Nwụnye Transformer Bushing n'ime nnukwu mgbanwe ọkụ - Nzọụkwụ - site na -Ntụziaka nrụnye ihe ntụgharị nzọụkwụ Nkebi 2
Mar 18, 2026
Hapụ ozi
01 Ihe kpatara nwụnye Bushing ji dị oke egwu na nnukwu mgbanwe ọkụ
N'ime nnukwu ihe ngbanwe ọkụ - karịsịa100 MVA ike transformerseji na ebe data ma ọ bụ ọdụ ụgbọ ala{0}transformer bushing ntinye bụ akụkụ dị oke egwu nke nrụnye transformer. Bushings abụghị nanị ihe njikọ njikọ; ha na-eje ozi dị ka nnukwu ihe mkpuchi mkpuchi voltaji -, ebe mgbakasị ahụ, na isi mmalite nke nrụnye{3}} ọdịda metụtara.
Nrụnye na-ezighi ezi nwere ike iduga nhụpụta mmanụ, mwepu akụkụ akụkụ, ma ọ bụ mgbawa n'ọhịa. Ya mere, njikwa siri ike n'oge ntinye ihe ntụgharị dị mkpa iji hụ na nchekwa ọrụ na ogologo ndụ.
02 chọrọ nwụnye ihe nrụnye nrụnye
Osisi kwụ ọtọ: mgbagha Ihe na-erughị ma ọ bụ haha na ogo 30 site na vetikal
Nkịta kwụ ọtọ: ndahie Ihe na-erughị ma ọ bụ haha na ogo 15 site na kehoraizin
Ịgafe oke ndị a nwere ike ibute enweghị oke nrụrụ aka, nkesa mmanụ na-ezighi ezi, yana mbelata ọrụ mkpuchi. Ịgbaso ụkpụrụ nrụnye transformer egbochie ogologo oge{1} ihe egwu mkpuchi.
03 Tupu{1}Nkwadebe nchekwa nwụnye
3.1 Mwepụta nrụgide

Mepee valvụ nru ububa ọ bụla (~ 1/3 oghere) iji hapụ nitrogen n'enweghị nsogbu ma hụ na nrụgide dị n'ime tank nke ihe ntụgharị na-adaba efu.
3.2 Nleba anya nleba anya n'elu elu nke Bushing
Gbaa mbọ hụ na akara ndị dị n'okpuru kwekọrọ na nrịbama flange dị elu na tank nke mgbanwe.
Gbaa mbọ hụ na flange nke ọkpọkọ njikọ dị na ntọala elu dakọtara na obere mmanụ{0}} na-anakọta ọkpọkọ.
Ịgbaso usoro ndị a na-ahụ maka nchekwa na ntụzịaka{0}} nwụnye ihe nrụnye na-akwado.

04 Ngwa na akụrụngwa achọrọ
- Ụdọ ebuli dị nro- na-adịkarị ogologo 20 m, dayameta 8-10 mm.(Ọ bụrụ na ị na-eji eriri igwe igwe, kechie ya na teepu akwa iji gbochie mmebi nke poselin ma ọ bụ akụkụ ígwè.)
- Na-ebuli skru anya- maka nrụnye bushing chọrọ.
- Ogologo eriri traction nwere bolts M8– maka threading site bushing Central tube, na maka ebuli ndu njikọ ma ọ bụ ndu mkpara.
- Torque mgbanaka maka hex bolts- n'ofe ụlọ 16 mm (M10) na 13 mm (M8), oke ike dị 10-80 Nm.
- Ihe mgbawa ike maka bolts isi hex cylindrical- n'ofe ala dị larịị 6 mm (M8), 5 mm (M6), na 4 mm (M5), oke ike 5-30 Nm.
- mgbanaka nwere ike idozi- obosara agba ruo 42 mm, torque 10-80 Nm.
- Ngwunye dị nro- maka ịkwado bushes n'oge njikwa na nrụnye.
Iji gbochie njide eri ma ọ bụ mebie ntinye waya n'oghere eri:
- Eriri na kọntaktị na mmanụ transformer: were anhydrous petroleum jelly, griiz No.28, ma ọ bụ mmanụ ọzọ{1}} mmanu mmanu.
- Eriri eriri ala: jiri griiz No.28 ma ọ bụ ihe dakọtara.
- Mpụga ọnụ na bọsbar nkwado bolts: jiri griiz No.28 ma ọ bụ dakọtara.
- N'ịgbaso ndepụta nrụnye nke nrụnye transformer a na-eme ka njikọ igwe na eletrik dị mma.
05 Ibulite na njikwa nke Bushings
Maka HV bushings (145 kV na n'elu), jiri okpukpu abụọ ebuli elu (usoro nko abụọ), jikwaa akụkụ ebuli nke nta nke nta, ma zere mmetụta na poselin.

Ọ bụrụ na etinyere ya n'ala, na-akwado n'otu ebe dị na nkwakọ ngwaahịa ma jiri akwa dị nro (roba ma ọ bụ osisi).

06 Nzọụkwụ -site na-Usoro nwụnye nke ịhịa aka n'ahụ
1. Wepu & nyochaa
Wepu bushes na nkwakọ ma tinye ha n'elu akwa raara onwe ya nye. Hichaa ma lelee elu ala ahụ maka mgbawa ma ọ bụ ncha, lelee ọkwa mmanụ, wee hụ na ọ nweghị mgbawa.(Rịba ama: mmanụ ala jelii na eri nwere ike ịgbanye n'okpuru oke okpomọkụ.)
2. Nnwale mkpuchi
Mee ule mkpuchi mkpuchi gụnyere nguzogide mkpuchi, njedebe{{0} mkpuchi ihuenyo, tanδ, ikike, na arụmọrụ mmanụ. Gaa n'ihu naanị ma ọ bụrụ na ule niile gafere.
3. Na-ebuli ya na nko abụọ
Tinye nko 1 na mgbanaka ebuli flange (sket 3-4 site na nsọtụ ndu) na nko 2 na poselin dị n'okpuru flange ma ọ bụ ihe nkwado. Bulite ha abụọ n'otu oge, jiri nwayọọ nwayọọ na-ebuli nko 1 ka ị na-ewetu nko 2 ruo mgbe osisi ahụ dabara na akụkụ elu elu.
4. Nduzi waya & akara
Tinye eriri ụzọ eriri site na tube onye na-eduzi, fanye atụdo, wee tinyeghachi okpu n'elu, ọta grading, na bọọdụ ọnụ. Gbaa mbọ hụ na akara nke ọma n'elu. Jikwaa nke ọma iji gbochie mmebi poselin.
5. Bolt tightening
Mechie bolts diagonally na nke nta nke nta iji gbochie nrụgide flange na-enweghị isi. Afefela torque akwadoro (20–25 N·m) ka ịzenarị ụgbụgba ọkụ.

| Nzọụkwụ | Omume |
|---|---|
| 1 | Bupụ ma nyochaa ọhịa |
| 2 | Mee ule mkpuchi mkpuchi |
| 3 | Bulite ya na nko abụọ |
| 4 | Tinye eriri ụzọ eriri, tinyegharịa okpu n'elu |
| 5 | Gbanyụọ bolts diagonally, jikwaa torque |
| 6 | Nyochaa ọkwa mmanụ na nhazi |
07 Nwụnye ọkụ ọkụ dị elu
Jiri etiti nrụnye ohia raara onwe ya nye wee mee nyocha zuru oke. Bushings nwere anya na-ebuli elu anọ na flange; tinye eriri isi iji buru ibu.
Isi ihe:
1. Nyocha & Nhicha
Nyochaa maka mmebi, ihe nkedo rụrụ arụ, ma hichaa uzuzu na unyi niile. Nwalegharịa akara ma ọ bụrụ na ọ ga-ekwe omume.
2. Ọnọdụ & Mgbanwe mmanụ
Debe ahịhịa na nkwụ ma dozie ihe nchekwa mmanụ ka ọ dị n'etiti{0}} elu (~ 1/2–2/3 nke nlele mmanụ).
- Mmanụ dị oke elu → nrụgide dị n'ime na-abawanye, nwere ike ibute ntapu.
- Mmanụ dị ala → na-egbochi nleba anya.
Gbanwee mmanụ site na plọọkụ flange ma ọ bụ nkwụnye ndochi nchekwa.
3. Njikọ njikọ
Fanye ngwucha ndu voltaji dị elu n'ime mkpanaka onye na-eduzi eri; ikpo ọkụ phosphor ọla kọpa iji mejupụta na ịgbado nkwonkwo.
4. Ebuli & Nhazi
Tinye eriri naịlọn (Karịrị ma ọ bụ hà nhata 2 × ogologo osisi, ike zuru oke) site na tube na-eduzi ruo ọdụ ọdụ. Ebuli na etiti oghere transformer; tinye eriri eriri na njikọ ndu site na eriri M12. Hazie ihe nlere mmanụ wee jiri nwayọọ nwayọọ na-agbadata mgbe ị na-ebuli elu elu ruo mgbe oke ọhịa dakwasịrị n'elu ebe mgbago elu nke transformer.
5. Ihe owuwu kacha elu
Abụọ- elu akara: skru positioning nuts, fanye cylindrical pins, wepụ ụdọ nylon, skrule connector n'ime onye na-eduzi, ma jiri obe kwechie{1}isi.

Nhazi elu emelitere: fanye atụdo ozugbo, wepụ eriri nylon, wụnye isi ihe nchịkwa, mechie bolts hex, wee hụ na akara nke ọma. A ga-edobe gaskets roba niile nke ọma.

Ọkara na obere voltaji bushings dị mfe karịa HV bushings, na-achọ naanị njikọ ọnụ kpọmkwem na elu kọntaktị dị ọcha na njikwa torque kwesịrị ekwesị.
08 Mmejọ nrụnye nke ịhịa aka n'ahụ

09 Nnwale Tupu Ike
Kwe ka ohia ahụ zuo ike ma ọ dịkarịa ala awa iri abụọ na anọ. Kpochapụ uzuzu dị n'elu na mmiri iji zere mpụpụ mpụga na-emetụta nha mwepu akụkụ (PD). Jiri ọnụ nha nha iji lelee tanδ na mwepu akụkụ. Wepu okpu nchebe, mana achịkọtala ma ọ bụ tụgharịa ọnụ. Jikọọ nha na-eduga na njedebe wee mee ule n'otu usoro. Mgbe anwalechara, tinyegharịa mkpuchi mkpuchi iji hụ na ntọ ala dị mma.
ndetu:Ewepụla ụzọ nha n'oge nleba anya ndụ. Ewepụla mkpuchi mkpuchi mgbe ị na-arụ ọrụ. Weghachite mkpuchi mkpuchi tupu ike. Bushings ga-ezu ike kwụ ọtọ (ihe na-erughị ma ọ bụ hà nhata na mgbagha ogo 30) opekata mpe awa 24 tupu itinye voltaji.
10 Mmechi: Ogo nwụnye na-ekpebi ntụkwasị obi nke ntụgharị
Maka nnukwu 100 MVA transformer, nrụnye ihe nrụnye nke transformer dị elu{1}}ihe ize ndụ yana nnukwu mmetụta-. Njikwa nrụnye nke ọma nke akụkụ nrụnye, torque, sealing, na ule eletrik na-ekpebi ogologo ndụ nke ngbanwe, nchekwa ọrụ, na ụgwọ ọrụ. N'ịgbaso iwu nwụnye transformer, ụkpụrụ na ndenye ndenye na-eme ka nrụnye ihe ntụgharị na-arụ ọrụ nchekwa.
Zipu ozi