75 kVA Transformer Ahịrị ike-13.8 / 0.12 * 0.24 kV|Guyana 2024
Ike: 75kVA
Voltaji: 13.8 / 0.12 * 0.24 kVA
Njirimara: ya na IFD

Ogige 75kVA tụkwasịrị ntụkwasị obi-Ugwu Transformers - SCOTECH Communities Powering Communities kemgbe 1999
01 Izugbe
1.1 Nkọwa oru ngo
Nke a bụ 75 kVAotu -osisi n'usoro{1} atụkwasịrị ihe ngbanweE bugara ya na Guyana na 2024. Soro ụkpụrụ IEEE & ANSI C57.12.00 siri ike. Polarity na-ebelata, na otu vector bụ Ii0. Edere maka voltaji izizi nke 13,800V na voltaji nke abụọ nke 120/240V, na-eme ka ọ dabara maka ngwa obibi na obere azụmaahịa.
Ihe ntụgharị ọkụ ọkụ na-egosipụta windings ọla kọpa maka nkwalite arụmọrụ na arụmọrụ. Ihe mgbochi nke 2%, na-ahụ na ọdịda voltaji dị ntakịrị n'okpuru ibu. ± 2.5% nke ịkụ aka, yana ngụkọta nke 10%. Na-enye ntọala ụkpụrụ voltaji enwere ike ịhazi ya, na-enye ohere njikwa nke ọma iji gboo mkpa ike pụrụ iche.
SCOTECHnwere ihe karịrị afọ 25 nke ahụmahụ n'ichepụta transformer. Ọbụna nnukwu iwu nwere ike ịnyefe n'oge site na nkwado otu.
1.2 Nkọwa nka nka
Nkọwapụta ahịrị ahịrị ike nke 75 kVA na mpempe data
|
Enyere ya
Guyana
|
|
Afọ
2024
|
|
Ụdị
Otu akụkụ okporo osisi etinyere ngbanwe
|
|
Ọkọlọtọ
IEEE & ANSI C57.12.00
|
|
Enyere ike
75 kVA
|
|
Ugboro ugboro
60HZ
|
|
Polarity
Mwepu
|
|
Otu vector
Ii0
|
|
Voltaji nke mbụ
13800 V
|
|
Voltaji nke abụọ
120/240 V
|
|
Ngwa ikuku
Ọlapa
|
|
Mgbochi
2%
|
|
Usoro jụrụ oyi
ONAN
|
|
Pịa Changer
NLTC
|
|
Ọkụ aka
±2X2.5%(Ngụkọta oke=10%)
|
|
Enweghị mfu ibu
214 W
|
|
Na Ibu Mfu
713 W
|
|
Ngwa ngwa
Nhazi ọkọlọtọ
|
1.3 Eserese
75 kVA transformer ahịrị ike na-akọwapụta eserese na aha aha
![]() |
![]() |
02 Nrụpụta
2.1 Isi
Cores ọnya dị kọmpat ma dịkwa fechaa, na-eme ka ọ dị mma maka otu {{0}pole phase{1}} nke etinyere n'ụba. Cores ọnya nwere nkwonkwo ole na ole, ụzọ ndọta ha na-efegharị na-adakọkwa n'ụzọ ntụgharị nke mpempe akwụkwọ magnetik, na-ebute mfu na-aga n'ihu na-aga n'ihu-. Uru ọzọ nke cores ọnya bụ na ha dị jụụ karịa cores laminated.

2.2 Ikuku

Igwe ọkụ eletrik nke dị kVA 75 anyị na-eji ikuku dị elu- enamed gburugburu waya ọla kọpa, na-egosipụta ọmarịcha ọkụ eletrik yana mkpuchi kọmpat. Waya ọla kọpa gbara okirikiri dị mfe ijikwa ma dabara maka ikuku akpaaka dị elu{3}. Nabata ihe nhazi igwe ikuku nke ikuku ikuku maka obere-coils voltaji na ikuku ikuku maka igwe ikuku dị elu{6}, na-eme ka nkwụsi ike na-arụ ọrụ nke ọma, ntụkwasị obi na ịrụ ọrụ ọkụ.
2.3 tank
N'ime na n'èzí tank ahụ, a ghaghị iwepụ ihe niile na-agbado ọkụ na spatter, na-elebara anya pụrụ iche na ntọala radiator na ihe na-ebuli elu iji zere ntụpọ nwụrụ anwụ. Mgbe nchara nchara, a ga-etinyerịrị ihe mgbochi mbụ - nchara n'ime awa isii; gafere nke ahụ, re{2}}a chọrọ mkpọmkpọ ájá. A ga-etinye mkpuchi mkpuchi na uwe elu abụọ na uwe elu abụọ, na mkpokọta 80 mil, nchikota siri ike, na nke dị nro, ọbụna na-egbuke egbuke.
2.4 Mgbakọ ikpeazụ
1. Mgbakọ ikuku:Wepụ ikuku HV/LV na isi laminated, na-ahụ na nhazi na mkpuchi mkpuchi kwesịrị ekwesị.
2. Njikọ eletrik:Jikọọ winding na-eduga na mgbata mgbata, bushes na ihe ndị ọzọ, wee chekwaa na mkpuchi nkwonkwo.
3. Isi -Ikpokoro eriri igwe:Tinye akụkụ ahụ gbakọtara (isi + windings) n'ime oven akpọnwụ maka ikpo ọkụ iji wepụ mmiri mmiri.
4. Nwụnye tankị:Tinye akụkụ ahụ a mịrị amị na-arụ ọrụ n'ime tank, dobe ya nke ọma, wee hụ na mkpuchi kwesịrị ekwesị site na mgbidi tank.
5. Ngwa mgbakwunye:Wụnye bushes, valvụ enyemaka nrụgide na ngwa ndị ọzọ, wee lelee maka ntapu.
6. Ndochi mmanụ & idozi:Vacuum{0}juju na mmanụ mkpuchi, degas, ma kwe ka edozi tupu ịlele ọkwa mmanụ yana ike dielectric.


03 Nnwale
Nnwale oge niile
1. Ntụle Nguzogide
2. Nnwale oke
3. Nnwale polarity
4. Ọ dịghị ibu efu na ọ dịghị ibu ugbu a
5. Ibu Ibu na Voltage Mgbochi
6. Nnwale voltaji etinyere
7. Nnwale anabatara voltaji
8. Ntụle Nguzogide mkpuchi
9. Nnwale ntanye na nrụgide maka mgbanwe mgbanwe mmiri mmiri
10. Oil Dielectric Test

Nsonaazụ ule
|
Mba. |
Nwale ihe |
Nkeji |
Ụkpụrụ nnabata |
Ụkpụrụ ndị atụtara |
Mmechi |
|
1 |
Ntụle Nguzogide |
/ |
/ |
/ |
Gafe |
|
2 |
Nlele oke |
/ |
Ngbanwe nke oke voltaji na ọpịpị bụ isi: Ihe na-erughị ma ọ bụ haha 0.5% Akara njikọ: ii0 |
-0.02 |
Gafe |
|
3 |
Nnwale polarity |
/ |
Mwepu |
Mwepu |
Gafe |
|
4 |
Ọ dịghị - ibu mfu na mkpali ugbu a |
% kW |
I0 :: nye uru a tụrụ atụ P0: nye uru a tụrụ atụ nnabata maka enweghị ibu ibu bụ +10% |
0.49 0.174 |
Gafe |
|
5 |
Ibu ibu, voltaji impedance, ngụkọta ọnwụ na arụmọrụ |
/ kW kW |
t:85 ogo Z%: uru tụrụ Pk: uru tụrụ Pt: uru tụrụ nnabata maka impedance bụ ± 10% Nkwenye maka mkpokọta mfu ibu bụ +6% |
1.98 0.710 0.884 99.11 |
Gafe |
|
6 |
Nnwale voltaji etinyere |
/ |
HV: 34KV 60s LV: 10kV 60s |
Enweghị ọdịda nke voltaji ule a na-eme |
Gafe |
|
7 |
Nnwale Iguzogide Voltaji butere |
/ |
Voltaji etinyere (KV): 2 Ua Ogologo oge (s): 48 Ugboro (HZ): 150 |
Enweghị ọdịda nke voltaji ule a na-eme |
Gafe |
|
8 |
Ntụle Nguzogide mkpuchi |
GΩ |
HV -LV gaa n'ala LV-HV gaa n'ala HV&LV ruo Ground |
77.3 68.9 64.5 |
/ |
|
9 |
Ule ntapu |
/ |
Ntinye nrụgide: 20kPA Ogologo oge: 12h |
Enweghị ntapu na mba Mmebi |
Gafe |
|
10 |
Nnwale Dielectric mmanụ |
kV |
Karịrị ma ọ bụ hà nhata 45 |
52.00 |
Gafe |
04 Mbukota na mbupu

05 Saịtị na nchịkọta
N'ịbụ nke a pụrụ ịdabere na ya na ịrụ ọrụ nke ọma, ewuru eriri ọkụ eletrik 75 kVA maka Guyana. Site na ikuku ọla kọpa dị elu-, nhazi tankị na-adịgide adịgide, yana njikwa mma siri ike, ọ na-eme ka ikesa ike kwụsie ike yana ogologo oge-.

Ihe nchịkọta dị ọkụ: ahịrị ike nke transformer, onye nrụpụta, onye na-eweta, ọnụahịa, ọnụ ahịa
You Might Also Like
150 kVA Pmt Transformer-19.92 / 0.24 * 0.12 kV|Canad...
500 kVA Pole Transformer-4.16 / 0.6 kV|Canada 2024
75 kVA ntụgharị na ogwe osisi-13.8 / 0.347 kV|Canada...
500 kVA Ogwe Ntugharị Ntugharị-24.94 / 0.6 kV|Canada...
167 kVA Pole Nkwanye nkesa nkesa-24.94 / 0.12 / 0.24...
167 kVA Ogwe Ntugharị Ntugharị-13.8 / 0.12 * 0.24 kV...
Zipu ozi