Nwụnye na Ntugharị Nrụnye Ụdị Akọrọ

Apr 08, 2026

Hapụ ozi

Dry Type Transformer Installation

1. Okwu mmalite

Ntuziaka a na-enye ntụzịaka zuru oke maka nrụnye, ịrụ ọrụ na nrụzi nke akọrọ{0}} ụdị ihe ngbanwe ọkụ. Ọ na-adabara na ndị na-abụghị -excitation dry-ụdị ike transformers na na-load regulation epoxy resin dry-ụdị ike transformers nwere ike ruru 6300 kVA na voltaji ratings ruo 35 kV. Ntuziaka dị n'ime ebe a na-ekpuchi njem, nchekwa, nrụnye, tupu{9}}nlele ọrụ, nnwale, ọrụ na mmezi.

Ụkpụrụ ndị dị:A na-ahazi ma rụpụta ụdị ihe ngbanwe akọrọ- dị n'ụkpụrụ ndị a: GB 6450-86Ụdị mgbanwe ọkụ ọkụ- kpọrọ nkụ, GB 10228-1997Nka nka na ihe achọrọ maka akọrọ -ụdị mgbanwe ọkụ, na GB 1094.1-1996Ndị Ngbanwe Ike- Akụkụ 1: Ozuruọnụ. Maka ngwa mba ofesi, enwere ike ịmetụ aka na IEC 726 na GB/T 1094.11{3}}2022 *Power Transformers-Nkebi 11: Ụdị ngbanwe *.

Ụdị ihe ngbanwe -dị nkụ dị mma nke ọma- dabara maka ngwa ebe nchekwa ọkụ bụ isi ihe, gụnyere nnukwu- ụlọ elu, ebe azụmahịa, ebe egwuregwu, akụrụngwa mmanụ ala, sistemu ụgbọ oloko, ọdụ ụgbọ elu, na ebe ndị ọzọ nwere oke nchekwa ọkụ chọrọ.

 


 

 

 

 

2. Ọnọdụ ọrụ

 

 

 

2.1 Ọnọdụ ọrụ nkịtị

A haziri ụdị ihe ntụgharị ọkụ kpọrọ nkụ{0}} maka ịrụ ọrụ n'okpuru ọnọdụ ọkọlọtọ ndị a:

Oke

Ọkọlọtọ Uru

Okpomọkụ gburugburu

N'okpuru ogo 40

Elu

N'okpuru 1000 m n'elu pụtara oke osimiri

Iru mmiri dị nso

N'okpuru 93% (enweghị condensation n'elu eriri igwe)

Saịtị nwụnye

Ime ụlọ, nke ọma{{0}ikuku ikuku, enweghị kemịkal na ihe ndị na-emebi emebi

Mgbe ọnọdụ okpomọkụ gafere ogo 40 ma ọ bụ elu gafere 1000 m, a ga-edozirịrị ọkwa ngbanwe dị ka GB 6450 chọrọ.

 

2.2 Klas nchekwa

Ụdị ihe ngbanwe{0} kpọrọ nkụ dị nwere klaasị nchekwa ọkọlọtọ atọ:

IP00:Enweghị mkpuchi mkpuchi; adabara maka ntinye n'ime ụlọ eletrọnịkị raara onwe ya nye ma ọ bụ mgbakọ mgbanwe.

IP20:Na-enye nchebe megide ihe siri ike si mba ọzọ buru ibu karịa 12 mm na dayameta. Nke a bụ ihe a na-ejikarị eme ihe n'ime ụlọ, na-egbochi mmekọrịta mberede na akụkụ ndị dị ndụ ma gbochie obere anụmanụ (òké, agwọ, nwamba, nnụnụ, wdg) ịbanye ma mee ka obere okirikiri.

IP23:Na mgbakwunye na nchekwa IP20, ihe mkpuchi IP23 na-egbochi ntinye mmiri site na ụmụ irighiri mmiri na-ada n'akụkụ akụkụ ruo ogo 60 site na vetikal. Nke a na-eme ka ha dị mma maka nrụnye n'èzí ma ọ bụ gburugburu nwere ìhè mmiri na-agba mmiri. Agbanyeghị, rịba ama na mkpuchi IP23 na-ebelata ikike jụrụ oyi, na-achọ nlebara anya.

dry type transformer enclosure installation
ntinye mkpuchi
IP20 enclosure
IP20 mkpuchi

 

2.3 Ụzọ jụrụ oyi

Uzo oyi abuo di maka akọrọ{0}ụdị transformers:

AN (Ikuku eke):Eke convection jụrụ oyi na-enweghị mmanye ikuku.

AF (Amanyere ikuku):Mmanye ikuku jụrụ site na iji fan. Mgbe ị na-arụ ọrụ n'ime oghere akpọchiri ma ọ bụ enweghị ikuku, a ga-agbakwunye akwa akwa AF. Igwe ikuku agbakwunyere achọrọ bụ 4 m³/min kwa 1 kW nke mkpokọta ọnwụ (P₀ + Pₖ).

AN cooling
AN
AF cooling
AF

 

 

 


 

 

 

 

3. Nhọrọ ntụgharị na nha nha

 

 

 

Nhọrọ nke ngbanwe kwesịrị ekwesị dị oke mkpa maka ntụkwasị obi sistemu yana ịrụ ọrụ ike.

3.1 Na-ekpebi ike akwadoro

Ekwesịrị ikpebi ikike nke ngbanwe (kVA) dabere na ibu agbakọ nke akụrụngwa ejikọrọ. Nke mbụ, gbakọọ ibu dị n'ezie site n'ịchịkọta ọkwa ike akụrụngwa na itinye ihe dị iche iche. Ekwesịrị ịhọrọ ike nke enyere ka ọ gafetụ ibu a gbakọrọ iji nabata ibu ibu n'ọdịnihu.

 

3.2 Oke arụmọrụ igodo

Mgbe ị na-ahọrọ transformer, ekwesịrị iji nlezianya nyochaa parampat ndị a:

Oke voltaji:Ga-adaba na voltaji ọkọnọ na ihe ndị chọrọ voltaji nke akụrụngwa ejikọrọ. Dị ka ihe atụ, 10 kV ọkọnọ na-eje ozi 0.4 kV ibu chọrọ 10 kV/0.4 kV transformer.

Ọ dịghị - ibu mfu na mfu:Paragraf ndị a na-emetụta arụmọrụ ike ozugbo. Ụkpụrụ dị ala na-egosi arụmọrụ ka mma yana mbelata ụgwọ ọrụ.

Voltaji impedance:Na-emetụta ụkpụrụ voltaji yana ọkwa mkpirisi mkpirisi ugbu a.

Ọkwa mkpọtụ:Maka nrụnye n'ime mkpọtụ{0}}gburugburu nwere mmetụta, ụdị mkpọtụ dị ala{1} (ọ na-adịkarị<55 dB) are preferred.

cast coil dry type transformer
nkedo eriri igwe akọrọ ụdị transformer
VPI dry type transformer
VPI akọrọ ụdị mgbanwe

 

 


 

 

 

 

4. Ụgbọ njem

 

 

 

4.1 General Transport chọrọ

Enwere ike ibuga ndị ngbanwe site n'okporo ụzọ ụgbọ oloko, mbupu, ụgbọ ala ma ọ bụ ụgbọ elu. Ụgbọ ala na arịa ga-adị ọcha ma kpọọ nkụ.

4.2 Na-ebu ma na-echekwa

A ga-edobe ngbanwe nke ọma n'ime ụgbọ ala na-ebu njem site na iji traktị, clamps na hinges njikọ.

Ejikọtala ma ọ bụ dọba eriri, insulator, efere ma ọ bụ ụzọ, n'ihi na nke a nwere ike imebi ngwaahịa ahụ.

Ọchịchọ nke transformer n'oge njem agaghị agafe ogo 30.

4.3 Nkwakọba na nchekwa n'oge Transit

Akpokola ihe ngbanwe n'oge nnyefe ma ọ bụ n'ebe njedebe.

A ga-edobe crossbeams osisi (crossies) n'okpuru ihe ntụgharị, na ịdị elu agaghị agafe 100 mm.

4.4 Akwụkwọ na ngwa ndị na-eso ya

Ngwa niile, akụkụ ahụ mapụtara, na ex{0}} akwụkwọ ọrụ ka a ga-ebunye ọnụ na transformer.

transformer loading
ntinye nke transformer
transformer shipping
mbupu transformer

 

 

 

 


 

 

 

 

5. Nyocha na nnabata

 

 

 

Mgbe nnata nke transformer, onye ahịa ga-eme nlele nnabata ndị a ozugbo:

5.1 Nyochaa akara aha

Nyochaa na data akọwara na efere aha (ikike agbagoro, ogo voltaji, ọnọdụ mgbata, otu vector, voltaji impedance, wdg) kwekọrọ na nkọwapụta ndị ekwuru na nkwekọrịta ịzụrụ.

5.2 Nyochaa akwụkwọ

Nyochaa na akwụkwọ - niile na-arụ ọrụ (akwụkwọ nkwado, mkpesa nnwale, ndepụta nkwakọ ngwaahịa, eserese n'ozuzu, wdg) zuru ezu ma kwekọọ n'ụkpụrụ nkwekọrịta.

5.3 Ngwa na akụrụngwa

Lelee akụkụ na ngwa niile emebisịworo megide ndepụta nkwakọ ngwaahịa iji gosi na enweghị mmebi ma ọ bụ ihe efu.

5.4 Nyochaa Ọnọdụ anụ ahụ

Nyochaa ihe ngbanwe na ihe mejupụtara ya maka mmebi ma ọ bụ mbugharị ọ bụla a na-ahụ anya.

Lelee ahịrị njikọ maka ịtọhapụ ma ọ bụ mgbawa.

Lelee insulators maka mgbawa ma ọ bụ mmebi ndị ọzọ.

Wepu osisi crossbeams ọ bụla ma ọ dị ya.

5.5 Nchekwa mgbe nyochachara

Ọ bụrụ na a gaghị etinye transformer n'ọrụ ozugbo nyochachara, a ga-akwakọba ya ma chekwaa ya nke ọma.

 

 


 

 

 

 

6. Nchekwa

 

 

 

6.1 Ọnọdụ nchekwa

Ngwaahịa na ngwa chọrọ nchekwa ekwesịghị imepe ikpe ha belụsọ maka nyocha na nnabata. Mgbe nyochachara, bughachi ya ozugbo.

Maka nchekwa ogologo oge{{0}, tinye ihe ngbanwe na ngwa n'ime ụlọ kpọrọ nkụ, dị ọcha na nke ọma{1}ikuku ikuku.

Echekwala kemịkalụ ma ọ bụ ihe na-emebi emebi n'otu ọnụ ụlọ.

Edokọla ngwaahịa.

6.2 Ime ụlọ vs. Nchekwa n'èzí

Ekwesịrị ịchekwa ụdị ngbanwe {{0} kpọrọ nkụ n'ime ụlọ. Ọ bụrụ na obere oge - nchekwa n'èzí agaghị ekwe omume n'ihi mmachi saịtị:

Emeghela casing.

Lelee ma chekwaa mkpuchi maka mkpuchi mmiri.

Debe crossbeams n'okpuru ihe ngbanwe (ịdị elu na-erughị ma ọ bụ hà 100 mm).

6.3 Oke Ogologo Ogologo

Nchekwa n'èzí agaghị agafe ọnwa abụọ. Ọnọdụ okpomọkụ n'oge nchekwa n'èzí ekwesịghị ịda n'okpuru -10 degrees.

Dry-type transformers indoor storage
Ụdị ihe ngbanwe ime ụlọ kpọrọ nkụ-
dry type transformer storage
Akọrọ ụdị nchekwa nchekwa

 

 

 


 

 

 

 

7. Nwụnye ikpeazụ na saịtị

 

 

 

7.1 Tupu{1}Nkwadebe nwụnye

Tupu ịmalite nrụnye:

Mụta nkọwapụta nke nrụnye, data efere aha, na eserese n'ozuzu ya nke ọma.

Kwadebe akụrụngwa ebuli elu kwesịrị ekwesị (cranes, forklifts, cranes gwongworo) na rigging.

7.2 Ibuli na njikwa

Usoro mbuli elu nke ọma dị oke mkpa iji gbochie mmebi akụrụngwa:

A ga-ebuli elu site na iji mgbanaka ebuli elu na transformer n'otu oge{0}} ewelitela ya naanị otu mgbanaka.

Mgbe ị na-ebuli ihe ngbanwe na-enweghị ngwugwu ma ọ bụ wepụ ya na ngwugwu ya, akụkụ elu agaghị agafe ogo 60.

Maka ndị na-agbanwe agbanwe na-ebufe na -load tap Changers (OLTC) agbakwunyere, ebuli na iji mgbanaka ebuli elu naanị{1}} anaghị ebuli ya site na OLTC.

Mgbe etiti ike ndọda kwụsịrị, gbanwee ogologo wires na-ebuli elu ka o wee nwee nguzozi.

Jiri nlezianya mee ihe n'oge usoro mgbakọ ahụ.

Lifting and Handling of dry type transformer

7.3 Nhazi saịtị na mkpochapụ

Achọrọ mkpochapụ

Ogologo kacha nta

Transformer na mgbidi ma ọ bụ mgbochi

Karịrị ma ọ bụ hà nhata 500 mm

N'etiti n'akụkụ ngbanwe

Karịrị ma ọ bụ hà nhata 500 mm

Ihe ntụgharị dị elu{0}} akụkụ voltaji gaa na mgbidi

Karịrị ma ọ bụ hà nhata 800 mm (atụ aro)

Ihe ntụgharị dị ala- akụkụ voltaji gaa na mgbidi

Karịrị ma ọ bụ hà nhata 600 mm (atụ aro)

Obosara wara ụzọ na-arụ ọrụ

Karịrị ma ọ bụ hà nhata 1200 mm

Transformer na ngere/nche nche

Karịrị ma ọ bụ hà nhata 600 mm

N'etiti transformers abụọ (ọkọlọtọ imewe)

Karịrị ma ọ bụ hà nhata 1.0 m

7.4 Opekempe Nchekwa (Elu-Voltaji Coil ruo Ground)

Opekempe nchekwa dị n'etiti ndị nduzi ume na ala ga-agbasorịrị GB 10237Ọkwa mkpuchi na Nnwale mkpuchi mkpuchi mkpuchi ikuku- Mwepu ikuku nke Mpụga:

Ogo HV

Ihe na-erughị ma ọ bụ hà nhata 1 kV

6 kV

10 kV

15 kV

20kV

35 kV

Nwepu net (mm)

40

60

90

120

160

250

Maka usoro 12 kV, ikuku mkpuchi ikuku kwesịrị ịdị ukwuu karịa ma ọ bụ nhata 125 mm; maka usoro 40.5 kV, Karịrị ma ọ bụ hà nhata 360 mm. Ebe dị anya nke creepage ga-adị ukwuu karịa ma ọ bụ nhata 18 mm/kV maka mkpuchi poselin yana karịa ma ọ bụ nhata 20 mm/kV maka mkpuchi organic.

7.5 Ntọala na ịrị elu

Ntọala ngbanwe ga-etinyerịrị bolts arịlịka ka edobere ya n'usoro ihe nleba anya izugbe iji kwekọọ na oghere mgbago nke transformer.

Ntọala kọnkịrị ga-enwe ikike ibu ibu karịa ma ọ bụ hà nhata 1.5 ugboro nke ịdị arọ nke ngbanwe, yana ngbanwe dị larịị nke na-erughị ma ọ bụ hà nhata 2 mm/m.

Maka nrụnye seismic ma ọ bụ vibration{0}}, a ga-etinye n'akụkụ anọ niile.

Maka ndị na-agbanwe agbanwe nwere wiil ndị na-abaghị uru, wiil ndị ahụ nwere ike ịtụgharị ogo 90 na ntụgharị ntụgharị. Mgbe etinyere ya, a ga-ewepụrịrị ma ọ bụ kpochie wiil ya n'ebe, na-edozi ihe ntụgharị site na arịlịka bolts.

A ga-ekpochapụ ụgbọala na-adọkpụ (mbupu isi) mgbe etinyere ya.

7.6 USB na njikọ Busbar

A ga-akwadorịrị eriri ma ọ bụ ụgbọ ala na-abata na nke na-apụ apụ nke ọma ma kụchie ya iji gbochie nrụgide n'arụ ọrụ na ọnụ ụzọ mgbanwe.

A ghaghị ịchachasị nkwonkwo bọsbar ọla kọpa ma were griiz conductive kpuchie ya tupu njikọ.

Achọrọ Torque maka fasteners:

Nha Bolt

M10

M12

M16

M20

Torque (Nm)

30

33

35

45

7.7 Mgbanwe

Ntọ ala nke ọma dị mkpa maka nchekwa:

Mkpuchi ihe ngbanwe, isi, na ebe na-anọpụ iche ga-enwerịrị ntọala nke onwe ya.

Ndị na-eduzi ala ga-eji eriri ọla kọpa nwere mpaghara obe{0}karịa ma ọ bụ ha nhata 50 mm².

Nguzogide ala ga-adị obere ma ọ bụ haha ​​na 4Ω.

 

dry type transformer site installation
akọrọ ụdị mgbanwe saịtị echichi
dry type transformer site install
akọrọ ụdị ngbanwe saịtị wụnye

 

 

 


 

 

 

 

8. Nyocha tupu ọrụ

 

 

 

Tupu itinye transformer n'ọrụ, a ga-eme nyocha ndị a:

8.1 Nyocha igwe

Lelee niile fasteners na njikọ; megharịa{0} ka ọ dị mkpa.

Nyochaa na etinyere akụrụngwa niile nke ọma ma chekwaa ya.

Wepu ihe ọ bụla si mba ọzọ ma ọ bụ ájá kwakọba (tụ aka na ngalaba 11.2 maka usoro nhicha).

8.2 Sistemụ jụrụ oyi na nyocha onye na-ahụ maka okpomọkụ

Lelee ndị fan iji hụ na a na-arụ ọrụ nkịtị.

Nyocha dị mkpa:Nyochaa ntụzịaka ntụgharị nke ndị na-akwado mgbanwe mgbanwe oge atọ{{0}. Usoro ikuku ga-esi n'okpuru eriri igwe pụta. Ọ bụrụ na ntụziaka ahụ ezighi ezi, gbanwee usoro nke usoro dịka nkọwapụta.

Lelee ndị na-ahụ maka okpomọkụ na nkeji ngosi okpomọkụ maka ịrụ ọrụ nkịtị.

Gbaa mbọ hụ na ntọ ala nke ọma nke ndị na-ahụ maka okpomọkụ na ngwa dị ka nkọwapụta ha siri dị.

Nyochaa na etinyere sensọ njikwa ọnọdụ okpomọkụ nke ọma n'ime oghere ntụ ọkụ ikuku (omimi ntinye nke karịrị 80 mm ma ọ bụ hà nhata).

8.3 Ihe njikwa okpomoku ndabara

Ụdị ndabara ndabara maka akọrọ -ụdị mgbanwe okpomọkụ bụ:

Oke okpomoku

Omume

Ihe na-erughị ma ọ bụ haha ​​na ogo 80

Fans kwụsị

Karịrị ma ọ bụ haha ​​na ogo 100

Fans na-amalite na-akpaghị aka

Karịrị ma ọ bụ haha ​​na ogo 130

Oti mkpu okpomọkụ karịrị{{0}

Karịrị ma ọ bụ haha ​​na ogo 150

Ngafe okpomọkụ{{0}

 

 

 


 

 

 

 

9. Nwale tupu ọrụ

 

 

 

A ga-eme ule ndị a tupu etinye transformer n'ọrụ:

9.1 DC Nleba Nguzogide

Tulee nguzogide DC nke windings n'ọnọdụ ọ bụla mgbata iji nyochaa kọntaktị kwesịrị ekwesị wee chọpụta njikọ ọ bụla rụrụ arụ.

9.2 Voltage Ratio na Vector Group Test

Tụọ oke voltaji n'ọnọdụ ọ bụla mgbata wee chọpụta aha otu vector.

9.3 nkwenye ala

Lelee na ahụ transformer na isi bụ ndị ala ala kpamkpam.

9.4 Ntụle Mgbochi Mgbochi (Windings)

Nwalee

Ihe achọrọ

Megohmmeter

HV-LV & HV-Ụwa

Karịrị ma ọ bụ hà nhata 300 MΩ

2500 V

LV-Ụwa

Karịrị ma ọ bụ hà nhata 100 MΩ

2500 V

Ọnọdụ ule:Okpomọkụ 20-30 degrees, iru mmiri na-erughị 90% ma ọ bụ nhata.

Ụkpụrụ mgbochi mkpuchi ga-ebelata na ọnọdụ iru mmiri. N'okpuru ọnọdụ mmiri mmiri, uru nguzogide kwesịrị ịbụ ihe na-erughị 2 MΩ kwa 1000 V nke voltaji egosipụtara (ọgụgụ a na-ewere na ogo 25 maka otu nkeji). Maka ndị na-agbanwe agbanwe nke ghọrọ mmiri mmiri ma ọ bụ gosi akara nke condensation/ntu oyi, a ga-emerịrị ọgwụgwọ ihicha tupu ọrụ wee nagide ule voltaji, n'agbanyeghị ụkpụrụ nguzogide ikuku.

9.5 Isi Mgbochi Nlebanya

Kwụpụ isi ihe mgbakwasị ụkwụ tupu nnwale.

Nwalee

Ihe achọrọ

Megohmmeter

Isi – Clamps & Ụwa

Karịrị ma ọ bụ hà nhata 2 MΩ

500 V

Ịkpọpu ihe ịghasa – eriri igwe & LV

Karịrị ma ọ bụ hà nhata 100 MΩ

500 V

Ọnọdụ ule:Okpomọkụ 20-30 degrees, iru mmiri na-erughị 90% ma ọ bụ nhata.

N'okpuru ọnọdụ iru mmiri, ụkpụrụ a tụrụ atụ ga-ebelata. Mgbe ọgwụgwọ ihichachara, uru nguzogide ga-adị ukwuu karịa ma ọ bụ hà nhata 0.1 MΩ tupu itinye ihe ntụgharị ahụ n'ọrụ.

9.6 Na nyocha {{1}Load Tap Changer (OLTC).

Maka ndị na-agbanwe agbanwe nwere OLTC, lelee ma nwalee dabere na nkọwapụta nke ndị nrụpụta OLTC tupu arụ ọrụ.

9.7 Ugboro ike na-eguzogide ule voltaji

Tinye voltaji na-eguzogide ugboro ugboro na 85% nke voltaji ule ụlọ ọrụ.

9.8 Nchịkọta ule nnabata

Mgbe emechara ule niile, a ga-akwadorịrị akwụkwọ nnabata ndị a: akụkọ nnwale (gụnyere nsonaazụ nnwale ntọhapụ, Ihe na-erughị ma ọ bụ ha nhata 10 pC), ndekọ nrụnye, yana data njikwa okpomọkụ.

dry type transformer test
akọrọ ụdị ngbanwe ule
dry type transformer tests
akọrọ ụdị ngbanwe ule

 

 

 


 

 

 

 

10. Ọrụ na Ọrụ

 

 

 

10.1 Kpatụ Ndozigharị ọnọdụ (Na-abụghị - ihe mkpali)

Maka ndị na-agbanwe mgbanwe ndị nwere gbanyụọ- ndị na-agbanwe mgbata okirikiri (dịka ọmụmaatụ, ogo voltaji 10,000 V ± 2 × 2.5%):

Pịa Ọnọdụ

Mpụta voltaji

2–3

10,500 V

3–4

10,250 V

4–5

10,000 V

5–6

9,750 V

6–7

9,500 V

Ọ bụrụ na voltaji sistemu ike mpaghara bụ 10 kV, jikọọ taps na ọnọdụ 4-5.

Ọ bụrụ na voltaji ọkọnọ gafere 10,500 V, gbanwee gaa n'ọnọdụ mgbata dị elu mgbe ị kwụsịrị voltaji dị elu.

Ọ bụrụ na voltaji ọkọnọ dị n'okpuru 9,500 V, gbanwee gaa na ọnọdụ mgbata dị ala mgbe ị kwụsịrị nnukwu voltaji.

A ga-emerịrị mmezi mgbata niile site na ịgbanyụ voltaji dị elu.

10.2 OLTC arụ ọrụ

Maka ndị na-agbanwe agbanwe nwere ndị na-agbanwe ihe mgbata ọkụ{{0}, rụtụ aka na nkọwapụta OLTC akọwapụtara. Enwere ike itinye transformer ka ọ rụọ ọrụ naanị mgbe emezigharịrị OLTC nke ọma. Kwupu ike tupu ime mgbanwe ọ bụla.

10.3 Njikwa okpomọkụ na Ngosipụta

Maka ndị na-agbanwe agbanwe nwere ihe njikwa okpomọkụ na ngosipụta okpomọkụ:

Buru ụzọ mee ka ihe ngbanwe dị ike, wee mee ka njikwa okpomọkụ wee gosipụta ya.

Hazie akụrụngwa dịka nkọwa njikwa okpomọkụ kwekọrọ.

10.4 Ike izizi

Emela ọrụ mmechi- nbibi{1}. Mwepu kachasị elu{3}} ọnụ ọgụgụ kasị elu nke mmechi inrush dị ugbu a nwere ike iru ugboro 8-10 karịa ọkwa ugbu a-nke a bụ ihe nkịtị.

Jiri nwayọọ nwayọọ na-abawanye ibu site na obere gaa na nnukwu mgbe ị na-enyocha ụda adịghị mma.

10.5 Mba{1}}Arụ ọrụ

Ọ dịghị - ọrụ ibu ga-agbaso IEC 905Iwu maka nkụnye ọkụ{0}Ụdị mgbanwe ọkụ. Enwere ike ime ọrụ ibufe obere oge{1} dabere na ọnọdụ okpomọkụ na ọnọdụ ibu mbụ.

10.6 Ibu ibu ike

Mgbe ọnọdụ ihu igwe dị ala karịa uru akwadoro, ike nrụpụta nwere ike ịdị elu karịa ụkpụrụ akwadoro, yana ọzọ.

Ikike ibufe nke akọrọ{0} ụdị ihe ngbanwe na-adabere na ọnọdụ okpomọkụ, ọnọdụ tupu ibu ibu, njirimara mwepu ikpo ọkụ, na oge okpomọkụ na-adịgide adịgide. Ekwesịrị ịnweta akụkụ ndị na-ebufe ibu site n'aka onye nrụpụta maka ngwa ụfọdụ.

10.7 Ọnọdụ ọrụ pụrụ iche

Enwere ike itinye ụdị ihe ntụgharị ọkụ kpọrọ nkụ{0}} n'ọrụ ozugbo emechara ume mbụ na-enweghị ọgwụgwọ pụrụ iche.

Otú ọ dị, ọ bụrụ na transformer na-arụ ọrụ n'ikuku dị mmiri mmiri ma ọ bụ gosi akara nke condensation/frost, a ghaghị ịme ọgwụgwọ ihicha tupu arụ ọrụ na-esote.

10.8 Usoro izizi ike mbụ

Emela ume ike- ugboro atọ, yana nkeji nkeji ise n'etiti ọrụ ọ bụla, wee lelee inrush current.

Na-arụ ọrụ na ibu Ihe na-erughị ma ọ bụ hà nhata 30% maka awa 24 iji nyochaa arụmọrụ.

Mmụba ikuku ikuku agaghị agafe 100 K maka mkpuchi klaasị F.

 

 


 

 

 

 

11. Nlekọta

 

 

 

11.1 Ugboro nyocha

gburugburu

Ugboro nyocha

Ebe dị ọcha, kpọrọ nkụ

Otu ugboro kwa afọ

Ebe e merụrụ emerụ

Kwa ọnwa 3-6

Ndị na-agbanwe mgbanwe ọhụrụ e nyere ọrụ kwesịrị ịnata nlele mbụ ha mgbe ọnwa 2-3 gachara ọrụ, na-esotekwa nyocha zuru oke kwa afọ ma emechaa. A na-atụ aro imegharị ihe zuru oke kwa afọ 3-5, ma ọ bụ dị ka onye nrụpụta nyere ndụmọdụ dabere na ọnọdụ akụrụngwa.

11.2 Nhicha

Lelee ma hichaa uzuzu ekpokọbara iji hụ na ikuku ikuku kwesịrị ekwesị ma gbochie ndakpọ mkpuchi.

Lezienụ anya n'ụzọ pụrụ iche na insulators na obere padding blocks.

Jiri ikuku kpọrọ nkụ ekpochapụ ọkpọkọ na ọwa mmiri jụrụ oyi (nrụgide ikuku na-erughị ma ọ bụ nhata 0.2 MPa).

11.3 Nleba anya

Lelee ihe ndị a n'oge nlele ọ bụla:

Fasteners, njikọ, na eduzi akụkụ maka nchara ma ọ bụ corrosion.

Elu mkpuchi maka akara creepage na carbonization.

Nkwado insulators maka mgbawa ma ọ bụ mgbawa akara.

Fans jụrụ oyi maka ọrụ nkịtị.

Njikọ voltaji dị elu na nke dị ala maka akara oke ọkụ.

Isi na winding maka mwepu, isi, ma ọ bụ ihe ọjọọ ndị ọzọ.

11.4 Nnwale mkpuchi mkpuchi oge

N'oge nhazi nhazi (ihe dị ka afọ ise ọ bụla), tụọ nguzogide mkpuchi dịka akụkụ nke 9.4 na 9.5 siri dị iji chọpụta ma akụrụngwa nwere ike ịga n'ihu na ọrụ. A na-atụkwa aro nnwale mgbochi mgbochi oge niile kwa ọnwa 6-12 ọ bụla.

dry type transformer cleaning
akọrọ ụdị transformer ihicha
dry type transformer manufacturing
akọrọ ụdị transformer n'ichepụta

 


 

 

 

 

 

12. Nrụnye Transformer emetụtara & Ntuziaka ọrụ

 

 

 

A na-ejikarị ihe ngbanwe ụdị kpọrọ nkụ eme ihe n'ime ụlọ yana na gburugburu ebe mmiri nwere mmetụta. Maka ngwa n'èzí, mmanụ jupụtara, ma ọ bụ ihe nkwụnye osisi, biko rụtụ aka na ntuziaka nrụnye na nrụnye ndị a.

 

 

 


 

 

 

 

13. Nchekwa nchekwa

 

 

 

12.1 Mkpuchi na Nchekwa

A ga-etinyerịrị ihe ngbanwe na-arụ ọrụ na-enweghị ebe nchekwa na ogige nchebe dị iche iche iji gbochie ihe mberede na-adịghị mma.

Maka nrụnye n'èzí ma ọ bụ nke ọkara{0}, a ga-enyerịrị ụzọ nchekwa nke opekata mpe 1.5 m n'ịdị elu n'akụkụ ihe ngbanwe ahụ, yana opekempe 0.5 m n'etiti ihe ngbanwe na nrụnye nche.

12.2 Omume amachibidoro

Ọ dịghị onye nwere ike imetụ ihe ngbanwe ahụ aka ma ọ na-enye ike.A ga-arụrịrị ọrụ ọkụ eletrik niile site na iji transformer emeziwanye ike, kpochie ya, ma kpado ya.

12.3 Ndị ọrụ tozuru oke

Nlele niile, nlele mkpuchi, na ọrụ mmezi na transformer ga-abụ ndị ọkachamara ọkụ eletrik zụrụ azụ na ndị ruru eru.

12.4 Nkwado enyemaka mbụ

A ga-emebe atụmatụ nzaghachi mberede, gụnyere usoro enyemaka mbụ maka ujo ọkụ eletrik ma zụọ ndị ọrụ ya otu a.

 

 