2100 kVA Akọrọ Ụdị nkesa nkesa-13.8 / 0.46 kV|South Africa 2024
Ike: 2100kVA
Voltaji: 13.8/0.46 kVA
Njirimara: ya na CT (5000/1)

Ihe nkesa nkesa ụdị akọrọ 2100 kVA nke ọma nwere mkpuchi dị elu yana nchebe smart.
01 Izugbe
1.1 Nkọwa oru ngo
Emepụtara maka onye ahịa South Africa na 2024, ụdị nkesa nkesa 2100 kVA akọrọ na-egosipụta windings nke etinyere nke ọma na resin epoxy. N'ịbụ mmanụ na-efu -, ọ na-ebelata ohere nke ọkụ na mmetọ gburugburu ebe obibi. Site na mkpuchi klaasị F akwadoro maka okpomọkụ na-arụ ọrụ ruo ogo 155.
A na-atụle ihe ngbanwe ahụ na 2100 kVA, yana voltaji bụ isi nke 13.8 kV na voltaji nke abụọ nke 0.468 kV (468 V). Ọ dị mma maka ịgbanye igwe mgbọ m na ngwa nhazi dị arọ nke na-arụ ọrụ na 468 V.
Otu vector ya bụ D (+15 ogo )d0, ebe akụkụ dị elu{2}} voltaji na-egosipụta mgbanwe usoro ogo +15. Nhazi a na-egbo mkpa usoro usoro ma na-enyere aka belata harmonics na ikesa mmiri n'oge arụ ọrụ yiri ya.
A na-eme isi ya bụ silicon steel nke nwere ọka, nke na-enye mfu dị ala yana njupụta magnetik dị elu, na-enye aka na mfu enweghị obere{{0} nke 3.2 kW.
Ejiri onye na-ahụ maka okpomọkụ na ihe ntụgharị dị ugbu a (5000/1 CT), onye na-agbanwe agbanwe na-akwado nlekota ikuku na nchedo ikuku, yana nha nke ugbu a, na-eme ka ntinye aka na nchebe na usoro nlekota oru.
1.2 Nkọwa nka nka
2100kVA Resin nkedo akọrọ ụdị ntụgharị nkọwapụta na mpempe akwụkwọ data
|
Enyere ya
South Africa
|
|
Afọ
2024
|
|
Ụdị
Resin nkedo ụdị ngbanwe
|
|
Isi ihe
Mpempe akwụkwọ silicon na-adabere na ọka
|
|
Ọkọlọtọ
IEC60076
|
|
Enyere ike
2100 kVA
|
|
Ugboro ugboro
60HZ
|
|
Usoro
Atọ
|
|
Otu vector
D(+15 ogo )d0
|
|
Ụdị oyi
AN
|
|
Voltaji nke mbụ
13.8 kV
|
|
Voltaji nke abụọ
0,468 kV
|
|
Ngwa ikuku
AL
|
|
Mgbochi
7.5%
|
|
Pịa Changer
/
|
|
Ọkụ aka
/
|
|
Enweghị mfu ibu
3.2 kW
|
|
Na Ọnwụ Ebu
3.2 kW
|
|
Ọkwa mkpuchi
F
|
|
Ngwa ngwa
Onye na-ahụ maka okpomọkụ, CT (5000/1)
|
1.3 Eserese
2100kVA resin nkedo akọrọ ụdị ihe ngbanwe eserese

02 Nrụpụta
2.1 Isi
Ihe nkesa 2100 kVA atọ - nkesa ụdị nkụgharị ihe nkesa isi na-eji ọka{2}} na-eji mpempe akwụkwọ nchara silicon nke nwere nnukwu ike ndọta, na-eme ka arụmọrụ elektrọnịk dịkwuo mma yana ibelata mfu ndị bụ isi. Ibé akwụkwọ ndị a nwere ihe arụrụ arụ siri ike iji nagide nhazi yana nrụgide ogologo oge{{4}. SCOTECH na-eme ka ọ bụrụ ihe na-erughị ma ọ bụ nhata 0.02mm na enweghị ntụpọ. A na-eji mmiri kpuchie isi isi okwu - resin epoxy na-egosi maka ịdịte aka yana nchebe iru mmiri.

2.2 Ikuku

Ụdị ihe ngbanwe akọrọ akọrọ na-egosipụta windings abụọ, nke ejiri ndị na-eduzi aluminum na-adịgide adịgide rụọ ya iji hụ na arụmọrụ dị mma na ogologo ndụ ọrụ. A na-eji ihe mkpuchi klaasị F kpuchie ikuku niile, yana ikuku epoxy klaasị F nwere oghere, na-etolite sistemu mkpuchi siri ike, iru mmiri{1} na nke na-ekpo ọkụ.
2.3 ikpeazụ mgbakọ
A na-achịkọta isi ihe ndị a kpụrụ akpụ na ikuku, n'oge a na-eme njikọ eletriki, mkpuchi, na nhazi nhazi.
N'okpuru oghere, a na-awụsa resin epoxy n'etiti windings na isi, na-eme ka usoro siri ike, gwọọ.
Mgbe mgbakọ na ọgwụgwọ gasịrị, a na-eme usoro ule eletriki na ígwè ọrụ iji hụ na onye na-agbanwe agbanwe na-ezute ụkpụrụ nhazi na nchekwa.

03 Nnwale


Nnwale oge niile
1. Ntụle nke winding iguzogide
2. Ntụle nke voltaji ratio na ịlele nke oge mbughari
3. Nleta nke mkpụmkpụ - ihe mgbochi okirikiri na mfu ibu
4. Nleta nke enweghị - ibu mfu na ugbu a
5. Nnwale voltaji etinyere
6. Nnwale ule na-eguzogide voltaji
7. Nnwale mwepụ nke akụkụ
8. Oil Dielectric Test
Nsonaazụ ule
|
Mba. |
Nwale ihe |
Nkeji |
Ụkpụrụ nnabata |
Ụkpụrụ ndị atụtara |
Mmechi |
|
|
1 |
Ntụle nke winding iguzogide |
/ |
Ọnụego enweghị nguzozi kacha nguzogide Nguzogide ahịrị: Ihe na-erughị ma ọ bụ haha 2% |
HV (akara) |
LV (akara) |
Gafe |
|
0.18% |
1.61% |
|||||
|
2 |
Ntụle nke oke voltaji na nlele nke mbugharị oge |
/ |
Nkwenye nke oke voltaji na ọpịpị bụ isi: ± 1/10 Akara njikọ: D({0}} ogo )d0 |
-0.18% ~ -0.07% D(+15 ogo )d0 |
Gafe |
|
|
3 |
Ntụnye nke Mkpirisi-Mkpirisi okirikiri na mfu ibu |
/ kW kW |
t:120 ogo Z%: uru tụrụ Pk: uru tụrụ Pt: uru tụrụ |
8.13% 12.662 16.261 |
Gafe |
|
|
4 |
Ntụle nke mba- ibu mfu na ugbu a na 90% na 110% nke voltaji e gosiri |
/ kW |
I0 :: nye uru a tụrụ atụ P0: nye uru a tụrụ atụ |
90% Uru |
110% Ur |
Gafe |
|
0.162% |
0.198% |
|||||
|
2.3265 |
2.8435 |
|||||
|
5 |
Nnwale voltaji etinyere |
/ |
HV: 38kV 60s LV: 3kV 60s |
Enweghị ọdịda nke voltaji ule a na-eme |
Gafe |
|
|
6 |
Nnwale Iguzogide Voltaji butere |
/ |
Voltaji etinyere (KV): 2 Ua Voltaji ebutere (KV): 0.936 Ogologo oge (s):40 Ugboro (HZ): 150 |
Enweghị ọdịda nke voltaji ule a na-eme |
Gafe |
|
|
7 |
Nnwale mgbapu akụkụ |
pC |
Ọkwa kacha nke mwepu akụkụ ga-abụ 10 pC |
<10 |
Gafe |
|
04 Mbukota na mbupu


05 Saịtị na nchịkọta
Nke a 2100 kVA resin nkedo ụdị nkesa ihe ngbanwe a, bụ nke ahaziri maka onye ahịa South Africa. Ihe ngbanwe a dabara adaba maka igwe ọrụ dị arọ-, nnukwu moto, na akụrụngwa nhazi na ngwa Ngwuputa na ngwa nrụpụta chọrọ nnukwu ibu. SCOTECH dị njikere ịnye ahaziri ọkachamara na ọrụ dị mma iji gboo ihe ị chọrọ.
Dị ka ọkachamara na-emepụta ihe ngbanwe ụdị akọrọ, SCOTECH na-enye ngwaahịa ndị kwekọrọ n'ụkpụrụ mba ụwa dịka IEC, ANSI/IEEE, NEMA, CSA, na BS. Ụdị ihe ngbanwe resin nke akọrọ anyị na-ekpuchi ike sitere na 50 kVA ruo 15 MVA, yana nnukwu voltaji ruo 36 kV. Ma ugboro 50 Hz na 60 Hz dị, yana njikọ delta ma ọ bụ kpakpando. A na-ekpuchi windings voltaji nke etiti na resin epoxy, yana klas mkpuchi sitere na A, E, B, F ruo H, yana ọkwa nchebe nwere ike ịhazi ya site na IP 2X ruo IP 4X.
Nhọrọ oyi na-agụnye oyi ikuku eke (ONAN) na mmanye ikuku jụrụ oyi (ONAF), nke nwere otutu ihe mmetụta okpomọkụ na relays okpomọkụ maka nchebe ọkụ a pụrụ ịdabere na ya. Anyị na-ewetakwa ngwa dị ka wiil, transformers ugbu a, na -load tap Changers (OLTC), na igbe mmiri iji gboo mkpa ndị ahịa dị iche iche.

Ihe nchịkọta dị ọkụ: akọrọ ụdị nkesa transformer, emeputa, soplaya, price, efu
You Might Also Like
630 kVA Nkedo eriri igwe ntụgharị-6.6 / 0.55 kV|Sout...
250 kVA Dry Cast Resin Transformers-10/0.4 kV|Georgi...
400 kVA Akọrọ Ụdị Ngbanwe eletriki-0.55 / 0.46 kV|Sa...
2500 kVA Dry Transformer-10 / 0.4 kV|Georgia 2025
630 kVA Atọ nke Akọrọ Ụdị Ntugharị-10 / 0.4 kV|Georg...
630 kVA 3 Usoro akọrọ ụdị ntụgharị-6.6 / 0.55 kV|Sou...
Zipu ozi