3000 kVA ntụgharị-25 / 0.6 kV|Canada 2025

3000 kVA ntụgharị-25 / 0.6 kV|Canada 2025

Obodo: Canada 2025
Ike: 3000 kVA
Voltaji: 25-0.6 / 0.347 kV
Njirimara: nwere temometa mmanụ n'elu
Zipu ozi

 

 

3000 kva pad mounted transformer

Nkesa ike Smart na-amalite site na mpe mpe akwa anyị{0}}Mounted Transformers!

 

 

01 Izugbe

1.1 Nkọwa oru ngo

3000 kVA three phase pad mounted transformer e zigara Canada na 2025. Ike nke transformer bụ 3000 kVA na ONAN jụrụ oyi. Isi voltaji bụ 25 kV na ± 2 * 2.5% tapping range (NLTC), nke abụọ voltaji bụ 0.6Y / 0.347 kV, ha guzobere vector otu Dyn1.

Mpempe akwụkwọ{{0}n'ekpudo n'elu bụ ihe dị mkpa na sistemu nkesa ọkụ eletrik ọgbara ọhụrụ, emebere maka ngbanwe ike dị mma, ntụkwasị obi na nke ọma n'ime obodo mepere emepe, ime obodo na ntọala ụlọ ọrụ mmepụta ihe. A na-edobere nkeji ndị a siri ike, ala{2}} n'ime ihe mkpuchi ihu igwe na-adịgide adịgide, na-echekwa ihe ndị dị mkpa ma na-ahụ na ọ dị mfe maka mmezi. Dị mma maka netwọk ike n'okpuru ala, pad{4} mounted transformers na-enye akara ukwu, atụmatụ nchekwa emelitere, yana obere ọrụ mkpọtụ- na-eme ka ha zuo oke maka mpaghara ebe ịchọ mma na oghere bụ isi ihe. Site na arụmọrụ dị elu, ogologo ndụ ọrụ yana nrube isi n'ụkpụrụ ụlọ ọrụ, ha na-enye ụlọ ọrụ na ndị na-azụ ahịa ihe ngwọta a pụrụ ịdabere na ya maka mgbada ala ọkara - voltaji ọkụ ruo ọkwa enwere ike iji ya rụọ ọrụ. Ma maka mmepe ebe obibi, ogige azụmahịa, ma ọ bụ njikọta ike mmeghari ohuru, pad{10}n'ekwanyere ngbanwe na-eweta arụmọrụ ị nwere ike ịtụkwasị obi.

 

 

 

1.2 Nkọwa nka nka

3000 kVA mpe mpe akwa akwadoro ụdị nkọwapụta na mpempe data

Enyere ya
Canada
Afọ
2025
Ụdị
Ihe mgbakwasa na mpe mpe akwa
Ọkọlọtọ
CSA C227.4:21
Enyere ike
3000 kVA
Ugboro ugboro
60HZ
Usoro
3
Nri
Loop
N'ihu
Nwụrụ anwụ
Ụdị oyi
ONAN
Voltaji nke mbụ
25 kV
Voltaji nke abụọ
0.6Y/0.347 kV
Ngwa ikuku
Aluminom
Ntugharị akụkụ
Dyn1
Mgbochi
5.75%
Pịa Changer
NLTC
Ọkụ aka
±2*2.5%
Enweghị mfu ibu
3.55 kW
Na Ọnwụ Ebu
26.5 kW
Ngwa ngwa
Nhazi ọkọlọtọ

 

 

1.3 Eserese

3000 kVA mpe mpe akwa akwadoro eserese eserese na nha.

3000 kva pad mounted transformer 3000 kva pad mounted transformer

 

 

02 Nrụpụta

2.1 Mgbanwe

Ọdụdọ ndị a na-agbada n'elu pad{{0}n'ekpudo n'elu bụ ihe ndị bụ isi maka iguzobe sistemu ntọ ala na-adịgide adịgide. N'ụzọ kwụ ọtọ welded ozugbo na transformer tank mgbidi na ma HV na LV n'akụkụ, ndị a ọnụ na-eje ozi dị ka isi njikọ njikọ. A na-eji ụgbọ ala ọla kọpa siri ike na-ejikọta ọnụ ụzọ abụọ a, na-emepụta ụzọ mgbochi na-aga n'ihu, dị ala{3} nke na-eme ka tankị na mgbakọ isi ga-anọgide na-enwe ike ime ala. Nhazi a na-ejikọta ihe niile dị mma nke ọma, na-enye ụzọ a pụrụ ịdabere na ya maka ikuku na-adịghị mma na ịkwalite nchekwa maka ma akụrụngwa na ọha.

20251201111501826177

 

2.2 LV Nnọpụiche Bushing(X0)

20251201111153824177

Obere {{0}Voltage Neutral Bushing (X0) dị na pad{2}} nke etinyere na ngbanwe na-arụ ọrụ dị ka ebe mgbado etiti maka sistemụ eletriki nke abụọ. A na-ejikọta ya na bọs ala nke transformer na-adịgide adịgide site na onye na-eduzi akwadoro nke nwere oke adịghị mma, na-ahụ na ụzọ nkwụsịtụ dị ala{{4} maka mmiri na-adịghị mma ma na-enye usoro kwụsiri ike na-anọpụ iche. Njikọ a dị oke egwu na-ewepụta ntụaka dị mma na ala ala, na-eme ka ọrụ akụrụngwa dị mma na ịkwalite ndị ọrụ na nchekwa ọha.

 

2.3 tank

Ejiri ígwè dị elu-ọkwa, corrosion{1}} wuo tankị ahụ iji hụ na ogologo oge- na-adịte aka na gburugburu mpụta siri ike. N'igosipụta imewe nke mechiri emechi na welds ziri ezi, ọ na-enye nchebe dị mma megide mmiri na mmetọ. Ụgbọ mmiri ahụ na-ejikọta nku na ọwa jụrụ oyi n'ụzọ dabara adaba iji kwalite mgbasa ọkụ ma na-edobe iguzosi ike n'ezi ihe. Ihe owuwu wusiri ike na akpa ebuli elu na akpa forklift na-eme njem na nrụnye dị mma. Mputa na-enweta sistemu mkpuchi mkpuchi mkpuchi ọtụtụ{7} maka nkwalite ihu igwe na mmasi mma.

corrosion-resistant-steel-oil-tank

 

2.4 Mgbakọ ikpeazụ

The final assembly of 3000kva pad-mounted transformers

Mgbakọ ikpeazụ nke mpe mpe akwa{0}}nkwalite ngbanwe na-ejikọ ọnụ{1}coil assemblies, elu - obere voltaji, na ngwaọrụ nchekwa n'ime ebe nchekwa siri ike, na-egbochi ihu igwe. Nhazi nkenke na-eme ka arụmọrụ sekit magnetik kacha mma ka ọ na-edobe nchapụta ọkụ eletrik kwesịrị ekwesị. Usoro mgbakọ na-agụnye nnwale siri ike nke ihe niile, mmanụ na-ejuputa maka mkpuchi dị elu, na nkwenye ikpeazụ. Ụlọ ọrụ- igbe njikọ agbakọtara na ngalaba nkwụsị USB na-enye njikọ ubi dị mma.

 

 

03 Nnwale

Nnwale ihe kpatara ọnwụ dielectric (ma ọ bụ ihe ike)
  • A na-eji ule ọnwụ dielectric iji nyochaa mfu nke ihe mkpuchi mkpuchi na ihe ntụgharị n'okpuru mmetụta nke ọkụ eletrik, na iji chọpụta ogo nke mmebi nke ọrụ mkpuchi ya. Nnwale a nwere ike inye ịdọ aka ná ntị mmalite gbasara ịka nká, mmebi ma ọ bụ ezughị ezu nke ihe mkpuchi mkpuchi.

 

3000 kva transformer fat
3000 kva transformer testing

 

 

04 ndị ọzọ

4.1 mgbanaka nkwụsị ibu anọ

Mgbanwe ibu ọnọdụ 4{1} nke Pad Mounted Transformer bụ isi ihe njikwa n'akụkụ oke voltaji ya, na-ahụ maka ịgbanwe ụdị nnweta ike yana ịgbanyụ/ gbanyụọ ọkụ. Ọ nwere ụdị ọrụ 4:

Ọnọdụ 1 (gbanyụọ isi mmalite A&B): na-ebipụ kpamkpam njikọ dị n'etiti nnukwu ọkụ ọkụ - na ihe ngbanwe. Nke a bụ ọnọdụ ọrụ nchekwa maka ngbanwe ibu n'oge mmezi akụrụngwa ma ọ bụ nchọpụta nsogbu.

Ọnọdụ 2 (Isi mmalite A pịa): Jikọọ na feeder ahịrị A (akara ntinye A). Ihe ntụgharị na-adọta ike ọrụ site na grid ọkụ site na eriri feeder A.

Ọnọdụ 3 (Isi mmalite B pịa): Jikọọ na feeder ahịrị B (akara ntinye B). Ihe ntụgharị na-adọta ike site na eriri feeder B, a na-ejikarị ọnọdụ a dị ka sekit ike ndabere.

Ọnọdụ 4 (Isi mmalite A&B pịa): Jikọọ ma feeder ahịrị A na B n'out oge, na-eme a loop ike ọkọnọ nhazi.

20251201111928829177

 

4.2 drain valve

20251201111929830177

valvụ mmiri na-ekpofu na pad{0}nke a na-agbanye mgbanaka, nke na-adịkarị n'ebe kacha ala nke tankị, bụ ihe dị mkpa maka mmezi na nchekwa. Ọ na-enyere aka na-achịkwa igbapu mmanụ mkpuchi maka ebumnuche dịka nyocha nke ime, nrụzi, ma ọ bụ nkwụsị ikpeazụ. Nhazi ya na-egbochi mwụfu a na-achịkwaghị achịkwa ma na-eme ka mmanụ dị mma na-eruba n'ime arịa nchekwa, na-ahụ maka nchekwa ọrụ yana nchedo gburugburu ebe obibi.

 

 

05 Saịtị na nchịkọta

Ma maka nkwalite netwọkụ nkesa nke obodo ma ọ bụ nkwado ike ogige ụlọ ọrụ, igwe mgbanaka mgbanaka anyị na-ebunye ngwọta nkesa kwụsiri ike, na-agbanwe agbanwe{0}nke njiri mara dị ka mgba ọkụ ọnọdụ 4- (maka nnweta ike dị iche iche) na ihu igwe{3}} na-eguzogide, dị elu{{6} mkpuchi mkpuchi. Otu onye ahịa akụrụngwa mpaghara kwuru, sị: "Ngalaba ndị a jikọtara n'enweghị nsogbu n'ime netwọkụ loop anyị; ọrụ mgba ọkụ na-adị mfe na 12+ ọnwa nke mmejọ na - oge ịgba ọsọ n'efu belata awa ọrụ nlekọta saịtị site na 20%."

Anyị dị njikere ịnye nhazi ahaziri ahazi yana nkwado okirikiri{0} ndụ{1} zuru oke, na-ahụ na sistemụ ike gị na-arụ ọrụ nke ọma na nke ọma.

3000 kva transformer

 