50 kVA Ogwe Ntugharị-34.5 / 0.48 kV|Canada 2024
Ike: 50kVA
Voltaji: 34.5/0.48kV
Njirimara: ya na mmanụ FR3

Na-enye ọganihu ike site na iji otu -osisi phase{1}} n'agbanyeghi ihe ngbanwe -nkenke, ntụkwasị obi, na ihe ọhụrụ jikọtara ọnụ.
01 Izugbe
1.1 Ihe ndabere oru ngo
Nke a 50kVA otu akụkụ okporo osisi mounted transformer na-exporting na Canada na July, 2024. The gosiri ike nke okporo osisi mounted transformer bụ 50 kVA, isi voltaji bụ 34.5 kV na nke abụọ voltaji bụ 0.48y/0.277 kV. Mba ndị mepere emepe na Ndịda Ebe Ọwụwa Anyanwụ Eshia, North na South America, ọnụ ọgụgụ buru ibu nke otu {{7} pole nke etinyere ihe ngbanwe dị ka ihe nkesa nkesa. Na netwọk nkesa nwere ọkụ ọkụ ekesa, otu - transformers nwere nnukwu uru dị ka nkesa nkesa. Ọ nwere ike ibelata ahịrị nkesa voltaji dị ala{11}, belata mfu ahịrị, melite ogo ọkọnọ ike, iji ike -Oru oma coil core structure design, the transformer e ji ojiji nke kọlụm mounted nkwusioru nrụnye, obere size, obere akụrụngwa ego, belata ala -voltaji ike ọkọnọ radius, nwere ike ibelata obere obere {10} akara. Ihe ngbanwe ahụ na-anakwere ihe owuwu kpuchiri ekpuchi nke ọma, ikike ibu ibu siri ike, ntụkwasị obi dị elu na arụ ọrụ na-aga n'ihu, mmezi dị mfe na ogologo ndụ ọrụ.
Otu {{0}pole mounted transformers dabara adaba maka grids ọkụ ime obodo, mpaghara ndị dịpụrụ adịpụ, obodo ndị gbasasịrị agbasa, mmepụta ugbo, ọkụ na oriri ọkụ, ma enwere ike iji ya mee ike{1} na-echekwa mgbanwe nke ahịrị nkesa kọlụm n'okporo ụzọ ụgbọ oloko na grid ike obodo.
1.2 Nkọwa nka nka
50 kVA otu ogwe osisi etinyere nkọwapụta ntụgharị na mpempe akwụkwọ data
|
Enyere ya
Canada
|
|
Afọ
2024
|
|
Nlereanya
50kVA-34.5D-0.48y/0.277kV
|
|
Ụdị
Otu akụkụ okporo osisi etinyere ngbanwe
|
|
Ọkọlọtọ
CSA C2.1-06
|
|
Enyere ike
50kVA
|
|
Ugboro ugboro
60HZ
|
|
Usoro
Naanị otu
|
|
Ụdị oyi
KNAN
|
|
Voltaji nke mbụ
34.5D kV
|
|
Voltaji nke abụọ
0.48y/0.277 kV
|
|
Ngwa ikuku
Aluminom
|
|
Polarity
Ihe mgbakwunye
|
|
Mgbochi
2.5%
|
|
Ndidi
±7.5%
|
|
Pịa Changer
NLTC
|
|
Ọkụ aka
±2*2.5%
|
|
Mmiri mmiri mmiri
FR3
|
|
Enweghị mfu ibu
0.118KW
|
|
Na Ibu Mfu
0.777KW
|
|
Ngwa ngwa
Nhazi ọkọlọtọ
|
1.3 Eserese
Ihe osise 50 kVA nke etinyere ihe ngbanwe ihe osise na nha.
![]() |
![]() |
02 Nrụpụta
2.1 Isi
Ihe bụ isi bụ nke dị elu-oyi dị mma-ọka a kpọgharịa{2}} silicon steel nwere mkpuchi ịnweta oxide, nke nwere ikike dị elu. N'okpuru otu ike ndọta, enwere ike ibunye flux ndọta nke ọma, si otú a na-emeziwanye arụmọrụ ọrụ nke transformer. Mpempe akwụkwọ sịlịkọn na-adabere na ọka nwere ike ibelata nhụsianya hysteresis site na nhazi ihe dị elu na nhazi nhazi, nke mere na ihe ngbanwe ahụ nwere ike ịnọgide na-arụ ọrụ dị elu n'okpuru ọnọdụ ibu dị elu. Site n'ịchịkwa usoro ịkpụ na nchịkọta nke mpempe akwụkwọ silicon, ọkwa mfu, ọ dịghị{7}} ibu ugbu a na mkpọtụ na-ebelata.

2.2 Ikuku

Igwe ikuku ikuku nwere ike ibelata nhụsianya dị ugbu a yana ikpo ọkụ na ikuku site na iji foils dị mkpa kama ịbụ waya okirikiri ọdịnala. Nhazi nke ikuku ikuku na-eme ka ikpochapụ ọkụ ka mma, belata ịrị elu okpomọkụ nke ikuku, ma kwalite ogologo oge - nkwụsi ike na ntụkwasị obi nke transformer. N'ihi ihe ọkụ eletrik na magnetik nke windings foil, ha na-arụ ọrụ nke ọma na ngwa ngwa dị elu, na-ebelata mfu ugboro ugboro. N'iji ya na ikuku okirikiri ọdịnala, usoro nke ikuku ikuku nwere ike ibelata mkpọtụ na ịma jijiji.
2.3 tank
Igwe na-egbutu laser dị elu na ịkụ ọkpọ CNC, mbenata, mpịaji na akụrụngwa ndị ọzọ iji hụ na nhazi ya ziri ezi, mgbe ịchachasị efere efere nchara nchara ma ọ bụ mebie ọgwụgwọ iji hụ na ịdị mma nke ịgbado ọkụ na-esote. A na-eme ịgbado ọkụ site na iji arc ịgbado ọkụ (dị ka MIG ịgbado ọkụ, TIG welding) ma ọ bụ gas na-echebe ịgbado ọkụ (GMAW), na ịgbado ọkụ usoro na-eme ka ike na tightness nke weld. Mgbe ịgbado ọkụ gwụchara, a na-enyocha weld ahụ n'anya, a na-eme nnwale na-emebi emebi (dị ka X-ray ma ọ bụ ultrasonic test) ka a na-eme ya iji gbanarị ebe mgbawa wee hụ na enweghị ntụpọ ịgbado ọkụ. Tinye ihe mkpuchi corrosion - n'ime na n'èzí tank. Ụzọ ọgwụgwọ a na-ahụkarị gụnyere ịfesa agba mgbochi - nchara ma ọ bụ ihe na-ekpo ọkụ iji mụbaa nguzogide corrosion.

2.4 Mgbakọ ikpeazụ


03 Nnwale
1. Ratio na njikọ niile wee pịa ọnọdụ
2. Nnwale polarity
3. Mba - ibu mfu na voltaji 100% agbaziri ruo ogo 85
4. Na-akpali akpali ugbu a na 100% gosiri voltaji
5. Ibu efu efu na impedance na akara ugbu a gbaziri na 85 ogo
6. Ntinye voltaji
7. Voltage na-ebute
8. Ntugharị tankị nke transformer{1}}nnwale nchọpụta.
Nsonaazụ ule
|
Mba. |
Nwale ihe |
Nkeji |
Nnabata Ụkpụrụ |
Ụkpụrụ ndị atụtara |
Mmechi |
|
1 |
Ntụle Nguzogide |
/ |
/ |
/ |
Gafe |
|
2 |
Nlele oke |
/ |
Ngbanwe nke oke voltaji na ọpịpị bụ isi: Ihe na-erughị ma ọ bụ haha 0.5% Akara njikọ: ii0 |
0.03 |
Gafe |
|
3 |
Nnwale polarity |
/ |
Ihe mgbakwunye |
Ihe mgbakwunye |
Gafe |
|
4 |
Ọ dịghị - ibu mfu na mkpali ugbu a |
% kW |
I0 : nye uru a tụrụ atụ P0: nye uru a tụrụ atụ nnabata maka enweghị ibu ibu bụ ± 15% |
0.42 0.111 |
Gafe |
|
5 |
Ngwunye ibu, voltaji impedance, mfu zuru oke na arụmọrụ |
/ kW kW |
t:85 ogo Z%: uru tụrụ Pk: uru tụrụ Pt: uru tụrụ nnabata maka impedance bụ ± 10% nnabata maka ngụkọta ibu ọnwụ bụ ± 8% |
3.01 0.737 0.848 98.90 |
Gafe |
|
6 |
Nnwale voltaji etinyere |
/ |
HV: 70KV 60S LV: 10kV 60s |
Enweghị ọdịda nke voltaji ule a na-eme |
Gafe |
|
7 |
Nnwale Nkwụghachi Voltaji butere |
/ |
Voltaji etinyere (KV): 69 Ogologo oge (s): 48 Ugboro (HZ): 150 |
Enweghị ọdịda nke voltaji ule a na-eme |
Gafe |
|
8 |
Ntụle Nguzogide mkpuchi |
GΩ |
HV -LV n'ala: LV-HV gaa n'ala: HV&LV n'ala: |
18.0 8.77 8.21 |
/ |
|
9 |
Ule ntapu |
/ |
Ntinye nrụgide: 20kPA Ogologo oge: 12h |
Enweghị ntapu na mba Mmebi |
Gafe |
|
10 |
Nnwale mmanụ |
kV, mg/kg, %, mg/kg, |
Ike Dielectric; Ọdịnaya Ọdịnaya; Ihe nbipu; Nyocha nke Furan; Nyocha chromatography gas |
56.37 9.7 0.00341 0.03 / |
Gafe |


04 Mbukota na mbupu


05 Saịtị na nchịkọta
A na-eji otu {{0}Pasese{{1} transformer, nwere ọmarịcha ịrụ ọrụ ya, ịdị mma a pụrụ ịdabere na ya, yana nrụnye ọ bụla, na netwọkụ nkesa ike obodo yana ime obodo yana ọnọdụ ụlọ ọrụ dị iche iche. Ọ bụghị naanị na ọ na-akwalite arụmọrụ arụmọrụ nke sistemu ike mana ọ na-enyekwa ndị ọrụ ahụmịhe ọkụ eletrik kwụsiri ike na nchekwa. Anyị na-agba mbọ ịnye ngwaahịa na ọrụ ndị ọkachamara{{4} dị elu, na-arụkọ ọrụ aka na gị iji wuo ọdịnihu ike dị mma na nke ọma!