100 kVA Residential Transformer-13.8 / 0.12 * 0.24 kV|Guyana 2024
Ike: 100kVA
Voltaji: 13.8 / 0.12 * 0.24 kVA

Ihe ntụgharị obibi 100kVA nke Scotech - Ngbanwe voltaji dị mma maka ụlọ ọgbara ọhụrụ
01 Izugbe
1.1 Nkọwa oru ngo
Nke a 100kVA otu akụkụ obibi transformer e zigara Guyana na 2024. Nọgidesie ike n'ụzọ na IEEE & ANSI C57.12.00 ụkpụrụ. Polarity na-ebelata, na otu vector bụ Ii0. Ike ịgbanwe voltaji site na 13,800V ruo 120/240V, ihe ngbanwe a nwere akara kVA nke 100 maka ịrụ ọrụ a pụrụ ịdabere na ya. Na-eme ka ọ dị mma maka ngwa azụmahịa ebe obibi na ọkụ. Ejiri ọla kọpa mee windings, ihe ngbanwe a na-eme ka omume dị elu na ịrụ ọrụ nke ọma. Usoro jụrụ oyi nke ONAN na-eme ka ikpochapụ ọkụ dị mma, na-akwalite ntụkwasị obi ogologo oge{13}.
Site na ± 2.5% nke ịpị aka na ngụkọta nke 10%, ọ na-egosipụta nzaghachi na-adịru nwa oge dị elu na ụkpụrụ voltaji, na-ebelata mmetụta nke oke ibu maka nchebe kwalite. Oghere otu akụkụ nke etinyere ihe ngbanwe nke enweghị{3}} bụ 263W, na mfu - ibu bụ 897W, na-eme ka ike{{7}arụ ọrụ nke ọma. Ọ na-egosipụta impedance nke 2.4%, na-ebelata ọdịda voltaji n'okpuru ọnọdụ ibu. Scotech pụrụ iche na-eresị ndị ahịa mgbanwe mgbanwe polemount n'ebe azụmahịa na ụlọ ọrụ mmepụta ihe.
1.2 Nkọwa nka nka
100kVAokporo osisi mounted residential transformernkọwa na mpempe akwụkwọ data
|
Enyere ya
Guyana
|
|
Afọ
2024
|
|
Ụdị
Otu akụkụ okporo osisi etinyere ngbanwe
|
|
Ọkọlọtọ
IEEE & ANSI C57.12.00
|
|
Enyere ike
100 kVA
|
|
Ugboro ugboro
60HZ
|
|
Polarity
Mwepu
|
|
Otu vector
Ii0
|
|
Voltaji nke mbụ
13800 V
|
|
Voltaji nke abụọ
120/240 V
|
|
Ngwa ikuku
Ọlapa
|
|
Mgbochi
2.4%
|
|
Usoro jụrụ oyi
ONAN
|
|
Pịa Changer
NLTC
|
|
Ọkụ aka
±2X2.5%(Ngụkọta oke=10%)
|
|
Enweghị mfu ibu
263 W
|
|
Na Ibu Mfu
897 W
|
|
Ngwa ngwa
Nhazi ọkọlọtọ
|
1.3 Eserese
100kVA okporo osisi n'ịnyịnya residential transformer akụkụ na arọ nkọwa
![]() |
![]() |
02 Nrụpụta
2.1 Isi
The Wound Transformer Cores bụ ngwa imewe dị mfe ma dị irè maka cores silicon steel maka nkesa nkesa. Na-ebelata nke ukwuu oge achọrọ iji kpọkọta ihe nkesa nkesa na ọ nweghị ihe mgbochi ọzọ ma ọ bụ ngwaike yiri ya achọrọ iji wuchaa isi ihe owuwu. Ọtụtụ ụlọ ọrụ na-ekesa ike na ahịa North na South America na-ahọrọ cores ígwè ọnya.

2.2 Ikuku

Igwe nrụgharị ọkụ anyị na-eji nnukwu- ịdị ọcha enamed gburugburu waya ọla kọpa, na-egosipụta ọmarịcha ọkụ eletrik yana mkpuchi kọmpat. Mgbakwunye enamel siri ike na-eme ka ịdịte aka ma na-eyi nguzogide. Nabata ihe nhazi igwe ikuku nke ikuku ikuku maka obere-coils voltaji na ikuku ikuku maka igwe ikuku dị elu{4}, na-eme ka nkwụsi ike arụmọrụ dị mma, ntụkwasị obi, na arụmọrụ ọkụ.
2.3 tank
Nrụpụta tankị transformer gụnyere injinia nkenke yana nka nka iji hụ na ọ dị ogologo ndụ tankị ahụ. All welds nke tank ga-adị ogologo, dị nro na otu, na-enweghị nkwonkwo oyi, weld beads, pores, ma ọ bụ bulges, na ekwesịrị ime ya na otu ngafe na-aga n'ihu ebe enwere ike. Welds ga-adị larịị na enweghị mgbawa. Ihe mkpuchi tankị ekwesịghị inwe mmiri a na-ahụ anya{3}} ebe anakọta.
2.4 Mgbakọ ikpeazụ
1. Mgbakọ ikuku:Wepụ ikuku HV/LV na isi laminated, na-ahụ na nhazi na mkpuchi mkpuchi kwesịrị ekwesị.
2. Njikọ eletrik:Jikọọ winding na-eduga na mgbata mgbata, bushes na ihe ndị ọzọ, wee chekwaa na mkpuchi nkwonkwo.
3. Isi -Ikpokoro eriri igwe:Tinye akụkụ ahụ gbakọtara (isi + windings) n'ime oven akpọnwụ maka ikpo ọkụ iji wepụ mmiri mmiri.
4. Nwụnye tankị:Tinye akụkụ ahụ a mịrị amị na-arụ ọrụ n'ime tank, dobe ya nke ọma, wee hụ na mkpuchi kwesịrị ekwesị site na mgbidi tank.
5. Ngwa mgbakwunye:Wụnye bushes, valvụ enyemaka nrụgide na ngwa ndị ọzọ, wee lelee maka ntapu.
6. Ndochi mmanụ & idozi:Vacuum{0}juju na mmanụ mkpuchi, degas, ma kwe ka edozi tupu ịlele ọkwa mmanụ yana ike dielectric.

03 Nnwale
Nnwale oge niile
1. Ntụle Nguzogide
2. Nnwale oke
3. Nnwale polarity
4. Ọ dịghị ibu efu na ọ dịghị ibu ugbu a
5. Ibu Ibu na Voltage Mgbochi
6. Nnwale voltaji etinyere
7. Nnwale anabatara voltaji
8. Ntụle Nguzogide mkpuchi
9. Nnwale ntanye na nrụgide maka mgbanwe mgbanwe mmiri mmiri
10. Oil Dielectric Test

Nsonaazụ ule
|
Mba. |
Nwale ihe |
Nkeji |
Ụkpụrụ nnabata |
Ụkpụrụ ndị atụtara |
Mmechi |
|
1 |
Ntụle Nguzogide |
/ |
/ |
/ |
Gafe |
|
2 |
Nlele oke |
/ |
Ngbanwe nke oke voltaji na ọpịpị bụ isi: Ihe na-erughị ma ọ bụ haha 0.5% Akara njikọ: ii0 |
-0.03 |
Gafe |
|
3 |
Nnwale polarity |
/ |
Mwepu |
Mwepu |
Gafe |
|
4 |
Ọ dịghị - ibu mfu na mkpali ugbu a |
% kW |
I0:: nye uru a tụrụ atụ P0: nye uru a tụrụ atụ Nkwenye maka enweghị ibu ibu bụ +10% |
0.88 0.211 |
Gafe |
|
5 |
Ngwunye ibu, voltaji impedance, mfu zuru oke na arụmọrụ |
/ kW kW |
t:85 ogo Z%: uru tụrụ Pk: uru tụrụ Pt: uru tụrụ Nkwenye maka impedance bụ ± 10% Nkwenye maka mkpokọta mfu ibu bụ +6% |
2.29 0.823 1.034 99.21 |
Gafe |
|
6 |
Nnwale voltaji etinyere |
/ |
HV: 34KV 60s LV: 10kV 60s |
Enweghị ọdịda nke voltaji ule a na-eme |
Gafe |
|
7 |
Nnwale Iguzogide Voltaji butere |
/ |
Voltaji etinyere (KV): 2 Ua Ogologo oge (s): 48 Ugboro (HZ): 150 |
Enweghị ọdịda nke voltaji ule a na-eme |
Gafe |
|
8 |
Ntụle Nguzogide mkpuchi |
GΩ |
HV -LV gaa n'ala LV-HV gaa n'ala HV&LV ruo Ground |
66.7 59.4 60.5 |
/ |
|
9 |
Ule ntapu |
/ |
Ntinye nrụgide: 20kPA Ogologo oge: 12h |
Enweghị ntapu na mba Mmebi |
Gafe |
|
10 |
Nnwale Dielectric mmanụ |
kV |
Karịrị ma ọ bụ hà nhata 45 |
52.33 |
Gafe |
04 Mbukota na mbupu

05 Saịtị na nchịkọta
Nke a100kVA otu -osisi n'usoro{2}} n'agbanyere ngbanwe emebere ya maka nkesa ike azụmahịa nke a pụrụ ịdabere na ya na ebe obibi. Site na ikuku ọla kọpa na-arụ ọrụ nke ọma, ihe owuwu na-adịgide adịgide, yana njikwa mma siri ike, ọ na-ewepụta arụmọrụ kwụsiri ike yana ọrụ ogologo oge{1} na gburugburu ebe na-achọsi ike.

Ihe nchịkọta dị ọkụ: transformer obibi, onye na-emepụta ihe, onye na-eweta, ọnụahịa, ọnụ ahịa
You Might Also Like
15 kVA Ogwe Ntugharị Ntugharị-24.94 / 0.12 * 0.24 kV...
75 kVA Transformer Na eriri ọkụ-12.4 * 24.94 / 0.12 ...
100 kVA Ogwe Ntugharị Ntugharị-7.97 / 0.12 * 0.24 kV...
167 kVA Pole nkesa ntụgharị-14.4 / 0.6 kV|Canada 2024
37.5 kVA Ogwe Ntugharị-2.4 / 0.12 kV|Canada 2025
167 kVA Ogwe Ntugharị Ntugharị-13.8 / 0.12 * 0.24 kV...
Zipu ozi