750 KVA Pad Nkwanye Ntugharị Ntugharị Ntanetị Nri-13.2/0.48 KV|USA 2024
Ike: 750kVA
Voltaji: 13.2/0.48kV
Njirimara: Atọ - nkeji atọ - ụkwụ

Mpempe akwụkwọ Scotech{0}} ihe nrụnye nrụgharị nwere nri loop na-ebuga ike dị mma, ntụkwasị obi
01 Izugbe
1.1 Nkọwa oru ngo
Nke a750kVA atọ agba mpe mpe akwa n'ịnyịnya transformerebugara America na 2024. Emere ya n'okpuru IEEE Std C57.12.34-2022 wee zute ọkọlọtọ nrụpụta ike ike DOE 2016. Nrụ ọrụ bụ 99.4%. Ọ nwere akara akaghị aka na imewe n'ihu maka nchekwa ma dị mfe na mpaghara mmepụta ihe na azụmahịa. Ike a kwadoro bụ 750kVA, yana voltaji bụ isi nke 13.2 kV na voltaji nke abụọ nke 0.48 kV. Ihe ntụgharị bụ UL edepụtara, na-ezute ụkpụrụ nchekwa US.
Ihe mgbochi bụ 5.75%. Ọnwụ enweghị - bụ 1.05kW. Mbelata ibu bụ 5.4kW. Mfu ndị a dị ala na-azọpụta ike ma melite arụmọrụ. Onye na-agbanwe mgbata abụghị - ụdị ibu (NLTC). Ọ nwere oke ± 2 × 2.5% iji dozie voltaji.
Igwe ikuku aluminom dị ọkụ, dị ike ma dị mma maka ịnyefe ọkụ. Ọ na-eme ka transformer dị jụụ ma kwụsie ike n'okpuru ibu. Usoro jụrụ oyi nke ONAN na-eji mmanụ eke na ikuku ikuku na-achịkwa okpomọkụ.
A na-eji igwe dị nro mee tankị ahụ ma were agba mgbochi- kpuchiri ya. Ọ siri ike ma na-agbapụta{2}}àmà. Ihe owuwu nwuru anwu- na-echekwa ndị ọrụ nchekwa site na ikpuchi akụkụ ndị dị ndụ. Usoro nri loop na-enye ohere ịrụ ọrụ na-aga n'ihu mgbe otu akụkụ na-arụ ọrụ, nke na-eme ka ntụkwasị obi dị na netwọk ike.
A na-eji ihe ngbanwe a na-eme iheỤlọ ọrụ mmepụta ihenausoro nkesa ịba uru. Ọ dịkwa mma makaebe azụmahịa, data akụrụngwa, na ọdụ ụgbọ mmiri dị n'èzí. Ọ na-enye ike kwụsiri ike na nke ọma ebe ntụkwasị obi na nchekwa dị mkpa.
1.2 Nkọwa nka nka
Mpempe akwụkwọ 750 kVA etinyere ihe ntụgharị ntụgharị na mpempe akwụkwọ data
|
Enyere ya
America
|
|
Afọ
2024
|
|
Ụdị
Atọ nke mpe mpe akwa ugwu transformer
|
|
Ọkọlọtọ
IEEE Std C57.12.34-2022
|
|
Enyere ike
750KVA
|
|
Ugboro ugboro
60HZ
|
|
Nri
Loop
|
|
N'ihu
Nwụrụ anwụ
|
|
Usoro
Atọ
|
|
Ụdị oyi
ONAN
|
|
Mmiri mkpuchi
Mineral Mmanụ
|
|
Voltaji nke mbụ
13.2 kV
|
|
Voltaji nke abụọ
0,48 kV
|
|
Otu Vector
Dyn1
|
|
Ngwa ikuku
Aluminom
|
|
Mgbochi
5.75%
|
|
Ịrụ ọrụ na mfu Ọkọlọtọ
DOE 2016, 99.4%
|
|
Pịa Changer
NLTC
|
|
Ọkụ aka
±2*2.5%
|
|
Enweghị mfu ibu
1.05 kV
|
|
Na Ibu Mfu
5,4 kV
|
|
Ngwa ngwa
Nhazi ọkọlọtọ
|
1.3 Eserese
Mpempe akwụkwọ 750 kVA etinyere ihe nrịbama loop ndepụta eserese na efere aha
![]() |
![]() |
02 Nrụpụta
2.1 Isi
Ihe mgbakwasa nke 750kVA loop feed pad na-anakwere atụmatụ isi ihe atọ{1} silicon steel , kachasị maka ikike dị elu yana njupụta ndọta dị ala. Usoro - nhazi isi ụkwụ na-ebelata mfu na mkpọtụ na-akpafu ma na-ejigide arụmọrụ dị mma yana nguzosi ike magnetik, dị mma maka netwọk ike mmepụta ihe dị arọ-.
2.2 Ikuku
Mpempe mpe mpe akwa 750 kVA nke etinyere ihe ntụgharị ntụgharị na-eji igwe ikuku aluminom dị elu{1} nwere mkpuchi interlayer siri ike yana njedebe gbasiri ike{2}} ụlọ mgbochi. Nhazi ahụ na-egbochi nrụgide electromechanical n'okpuru ọnọdụ mkpirisi -. ihicha oghere dị elu yana impregnation varnish na-ahụ na iguzosi ike n'ezi ihe mkpuchi na ogologo ndụ ọrụ na nnukwu ọrụ-.
2.3 tank

A na-eji ígwè dị nro mee tank mmanụ ahụ. O nwere ihe eji ekpuchi ya na mkpuchi mkpuchi. Ihe owuwu a na-enye nkwado siri ike ma gbochie nsị mmanụ. Usoro nju oyi nke ONAN na-eji mmanu mmanu ewepu okpomoku. Ọ na-eme ka transformer dị jụụ ọbụna mgbe ibu dị elu. A na-eji ihe mgbochi- na-eji ihe mgbochi agwọ elu ala niile, na-agbatị ndụ ọrụ n'ọnọdụ dị n'èzí siri ike.
2.4 Mgbakọ ikpeazụ
A na-ehicha isi na coils, na-enyocha, ma kwado ya nke ọma, na-akwado ikuku aluminom ma kpọchie ya maka nkwụsi ike. N'oge ịkwọ ụgbọ mmiri, a na-agbada akụkụ ahụ na-arụ ọrụ n'ime tank dị ọcha, gbanye ya nke ọma, ma chekwaa ya na nkwado mkpuchi.
Ngwa ndị dị ka elu- na obere{1} voltaji bushings, radiators, mgbali enyemaka valve, ebuli lugs na mgbanyụ-circuit tap mgbanwe na-arụnyere na akara. Ngwa ndị agbakwunyere gụnyere fuse bayonet nwere CLFs, mgba ọkụ 2- LBOR, ihe nlele ọkwa mmiri, ihe nrụgide ikuku, temometa ụdị ọkpụkpọ, na drain na valvụ nlele maka ọrụ nchekwa yana nleba anya dabara adaba.
Ngwa ahụ nwere oghere- juputara na mmanụ ịnweta, na-ahụ na akara nke ọma na ọkwa mmanụ. Nnwale eletriki dị ka nguzogide, oke, mmekọrita oge, mfu, voltaji na-eguzogide, mkpuchi, ntanye, na ule mmanụ dielectric na-eme ka arụmọrụ a pụrụ ịdabere na ya na nrube isi n'ụkpụrụ imewe.
N'ikpeazụ, a na-ehicha ihe dị n'èzí, kpuchie ya ma nyochaa ya. Ekwenyere data efere aha, akara njedebe, na eserese wiring maka izi ezi tupu nkwakọ na nnyefe.

03 Nnwale
Ọkọlọtọ nnwale
|
IEEE C57.12.00-2021 |
Ụkpụrụ IEEE maka ihe ndị achọrọ maka Liquid{0}} Nkesa, ike na nhazi mgbanwe. |
|
IEEE Std C57.12.34-2022 |
Ihe achọrọ ọkọlọtọ IEEE maka mpe mpe akwa -Edokwasịrị, ngalaba{1}}Ụdị, Onwe- jụrụ oyi, atọ-Mgbanwe nkesa nkesa, 10 MVA na obere; Elu -Voltaji, 34.5 kV Nominal System Voltage na N'okpuru; Obere-Voltaji, 15kV Nominal Sistemu Voltage na N'okpuru |
|
IEEE C57.12.90-2021 |
Koodu Ule Ọkọlọtọ IEEE maka Liquid-Nkesa, Ike, na Ngbanwe Na-ahazi |
Nnwale oge niile
1. Ntụle Nguzogide
2. Nnwale oke
3. Usoro{1}}Nnwale mmekọrịta
4. Ọ dịghị ibu efu na ọ dịghị ibu ugbu a
5. Ibu efu Impedance voltaji na arụmọrụ
6. Nnwale voltaji etinyere
7. Nleba anya na-eguzogide voltaji
8. Nnwale leak na nrụgide maka mgbanwe mgbanwe mmiri mmiri
9. Ntụle Nguzogide mkpuchi
10. Oil Dielectric Test


04 Mbukota na mbupu


05 Saịtị na nchịkọta

Ebutere nri Scotech 750kVA na-ebunye ihe ntụgharị ntụgharị na America na 2024. Nri loop ya na nke nwụrụ anwụ - n'ihu n'ihu na-enye nchekwa, mmezi dị mfe, na ọrụ na-aga n'ihu.
Ihe ngbanwe na-eji igwe silicon steel core atọ{0}} nwere obere mfu yana mkpọtụ dị ala. Igwe ikuku aluminom na-enye arụmọrụ siri ike, nnyefe ọkụ dị mma, yana ogologo ndụ ọrụ. Ọkọlọtọ na ngwa ndị agbakwunyere gụnyere bushes, valvụ enyemaka nrụgide, mgbata mgbata, fuse bayonet nwere CLFs, 2- ọnọdụ LBOR mgba ọkụ, nlele ọkwa mmiri mmiri, nlele vacuum, temometa ụdị ọkpụkpọ, na igbapu na valvụ sample.
Ihe ngbanwe ahụ bụ oghere- juputara na mmanụ ịnweta ma na-agafe ule oge niile maka nguzogide, oke, mmekọrita oge, mfu, ihe mgbochi voltaji, mkpuchi, ntapu, na arụmọrụ dielectric mmanụ. Ihe ngbanwe Scotech na-ebunye ntụkwasị obi, ike{2}arụ ọrụ nke ọma, yana ọnụ ahịa{3} ike dị irè maka netwọk nkesa usoro atọ ọgbara ọhụrụ.
Ihe nchịkọta dị ọkụ: Mpempe akwụkwọ na-ebunye ihe ntụgharị ntụgharị, onye na-emepụta ihe, onye na-ebubata, ọnụahịa, ọnụ ahịa
You Might Also Like
750 kVA Pad Nkwanye Utility Transformer-34.5 / 0.48 ...
1000 kVA Pad Nkwanye Ngbanwe Ọnụ Ahịa -13.8 / 0.415 ...
1000 kVA Nwụrụ Anwụ n'ihu Transformer-24 / 0.48 kV|U...
150 kVA Ansi Transformer-24.94 / 0.208 kV|USA 2024
1000 KVA Residential Transformer Box-22.86 / 0.208 K...
1000 KVA ntụgharị-0.6 / 13.2 KV|USA 2025
Zipu ozi