25 KVA Single Phase Pole Transformer-25 / 0.347 KV|Canada 2024

25 KVA Single Phase Pole Transformer-25 / 0.347 KV|Canada 2024

Obodo nzipu: Canada 2024
Ike: 25 kVA
Voltaji: 25/0.347kV
Njirimara: Igwe ọkụ okpukpu abụọ dị elu{{0}
Zipu ozi

 

25 kVA single phase pole transformer

25 kVA otu pole transformer – ntụkwasị obi, ịrụ ọrụ nke ọma na àmụmà{1}}ike mpụga echedoro

 

 

01 Izugbe

1.1 Nkọwa oru ngo

Scotech wetara onye ahịa Canada ihe ntụgharị ọkụ ọkụ 25 kVA otu -oghere phase{2}} n'afọ 2024 dị ka akụkụ nke usoro itoolu-. Dabara nke ọma na ụkpụrụ CSA C2.2-06. Edere maka voltaji mbụ nke 25 kV na voltaji nke abụọ nke 0.347 kV, na-enye ikike ngụkọta nke 25 kVA n'okpuru ibu na-aga n'ihu. Ọ na-eji ONAN jụrụ oyi mmanụ, mmanụ ịnweta dị ka ihe mkpuchi, polarity mgbakwunye, na otu vector Ii6.

Ihe ngbanwe a na-egosipụta ikuku aluminom, na-ebelata ibu na ọnụ ahịa, na-eme ka ntinye na njem dị mfe. Ihe mgbochi 2.8% ya na-enyere aka itule mkpirisi mkpirisi mkpirisi mkpirisi okirikiri na ụkpụrụ voltaji na sistemu nkesa, na-eme ka ntọala nchedo dị mfe. Ejiri ya na NLTC (Mba-Load Tap Changer) nwere nzọụkwụ 2.5%, na-enye ohere mgbanwe voltaji n'oge arụ ọrụ iji mee ka voltaji kwụsie ike. Ọ nwekwara 33 kV polymer ọkụ njide na ihe abụọ dị elu -voltaji bushings maka àmụmà dị irè na oke voltaji.

Nhazi voltaji a na-ahụkarị na sistemụ nkesa North America na Canada. Ihe nlereanya a na-ejere obodo ime obodo, agbata obi, na obere azụmaahịa ebe ike otu - kwụsiri ike dị mkpa. Njikọ isi 25 kV na-eme ka ọ bụrụ nhọrọ siri ike maka sistemu nri ma ọ bụ loop na gburugburu mpụta nwere ọrụ ọkụ dị elu. Ma ejiri ya na ahịrị ime ime obodo ma ọ bụ na njedebe nke netwọk mgbanaka, ihe ngbanwe a na-enye arụmọrụ kwụsiri ike na ntụkwasị obi.

 

1.2 Nkọwa nka nka

25 kVA otu akụkụ pole transformer nkọwa na mpempe akwụkwọ data

Enyere ya
Canada
Afọ
2024
Ụdị
Ntugharị okporo osisi akwụgoro
Ọkọlọtọ
CSA C2.2-06
Enyere ike
25kVA
Ugboro ugboro
60HZ
Polarity
Ihe mgbakwunye
Usoro
1
Ụdị oyi
ONAN
Ihe mgbochi mmiri
Mineral Mmanụ
Voltaji nke mbụ
25 kV
Voltaji nke abụọ
0,347 kV
Otu Vector
Ii6
Ngwa ikuku
Aluminom
Mgbochi
2.8%
Ịrụ ọrụ
98.63%
Pịa Changer
NLTC
Ọkụ aka
±2*2.5%
Enweghị mfu ibu
83 kV
Na Ọnwụ Ebu
404 kV
Ngwa ngwa
Onye njide

 

1.3 Eserese

25 kVA otu akụkụ okporo osisi transformer eserese na aha aha

25 kVA single phase pole transformer drawing 25 kVA single phase pole transformer nameplate

 

 

02 Nrụpụta

2.1 Isi

Isi ihe ngbanwe bụ isi ihe na-eme sekit magnetik ma na-enye ike nyefe ike n'etiti windings nke mbụ na nke abụọ. Ọ na-eji ọka ọka dị elu{{2}{2}} gbakwasara ala silicon steel lamination nke etinyebere na mkpuchi iji belata mfu efu ugbu a. Isi ihe nwere ụdị isi- nwere kọlụm akụkụ anọ, emebere ya maka nrụgharị magnetik kachasị yana arụmọrụ dị elu na arụ ọrụ ụlọ ọrụ na-aga n'ihu.

 

2.2 Ikuku

A na-emepụta ikuku aluminom n'okpuru nchịkwa siri ike nke ntụzịaka, polarity, na esemokwu. A na-ebu ụzọ merụọ eriri igwe LV ahụ, na-esote eriri HV, na-eji mkpuchi oyi akwa tinye nke ọma na enweghị wrinkles. Ntụgharị ziri ezi bụ n'ime ± 0.3%. Ọwara mmanụ radial Karịrị ma ọ bụ ha nhata 3 mm na mkpakọ siri ike na-ejigide ume dị mma na ike igwe, na-egbochi nrụrụ n'oge arụ ọrụ.

25 kVA single phase pole transformer winding

 

2.3 tank

25 kVA single phase pole transformer oil tank

Ewubere tankị mmanụ ahụ iji zute ụkpụrụ nrụnye njide siri ike. Ọ nwere flanges siri ike na nkwado, nwere ike ibu ibu na ịma jijiji, yana njiri oghere mgbago echekwabara. Akụrụngwa tank na-eguzogide oke okpomọkụ na nrụgide. Gasket na-ahụ na ọ nweghị mgbapu mmanụ. A na-emeso elu ahụ megide corrosion. N'elu na-enye ohere zuru oke maka iwepụ ngwa ngwa na ngbanwe nke ndị njide na-enweghị imebi akara.

 

2.4 Mgbakọ ikpeazụ

Isi na Mgbakọ Winding
Wụnye ikuku dị elu {{0}voltaji na obere{1}} voltaji n'ime isi, na-ahụ na mkpuchi na itinye uche.
Ntinye ahụ
Tinye isi na mgbakọ winding n'ime tank mmanụ.
Wụnye ụzọ na mkpuchi mkpuchi, na-ahụ na akara nke ọma.
Na-ejuputa Mmanụ Transformer
Wụnye mmanụ nzacha nzacha, hụ na ọ dị ọcha na enweghị adịghị ọcha.
Wụnye Ngwa Mpụga
Tinye valvụ nchekwa, nlele ọkwa mmanụ, yana njikọ ọnụ.

25 kVA single phase pole transformer active part

 

 

03 Nnwale

Nnwale Ọkọlọtọ na Nnwale oge

CSA C2.2-06(R2022) Otu{3}}usoro na atọ- ihe nkesa nkesa mmiri mmiri juru
CSA C802.1-13(R2022) ụkpụrụ arụmọrụ kacha nta maka ihe nkesa nkesa mmiri mmiri juru.
 

1. Ntụle Nguzogide
2. Nnwale oke
3. Nnwale polarity
4. Ọ dịghị ibu efu na ọ dịghị ibu ugbu a
5. Ibu Ibu na Voltage Mgbochi
6. Nnwale voltaji etinyere
7. Nleba anya na-eguzogide voltaji
8. Ntụle Nguzogide mkpuchi
9. Nnwale ntanye na nrụgide maka mgbanwe mgbanwe mmiri mmiri
10. Nnwale mmanụ
 

Nsonaazụ ule

Mba.

Nwale ihe

Nkeji

Nnabata

Ụkpụrụ

Ụkpụrụ ndị atụtara

Mmechi

1

Ntụle Nguzogide

/

/

/

Gafe

2

Nlele oke

/

Ngbanwe nke oke voltaji na ọpịpị bụ isi: Ihe na-erughị ma ọ bụ haha ​​0.5%

Akara njikọ: ii6

0.11~0.12

Gafe

3

Nnwale polarity

/

Ihe mgbakwunye

Ihe mgbakwunye

Gafe

4

Ọ dịghị - ibu mfu na mkpali ugbu a

%

I0 :: nye uru atụpụtara (100%)

0.38

Gafe

kW

P0: nye uru tụrụ (100%)

0.0681

%

I0 :: nye uru atụpụtara (105%)

0.40

kW

P0: nye uru tụrụ (105%)

0.0766

/

nnabata maka enweghị ibu ibu bụ +10%

/

5

Ibu ibu, voltaji impedance, ngụkọta ọnwụ na arụmọrụ

/

t:85 ogo

nnabata maka impedance bụ ± 7.5%

Nkwenye maka mkpokọta mfu ibu bụ +6%

/

Gafe

%

Z%: uru tụrụ

2.60

kW

Pk: uru tụrụ

0.366

kW

Pt: uru tụrụ

0.4341

%

Ịrụ ọrụ adịghị erughị 98.63%

98.81

6

Nnwale voltaji etinyere

/

LV: 10kV 60s

HV: 40kV 60s

Enweghị ọdịda nke voltaji ule a na-eme

Gafe

7

Nnwale Iguzogide Voltaji butere

/

Voltaji etinyere (KV):2Ur

Enweghị ọdịda nke voltaji ule a na-eme

Gafe

Ogologo oge (s):40

Ugboro (HZ): 180

8

Ntụle Nguzogide mkpuchi

GΩ

HV-LV·to·Ground

306

Gafe

LV-HV gaa n'ala

422

HV&LV ruo Ground

129

9

Ule ntapu

/

Ntinye nrụgide: 20kPA

Enweghị ntapu na mba

Mmebi

Gafe

Ogologo oge: 12h

10

Nnwale mmanụ

kV

Ike Dielectric

61.0

 

mg/kg

Ọdịnaya Ọdịnaya

13.6

%

Ihe nchụsa

0.158

mg/kg

Nyocha nke Furan

Ihe na-erughị ma ọ bụ hà nhata 0.1

/

Nyocha chromatography gas

/

image013
image015

 

 

04 Mbukota na mbupu

25 kVA single phase pole transformer packing
 
25 kVA single phase pole transformer shipping
 
 

05 Saịtị na nchịkọta

25 kVA single phase pole transformer

Kwesịrị ntụkwasị obi na ịrụ ọrụ nke ọma, ihe ngbanwe 25 kVA na-ezute ụkpụrụ CSA C2.2-06 nwere ogo 25 kV/0.347 kV, windings aluminom, na ntụ oyi ONAN. Ejiri ya na onye na-agbanwe mgbata NLTC na ndị na-ejide ọkụ ọkụ 33 kV, ọ na-eme ka voltaji na nchebe kwụsie ike. Dị mma maka ime obodo, ebe obibi, na obere netwọk azụmahịa, ọ na-ebunye nchekwa, dịgidere, yana dị mfe-ịwụnye ike n'èzí.

 

Ihe nchịkọta dị ọkụ: otu akụkụ okporo osisi transformer, emeputa, soplaya, price, efu

Zipu ozi