630 kVA Atọ nke Akọrọ Ụdị Ntugharị-10 / 0.4 kV|Georgia 2025
Ike: 630 kVA
Voltaji: 10/0.4 kV
Njirimara: ya na njikwa okpomọkụ

Emebere ya na ihe ọhụrụ, jiri nkenke wuo{0}}Resin Cast Dry Type Transformer, na-enye nchekwa na arụmọrụ!
01 Izugbe
1.1 Ihe ndabere oru ngo
A na-ahazi nke ọma, wuo ya ma nwalee ihe nkedo SCOTECH ka ọ na-agbaso ụkpụrụ ụlọ ọrụ kachasị elu, gụnyere NEMA, ANSI C.57, DOE, na IEEE, dịka ọ dị.
Ụdị ihe ngbanwe nke SCOTECH nke igwe nkụ bụ maka ime ime ma n'èzí, na-achọ obere nrụzi n'ihi ihe owuwu ha siri ike. N'iji sistemu mkpuchi na-emekọrịta ihe na gburugburu ebe obibi, ha na-ewepụ mkpa ebe nchekwa ọkụ na-ejidekwa basins nke mmiri mmiri ọdịnala{1} juru eju na-achọkarị. Ikike a na-eme ka nrụnye nkedo igwe ngbanwe nkedo dị nso na ibu ahụ, na-eme ka sistemụ kwụsie ike n'ozuzu ya na ibelata mfu ahịrị nke abụọ dị oke ọnụ. Na mgbakwunye, fiberglass ha -emebere nrụpụta na-enye ike dị mkpụmkpụ{5} na ike ọkụ ọkụ. t na-etu ọnụ mara mma n'ibu àgwà, bụ nke na-adịghị nke cracks na esịtidem ikuku egosipụta, na atụmatụ ala obodo mwepu, n'ịhụ elu pụrụ ịdabere na ogologo ọrụ ndụ.
1.2 Nkọwa nka nka
2500 kVA resin nkedo akọrọ ụdị ntụgharị nkọwapụta na mpempe akwụkwọ data
|
Enyere ya
Jọjia
|
|
Afọ
2024
|
|
Ụdị
Resin nkedo ụdị ngbanwe
|
|
Isi ihe
Mpempe akwụkwọ silicon na-adabere na ọka
|
|
Ọkọlọtọ
IEC60076-11, EN50541-1, ISO9001, ISO14001
|
|
Enyere ike
630kVA
|
|
Ugboro ugboro
50HZ
|
|
Usoro
Atọ
|
|
Otu vector
Dyn11
|
|
Ụdị oyi
ONAN
|
|
Voltaji nke mbụ
10 kV
|
|
Voltaji nke abụọ
0,4 kV
|
|
Ngwa ikuku
Aluminom
|
|
Mgbochi
6%
|
|
Pịa Changer
NLTC
|
|
Ọkụ aka
± 2 * 2.5% @ isi voltaji
|
|
Enweghị mfu ibu
1.13KW
|
|
Na Ọnwụ Ebu
5.6KW
|
|
Ọkwa mkpuchi
F
|
1.3 Eserese
630 kVA resin nkedo akọrọ ụdị ihe ngbanwe eserese na nha.
![]() |
![]() |
02 Nrụpụta
2.1 Isi
A na-emepụta isi ihe ndọta nke transformer site na obere mfu -mfu, ọka{1}} mpempe igwe gbadoro ụkwụ na ya, na-egosipụta nkwonkwo ụkwụ ụkwụ ogo 45- nke na-ebelata nhụsianya na-efunahụ akpafu. Iji mee ka ịdịte aka dịkwuo elu, a na-eji ihe mkpuchi pụrụ iche na-echebe elu nke magnetik, ma na-ebelata mkpọtụ arụ ọrụ. Nchikota a nke ihe di elu na ihe ohuru ohuru na-eme ka o doo anya na oru kacha mma na ogologo ndu di iche iche.

2.2 Ikuku

A na-eji ọtụtụ ọkwa rụọ ikuku nkedo, nke ọ bụla nwere otu ntụgharị, nke na-eme ka nguzogide voltaji na-akpali akpali ma na-ebelata ohere nke mwepu akụkụ. A na-emekarị site na teepu aluminom, imewe a na-ebelata nke ọma nrụgide n'ibu na-esite na mgbanwe okpomọkụ na mgbanwe mgbanwe. Igwe ikuku voltaji dị ala na-eji foil na-aga n'ihu nke ma ọ bụ aluminom ma ọ bụ ọla kọpa, nke na-enye nguzogide siri ike na mkpirisi nrụgide gburugburu n'ihi nrụgide dielectric na-enweghị atụ nke gụnyere. Nhazi ikuku ọhụrụ a abụghị naanị na-eme ka ntụkwasị obi dịkwuo mma kamakwa ọ na-ahụkwa na arụmọrụ kachasị mma gafere ọnọdụ ọrụ dị iche iche.
Mgbakọ isi: Wụnye isi electromagnetic, hụ na edobere ihe niile na nchekwa.
Ntinye ikuku: Wụnye windings voltaji dị elu na nke dị ala dịka nkọwa nhazi, na-ejigide ihe mkpuchi dị mma.
Sistemụ mkpuchi na oyi: Tinye ihe mkpuchi ma chepụta usoro jụrụ oyi kwesịrị ekwesị maka gburugburu ebe obibi.
Ịwụsa resin: Uniformly wụsa resin gburugburu windings na isi, na-ewepụ ikuku egosipụta.
Usoro ọgwụgwọ: Gwakọta resin n'okpuru ọnọdụ kwesịrị ekwesị iji mepụta oyi akwa mkpuchi siri ike.
Nyocha Mgbakọ Ikpeazụ: Na-eme nyocha anya na ule eletriki iji hụ na nnabata na ụkpụrụ.
Nwụnye Ọdịdị Mpụga: Wụnye corrosion - shei na ọnụ ọnụ na-eguzogide, na-ahụ na akara ngosi doro anya.

03 Nnwale
|
Mba. |
Nwale ihe |
Nkeji |
Ụkpụrụ nnabata |
Ụkpụrụ ndị atụtara |
Mmechi |
|
|
1 |
Ntụle nke winding iguzogide |
/ |
Ọnụego enweghị nguzozi kacha nguzogide Nguzogide ahịrị: Ihe na-erughị ma ọ bụ haha 2% |
HV (akara) |
LV (akara) |
Gafe
|
|
0.28% |
1.02% |
|||||
|
2 |
Ntụle nke oke voltaji na nlele nke mbugharị oge |
/ |
Nkwenye nke oke voltaji na ọpịpị bụ isi: ± 1/10 Akara njikọ: Dyn11 |
-0.07% ~ 0.12% Dyn11 |
Gafe
|
|
|
3 |
Ntụnye nke Mkpirisi-Mkpirisi okirikiri na mfu ibu |
/ kW kW |
t:120 ogo Z%: uru tụrụ Pk: uru tụrụ Pt: uru tụrụ |
6.01% 4.181 5.765 |
Gafe
|
|
|
4 |
Ntụle nke mba- ibu mfu na ugbu a na 90% na 110% nke voltaji e gosiri |
/ kW |
I0 : nye uru a tụrụ atụ P0: nye uru a tụrụ atụ |
90% Uru |
0.261 0.9018 |
Gafe
|
|
100% Ur |
0.29 1.002 |
|||||
|
110% Ur |
0.319 1.102 |
|||||
|
5 |
Nnwale voltaji etinyere |
/ |
HV: 28kV 60s LV: 3kV 60s |
Enweghị ọdịda nke voltaji ule a na-eme |
Gafe
|
|
|
6 |
Nnwale Nkwụghachi Voltaji butere |
/ |
Igwe ọkụ etinyere (kV):2 Ur Voltaji ebutere (kV): 0.8 Ogologo oge (s):40 Ugboro (HZ): 150 |
Enweghị ọdịda nke voltaji ule a na-eme |
Gafe
|
|
|
7 |
Nnwale mgbapu akụkụ |
pC |
Ọkwa kacha nke mwepu akụkụ ga-abụ 10 pC |
<10 |
Gafe
|
|


04 Mbukota na mbupu


05 Saịtị na nchịkọta
Na nchịkọta, resin cast dry type transformers, nwere ezigbo nchekwa nchekwa ha, ntughari ike dị mma, njirimara gburugburu ebe obibi pụtara ìhè, na nrụzi dị mma, abụrụla ngwa eletriki a ma ama na mpaghara azụmahịa na ụlọ ọrụ mmepụta ihe. Ma n'ọgba ọkụ mepere emepe, ogige ụlọ ọrụ mmepụta ihe, nnukwu ụlọ elu-, ma ọ bụ sistemu metro, resin cast dry type transformers na-enye nkwado ike siri ike ma kwụsie ike. Ịhọrọ elu- resin cast dry type transformers abụghị naanị nkwa maka nrụpụta ụlọ ọrụ kamakwa ọ na-enye aka dị mma maka mmepe akwụkwọ ndụ akwụkwọ ndụ na nke na-adigide. Anyị na-agba mbọ ịnye gị ngwaahịa kachasị mma na ọrụ ọkachamara, anyị na-atụkwa anya ịkwado gị iji kwalite ọganihu ụlọ ọrụ.