2500 kVA ntụgharị-0.6 / 13.8 kV|USA 2025
Ike: 2500 kVA
Voltaji: 13.8GrdY/7.97-0.6Y/0.346kV
Njirimara: ya na ihuenyo mwepu dịpụrụ adịpụ

Ike anaghị ahụ anya, Nchekwa enweghị atụ: Ngwọta Ntugharị anyị -Edokwasịrị.
01 Izugbe
1.1 Nkọwa oru ngo
2500 kVA three phase pad mounted transformer e zigara Canada na 2025. Ike nke transformer bụ 2500 kVA na KNAN jụrụ oyi. The elu voltaji bụ 13.8GRDY / 7.97 kV na ± 2 * 2.5% tapping nso (NLTC), ala voltaji bụ 0.6Y / 0,346 kV, ha guzobere a vector otu YNyn0.
Obi dị anyị ụtọ iwebata ihe nrụnye 2500kVA{1} nke a na-agbanye mgbanaka, nke na-ejikọta arụmọrụ dị elu, ntụkwasị obi na nkwado gburugburu ebe obibi, na-eme ka ọ dabara maka nkesa ike obodo, azụmahịa na ngwa mmepụta ihe. Ngwaahịa a na-agbaso ụkpụrụ nrụpụta ike ike DOE 2016, na-enweta ọmarịcha arụmọrụ ruru 99.53%. Ọ na-eji mmanụ mkpuchi FR3® eke ester na-ahụ maka gburugburu ebe obibi, na-enye nchekwa nchekwa ọkụ dị elu (klas K4) na biodegradability. Nrụmọrụ ọkụ ya kacha mma yana njikwa ịrị elu okpomọkụ na-eme ka ọrụ kwụsie ike ogologo oge.
N'akụkụ voltaji dị elu{{0}, ọ nwere plọg 600A agbakwunyere{2} na bushes, nwere ihe mgbochi poselin na-anọpụ iche yana agbakwunyere ụdị mmanya ọla kọpa abụọ{3}}oghere-, na-enye njikọ echekwabara na ntụkwasị obi. Akụkụ dị ala{6} voltaji nwere resin{7}} nkedo nkedo na oghere ọla kọpa iri dị ugbu a, na-eme ka owuwu siri ike na nrụnye dị mfe. Akụkụ dị ọhụrụ{11}}ichepụta ụzọ ọpụpụ na-echekwa ohere wee bịa zuru oke na njikọ mmanya ọla kọpa na mkpuchi nchebe, na-ahụ na nchekwa ọrụ. Na mgbakwunye, a na-etinye ohia ala abụọ maka ihuenyo mgbado n'etiti elu na obere voltaji yana maka ntinye ala na-anọpụ iche, na-enye atụmatụ zuru oke iji gboo ihe dị iche iche chọrọ.
Mkpọchi ahụ jikọtara igwe ọkụ ọkụ abụọ{{0} ọnọdụ ọnọdụ, ihe njide atọ, sistemu ọta na-akụda ala, yana sistemu mgbochi nitrogen, na-ebuga nchekwa zuru oke yana ọrụ mgbanwe. Ngalaba a bụ nhọrọ dị mma maka iwu grid ike ọgbara ọhụrụ, na-enye arụmọrụ dị elu, nchekwa na ntụkwasị obi.
1.2 Nkọwa nka nka
2500 kVA mpe mpe akwa n'ịnyịnya mgbanwe ụdị nkọwapụta na mpempe akwụkwọ data
|
Enyere ya
USA
|
|
Afọ
2025
|
|
Ụdị
Ihe mgbakwasa na mpe mpe akwa
|
|
Ọkọlọtọ
IEEE C57.12.34
|
|
Enyere ike
2500 kVA
|
|
Ugboro ugboro
60HZ
|
|
Usoro
3
|
|
Nri
Loop
|
|
N'ihu
Nwụrụ anwụ
|
|
Ụdị oyi
KNAN
|
|
Voltaji nke mbụ
13.8GDY/7.97kV
|
|
Voltaji nke abụọ
0.6Y/0.346 kV
|
|
Ngwa ikuku
Aluminom
|
|
Ntugharị akụkụ
YNyn0
|
|
Mgbochi
5.75%
|
|
Pịa Changer
NLTC
|
|
Ọkụ aka
±2*2.5%
|
|
Enweghị mfu ibu
2.4 kW
|
|
Na Ọnwụ Ebu
15.79 kW
|
1.3 Eserese
2500 kVA mpe mpe akwa akwadoro eserese eserese na nha.
![]() |
![]() |
02 Nrụpụta
2.1 Isi
Mpempe mpe mpe akwa 2500kVA{1} agbakwunyere igwe nrụnye nwere oghere atọ -fase ise-nke arụrụ site na nnukwu oyi{4}}ụyi dị elu-ọka akpọre akpọre -ọkpụkpụ silicon steel lamination. Nhazi ụkwụ ise - na-ebelata nke ọma enweghị mmasị na enweghị mfu -, ebe ọ na-ebelata nrịba mmiri magnetik na ọdịnaya kwekọrọ na isi. Akụkụ akụkụ abụọ ahụ agbakwunyere na-arụ ọrụ dị ka ụzọ nkwụsịtụ dị ala{12} nke atọ -harmonic flux, si otú ahụ na-ebelata mgbagha voltaji waveform na hụ na mmepụta ike dị elu{13}. Isi ihe na-egosipụta ọmarịcha magnetik na nkwụsi ike nke igwe, nwere ike iguzogide mmetụta mkpirisi mkpirisi na ibelata mkpọtụ arụ ọrụ. Nhazi a siri ike na-enye ntọala siri ike maka ọrụ mgbanaka na-arụ ọrụ nke ọma, dị nro na nke dị ala{17}}.

2.2 Ikuku

Igwe ọkụ eletrik dị ala - na-anabata usoro ikuku foil, na foil nwere ezigbo ọkụ eletrik, nke nwere ike melite arụmọrụ nnyefe ugbu a; elu - voltaji winding nwere waya - ọnya Ọdịdị, nke nwere ike izute chọrọ nke elu - voltaji nnyefe ọkụ. A na-edozi akụkụ elu na nke dị ala nke winding ma na-ejikọta ya na efere ígwè. Site na nkwụsi ike nke efere ígwè, a na-ahụ na ikuku na-eme ka ọ dịgidere ọdịdị na nhazi n'oge nhazi na ojiji ọzọ. Mgbe emechara, enwere ike iwepụ efere ígwè ahụ, nke mere na ikuku na-egbo mkpa mgbakọ niile nke onye na-agbanwe agbanwe ma na-eme ka ọrụ eletrik na nkwụsi ike nke ígwè ọrụ nke onye na-agbanwe agbanwe.
2.3 tank
A na-arụ tankị ahụ site na corrosion{0}} nchara na-eguzogide ma nwee mmechi nke ọma, dị ala{1}profaịlụ. Emechara ya na Green Equipment (Munsell 9 GY 1.5/2.6), ọ na-enye ogologo oge na nchebe corrosion. Juputara na mmiri ester eke eke FR3® maka nkwalite nju oyi yana nchekwa ọkụ, tankị ahụ na-enweta ihicha siri ike{8}}Nnwale akaebe iji hụ na ntụkwasị obi ogologo oge- na gburugburu ebe chọrọ.

2.4 Mgbakọ ikpeazụ

Mgbakọ ikpeazụ nke mpe mpe akwa a{0} agbakwunyere ngbanwe na-amalite site na mgbakọ nke akụkụ nọ n'ọrụ: a na-etinye windings nke ọma na kọlụm ndị dị na ya, na-esote ntinye nke yoke n'elu iji mechaa sekit magnetik. A na-etinyezi ihe enyemaka niile, gụnyere bushes, ndị na-agbanwe mgbata na ngwaọrụ nchekwa ma jikọọ ya na nchekwa. N'ikpeazụ, a na-eji nlezianya jupụta tank ahụ na FR3® eke ester insulating mmiri n'okpuru ọnọdụ oghere a na-achịkwa iji hụ na impregnation zuru oke na mkpochapụ nke ikuku, na-ekwe nkwa mkpuchi ọkụ eletrik kachasị mma na arụmọrụ ọkụ n'oge ndụ ya niile.
03 Nnwale
|
Mba. |
Nwale ihe |
Nkeji |
Ụkpụrụ nnabata |
Ụkpụrụ ndị atụtara |
Mmechi |
|
1 |
Ntụle Nguzogide |
% |
Ọnụego enweghị nguzozi kacha nguzogide |
4.05 |
Gafe |
|
2 |
Nlele oke |
% |
Ngbanwe nke oke voltaji na ọpịpị bụ isi: Ihe na-erughị ma ọ bụ haha 0.5% Akara njikọ: YNyn0 |
-0.03% ~- 0.02% |
Gafe |
|
3 |
nkeji -nnwale mmekọ |
/ |
YNyn0 |
YNyn0 |
Gafe |
|
4 |
Ọ dịghị - ibu mfu na mkpali ugbu a |
/ |
I0 :: nye uru a tụrụ atụ |
0.22% |
Gafe |
|
P0: nye uru a tụrụ atụ (t:20 degrees) |
2.192kW |
||||
|
nnabata maka enweghị ibu ibu bụ +10% |
/ |
||||
|
5 |
Ibu na-efunahụ voltaji impedance na arụmọrụ |
/ |
t:85 ogo nnabata maka impedance bụ ± 7.5% Nkwenye maka mkpokọta mfu ibu bụ +6% |
/ |
Gafe 合格 |
|
Z%: uru tụrụ |
5.70% |
||||
|
Pk: uru tụrụ |
15.158 kW |
||||
|
Pt: uru tụrụ |
17.350 kW |
||||
|
Ịrụ ọrụ adịghị erughị 99.53% |
99.55% |
||||
|
6 |
Nnwale voltaji etinyere |
kV |
LV/ 低压: 10kV 60s |
Enweghị ọdịda nke voltaji ule a na-eme |
Gafe |
|
7 |
Nnwale Nkwụghachi Voltaji butere |
kV |
Voltaji etinyere (KV):2Ur |
Enweghị ọdịda nke voltaji ule a na-eme |
Gafe |
|
Ogologo oge (s):48 |
|||||
|
Ugboro (HZ): 150 |
|||||
|
8 |
Ule ntapu |
kPa |
Ntinye nrụgide: 50kPA |
Enweghị ntapu na mba Mmebi |
Gafe |
|
Ogologo oge: 24h |
|||||
|
9 |
Ntụle Nguzogide mkpuchi |
GΩ |
HV -LV n'ala: |
1.22 |
/ |
|
LV-HV gaa n'ala: |
1.45 |
||||
|
HV&LV ruo Ground |
0.758 |
||||
|
10 |
Nnwale mkpali ọkụ |
kV |
ife zuru oke |
Enweghị ọdịda nke voltaji ule a na-eme |
Gafe |


04 Mbukota na mbupu
4.1 mbukota
Mpempe akwụkwọ 2500kVA {{1} agbakwunyere n'elu bụ nke etinyere na nchekwa n'ime akpa e ji osisi rụọ{2}, na-eme ka nchekwa zuru oke n'oge njem na nchekwa. Agbachikwara ọgbakọ a niile n'ime nnukwu osisi siri ike nke nwere mmiri{4} ihe mgbochi na ihe mgbochi iji gbochie ikpughe iru mmiri na mmetụta anụ ahụ. A na-eji ọta nchebe raara onwe ya nye kpuchie ihe ndị dị mkpa dị ka bushes na gauges. A na-etinye ihe nkwado dị n'ime na ihe nkedo iji gbochie ngbanwe. Nkwakọ ngwaahịa ahụ kwekọrọ n'ụkpụrụ mbupu mba ofesi yana njirimara doro anya akara mpụga yana ntuziaka njikwa maka nnyefe dị mma ma dị mfe na- njirimara na ntinye saịtị.
4.2 Mbupu
A ga-ebufe ihe ngbanwe ahụ n'okpuru usoro DDU (Delivered Duty Unpaid) na ebe a na-aga. Onye na-ebubata ya na-ejikwa nhazi njem na ụgwọ niile na adreesị akọwapụtara, gụnyere usoro mbupụ na ibu ụgbọ mmiri / ala, ebe onye na-azụ ahịa na-ahụ maka mbubata mbubata, ọrụ, ụtụ isi, na mbupu ikpeazụ na ebe ọ na-aga. N'oge njem niile, a ga-enyocha mbupu ahụ iji hụ na nchekwa igwe na gburugburu ebe obibi, na mgbe ọ bịarutere, onye nnata ga-enyocha iguzosi ike n'ezi ihe nke nkwakọ ngwaahịa na akụrụngwa.
05 Saịtị na nchịkọta
Ihe ngbanwe a na-ejikọta ike dị elu, nkwado gburugburu ebe obibi, na ntụkwasị obi pụtara ìhè iji gboo ihe na-achọsi ike nke netwọk nkesa ike ọgbara ọhụrụ. Site na arụmọrụ nchekwa ọkụ pụrụ iche yana ogologo ndụ ọrụ, ọ na-eme ka ọkụ na-aga n'ihu ma kwụsie ike ma na-ebelata ụgwọ ọrụ na mmezi. Nhazi nhazi nke mmadụ na usoro nchebe jikọtara ọnụ na-eme ka ọ dị mfe nke ntinye ma belata mmetụta gburugburu ebe obibi. Anyị na-agba mbọ ịnye azịza ntụkwasị obi maka ụdị nkesa dị iche iche site na teknụzụ dị elu na nrụpụta siri ike, na-enye aka na akụrụngwa eletriki nke nwere ọgụgụ isi na nke na-agbanwe agbanwe.

Ihe nchịkọta dị ọkụ: 2500 kva transformer, emeputa, soplaya, price, efu
You Might Also Like
75 kVA 3 Phase Pad Mount Transformer-24.94 / 0.208 k...
75 kVA Pad Mount Transformer-22.86 / 0.208 kV|USA 2024
500 kVA Pad Nkwanye ebe obibi Transformer-34.5 / 0.4...
500kVA Pad Mount Transformer-14.4 / 0.208 kV|US 2025
1000 kVA Mmanụ jupụtara na mpe mpe akwa na-agbanye i...
3000 kVA Pad Nkwanye Ntugharị-25 / 0.6 kV|Canada 2025
Zipu ozi