri ezi nke isi, windings, tank, na ngwa n'ime usoro jikọtara ọnụ na nke siri ike. Usoro a dị oke egwu na-achọpụta na echekwabara njikọ eletriki niile dị n'ime, ihe arụrụ arụ na-ada ụda, na agbachikwara nke ọma. Nsonaazụ bụ nke zuru oke nke onwe ya{2}nwere, dị njikere-maka{4}} nkeji ike arụ ọrụ nke na-ebuga arụmarụ arụrụ arụ, ịdịte aka na ntụkwasị obi.

image011

 

 

03 Nnwale

Mba.

Nwale ihe

Nkeji

Ụkpụrụ nnabata

Ụkpụrụ ndị atụtara

Mmechi

1

Ntụle Nguzogide

%

Ọnụego enweghị nguzozi kacha nguzogide

3.19

Gafe

2

Nlele oke

%

Ngbanwe nke oke voltaji na ọpịpị bụ isi: Ihe na-erughị ma ọ bụ haha ​​0.5%

-0.05~0.01

Gafe

3

Usoro{0}}Nnwale mmekọrịta

/

Dyn1

Dyn1

Gafe

4

Ọ dịghị - ibu mfu na mkpali ugbu a

%

I0 :: nye uru a tụrụ atụ

0.47

Gafe

kW

P0: nye uru a tụrụ atụ

0.938

/

nnabata maka enweghị ibu ibu bụ +0%

/

5

Mfu ibu , impedance voltaji, ngụkọta mfu na arụmọrụ

/

t:85 ogo

nnabata maka mgbochi bụ +7.5%

Nkwenye maka mkpokọta mfu ibu bụ +0%

/

Gafe

%

Z%: uru tụrụ

6.20

kW

Pk: uru tụrụ

6.903

kW

Pt: uru tụrụ

7.841

%

Ịrụ ọrụ adịghị erughị 99.16%

99.21

6

Nnwale voltaji etinyere

/

HV: 34kV 60s

LV: 10kV 60s

Enweghị ọdịda nke voltaji ule a na-eme

Gafe

7

Nnwale Iguzogide Voltaji butere

/

Voltaji etinyere (KV): 0.96

Enweghị ọdịda nke voltaji ule a na-eme

Gafe

Ogologo oge (s):40

Ugboro (HZ): 180

8

Ntụle Nguzogide mkpuchi

GΩ

HV -LV n'ala:

8.18

Gafe

LV-HV gaa n'ala:

3.79

HV&LV n'ala:

8.98

9

Ule ntapu

/

Ntinye nrụgide: 50kPA

Enweghị ntapu na mba

Mmebi

Gafe

Ogologo oge: 12h

10

Nnwale mkpali ọkụ

kV

ife zuru oke

Enweghị ọdịda nke voltaji ule a na-eme

Gafe

11

Nnwale mmanụ

kV

Ike Dielectric

Uru tụrụ atụ Karịrị ma ọ bụ nhata na 45 kV

68.4

Gafe

mg/kg

Ọdịnaya Ọdịnaya

168.6

%

Ihe nchụsa

3.751

mg/kg

Nyocha nke Furan

/

/

Nyocha chromatography gas

/

 

image013
image015

 

 

04 Mbukota na mbupu

4.1 mbukota

A na-akpakọba ihe ngbanwe nke unit ahụ na-elekwasị anya na nchekwa echekwara yana njikwa arụmọrụ. A na-ekobere ya na ntọala siri ike, nke gbapụrụ agbapụ maka iguzosi ike n'ezi ihe nhazi yana ịnweta ndụdụ forklift. A na-akwado ihe ndị dị mkpa, na akụkụ ahụ dum bụ ihu igwe{2} akwadoro iji hụ na ị ga-ebufe na nchekwa, na-erute na saịtị dị njikere maka nwụnye.

 

4.2 Mbupu

A na-akwado igwe ngbanwe nke otu maka ibu oke osimiri na-aga United States nwere mkpuchi ihu igwe siri ike- echekwara na akpa mbupu mba ofesi. Akara ya nke ọma na ebe ebuli elu, etiti{2} nke{3}} ihe nleba anya ike ndọda, na akwụkwọ kọstọm iji hụ na njikwa adịghị mma, njem kwụsiri ike, yana nwechapụ nke ọma mgbe ọ rutere n'ọdụ ụgbọ mmiri US.

 

05 Saịtị na nchịkọta

Karịa naanị otu akụrụngwa, ihe ngbanwe nke ngalaba a bụ obi ntụkwasị obi nke akụrụngwa eletriki gị. Ọ na-egosipụta nraranye maka ịdịte aka, nchekwa, na arụmọrụ, emepụtara iji wepụta ike anaghị akwụsị akwụsị maka ọrụ gị kacha mkpa. Họrọ ya dị ka isi nkuku nke ọrụ gị maka ịrụ ọrụ nke na-adịgide adịgide.

Kpọtụrụ anyị taa ka ị wepụta ihe ngwọta ahaziri maka mkpa gị.