500 kVA Utility Pad Nkwanye Transformer-24 / 0.48 kV|US 2024

500 kVA Utility Pad Nkwanye Transformer-24 / 0.48 kV|US 2024

Obodo nzipu: USA 2024
Ike: 500kVA
Voltaji: 24000 D-480Y/277 V
atụmatụ:yana ndepụta{0}}site na ntinye
Zipu ozi

 

 

500 kva utility pad mounted transformer-inside-view

Ịkwado ntụkwasị obi site na nchekwa, arụmọrụ, na ịdịte aka - Scotech pad - atụkwasịrị ihe ngbanwe nke arụrụ maka ike ike taa.

 

 

01 Izugbe

1.1 Nkọwa oru ngo

Nke 500 kVA atọ -phase pad{2}} nke etinyere ngbanwe, nke ewepụtara na USA na 2024, ka arụpụtara iji zute ụkpụrụ arụmọrụ IEEE Std C57.12.34-2022 na DOE 2016.

Na-arụ ọrụ na 60 Hz, ọ na-egosipụta isi voltaji nke 24 kV na voltaji nke abụọ nke 480GrdY/277 V nwere otu Dyn1 vector. NkeUtility mpe mpe akwa n'ịnyịnya transformerna-eji windings ọla kọpa na KNAN jụrụ oyi, jupụtara na mmanụ ester eke FR3 maka nchekwa ọkụ ka mma yana nnabata gburugburu ebe obibi. Ọ gụnyere ikike nri loop, nwụrụ anwụ -ịnweta ihu, yana enweghị -mgbanwe mgbata nwere oke mgbanwe voltaji ±2 × 2.5%. Site na ihe mgbochi nke 5.75%, enweghị- ibu efu nke 0.610 kW, yana na mfu nke 4.530 kW, nkeji a na-ebuga nkesa nke ọma na ntụkwasị obi- ike voltaji. Ọ dị mma maka iji na ogige azụmahịa, obere ụlọ ọrụ mmepụta ihe, na mmepe obibi ebe achọrọ mgbanwe ike dị mma, na-agbanwe agbanwe na nke ọma.

 

 

 

1.2 Nkọwa nka nka

500kVA utility mpe mpe akwa n'ịnyịnya ntụgharị nkọwapụta na mpempe akwụkwọ data

Enyere ya
USA
Afọ
2024
Ụdị
Atọ nke mpe mpe akwa ugwu transformer
Ọkọlọtọ
IEEE Std C57.12.34-2022
Enyere ike
500 kVA
Ugboro ugboro
60HZ
Nri
Loop
N'ihu
Nwụrụ anwụ
Usoro
Atọ
Ụdị oyi
KNAN
Ihe mgbochi mmiri
Mmanụ FR3
Voltaji nke mbụ
24 kV
Voltaji nke abụọ
0,48 kV
Otu Vector
Dyn1
Ngwa ikuku
Ọla kọpa
Mgbochi
5.75%
Standardkpụrụ arụmọrụ na mfu
DOE 2016
Pịa Changer
NLTC
Ọkụ aka
±2*2.5%
Enweghị mfu ibu
0,610 kW
Na Ibu Mfu
4.530 kW
Ngwa ngwa
Nhazi ọkọlọtọ

 

 

1.3 Eserese

500kVA utility mpe mpe akwa n'ịnyịnya transformer eserese na aha aha

500 kva utility pad mounted transformer-outline-drawing 500 kva utility pad mounted transformer-nameplate

 

 

02 Nrụpụta

2.1 Isi

A na-eme cores transformer SCOTECH site na oyi na-atụ dị elu{0}}ọkwa e webatara -ọkpụkpọ silicon steel. N'iji n'ime- ahịrị ịkpachapụta nke ọma n'ụlọ, a na-achịkwa burrs n'okpuru 0.02 mm. Ihe cores ndị ahụ na-egosipụta nkwonkwo mitered zuru oke na-enweghị ntụmadị ma ọ bụ yoke ekpokọtara ọnụ, na-eme ka arụmọrụ magnetik na-ebelata ike mfu.

500 kva utility pad mounted transformer-steel-core

 

2.2 Ikuku

500 kva utility pad mounted transformer-copper-foil-windings

Nke a 500 kVA ngbanwe nwere ọla kọpa ma ọ bụ aluminom ikuku windings n'akụkụ LV, na-enye ọbụna nkesa ugbu a na ike dị mkpụmkpụ - mgbochi okirikiri. Akụkụ HV na-eji enamel{3}}waya kpuchiri ekpuchi n'ụdị nhazi ọtụtụ{4}, na-enye mkpuchi siri ike yana ịrụ ọrụ kwụsiri ike na 24 kV.

 

2.3 tank

Tank nke na-agbanwe agbanwe bụ ihe owuwu nchara mechiri emechi nke nwere isi, windings, na mmanụ mkpuchi. Ezubere maka ike na ịdịte aka, ọ na-echebe ihe ndị dị n'ime ya site na mmiri mmiri, ihe ndị na-emerụ emerụ, na mmebi ngwaọrụ, na-eme ka ọrụ nchekwa na ogologo ndụ ọrụ.

500 kva utility pad mounted transformer-sealed steel transformer tank

 

2.4 Mgbakọ ikpeazụ

500 kva utility pad mounted transformer-front-door-open

Scotech na-emetụta mkpuchi dị elu{0}} n'elu ihe ngbanwe niile. Mgbe echichi na ihichachara, a ga-emetụ ncha ma ọ bụ mebie mmebi ọ bụla site na iji agba nchebe dabara na Scotech nyere ma ọ bụ kọwaa ya, na-ejigide ma nguzogide corrosion na ịdị mma.

 

 

03 Nnwale

Nnwale oge na ụkpụrụ nnwale

1. Ntụle Nguzogide dịka IEEE C57.12.90-2021 Nkeji edemede 5 siri dị.

2. Usoro{1}}Nnwale mmekọrịta dịka IEEE C57.12.90-2021 Nkeji edemede 6 siri dị.

3. Nnwale oke dịka IEEE C57.12.90-2021 Nkeji edemede 7 siri dị.

4. Enweghị mfu ibu na enweghị ibu dị ugbu a dịka IEEE C57.12.90-2021 Nkeji edemede 8

5. Ntufu ibu, Voltaji impedance na arụmọrụ dị ka IEEE C57.12.90-2021 Nkeji edemede 9 si dị.

6. Nnwale Nkwụghachi voltaji dị ka IEEE C57.12.90-2021 Nkeji edemede 10.5.1 siri dị.

7. Nnwale voltaji etinyere dịka IEEE C57.12.90-2021 Nkeji edemede 10.6 siri dị.

8. Nnwale ntanye na nrụgide maka ndị na-eme mgbanwe mmiri mmiri - a ga-eme ule ntapu na 15 kPa maka awa 12 na-enweghị ntapu. Enweghị nrụrụ na-adịgide adịgide.

9. Ntụle Nguzogide mkpuchi

10. Oil Dielectric Test

500 kva utility pad mounted transformer-load losses tests
500 kva utility pad mounted transformer-electrical-test

 

Nsonaazụ ule

Mba.

Nwale ihe

Nkeji

Ụkpụrụ nnabata

Ụkpụrụ ndị atụtara

Mmechi

1

Ntụle Nguzogide

%

Ọnụego enweghị nguzozi kacha nguzogide

0.171

Gafe

2

Nlele oke

%

Ngbanwe nke oke voltaji na ọpịpị bụ isi: Ihe na-erughị ma ọ bụ haha ​​0.5%

Akara njikọ: Dyn1

0.03% ~ 0.05%

Gafe

3

nkeji -nnwale mmekọ

/

Dyn1

Dyn1

Gafe

4

Ọ dịghị - ibu mfu na mkpali ugbu a

%

kW

I0 :: nye uru a tụrụ atụ

P0: nye uru a tụrụ atụ

Nkwenye maka enweghị ibu ibu bụ +0%

0.13%

0.544

Gafe

5

Ibu na-efunahụ voltaji impedance na arụmọrụ

%

kW

kW

t:85 ogo

Z%: uru tụrụ

Pk: uru tụrụ

Pt: uru tụrụ

Nkwenye maka impedance bụ ± 7.5%

Nkwenye maka mkpokọta mfu ibu bụ +0%

Ịrụ ọrụ adịghị erughị 99.35%

5.70%

4.453

4.997

99.38%

Gafe

6

Nnwale voltaji etinyere

kV

HV: 40kV 60s

LV: 10kV 60s

Enweghị ọdịda nke voltaji ule a na-eme

Gafe

7

Nnwale Iguzogide Voltaji butere

kV

Voltaji etinyere (KV):

0.960

Ogologo oge (s):40

Ugboro (HZ): 180

Enweghị ọdịda nke voltaji ule a na-eme

Gafe

8

Ule ntapu

kPa

Ntinye nrụgide: 15kPA

Ogologo oge: 12h

Enweghị ntapu na mba

Mmebi

Gafe

9

Ntụle Nguzogide mkpuchi

HV -LV n'ala:

LV-HV gaa n'ala:

HV&LV n'ala:

5.11

4.87

5.08

/

10

Nnwale Dielectric mmanụ

kV

Karịrị ma ọ bụ ha nhata 40

52.3

Gafe

 

 

04 Mbukota na mbupu

utility pad mounted transformer packing utility pad mounted transformer shipping
 
 

05 Saịtị na nchịkọta

Scotech's 500 kVA atọ -mkpụrụ osisi - agbakwunyere ngbanwewuru ya na windings ọla kọpa na KNAN jụrụ oyi, transformer na-eji mmanụ ester eke FR3{1} na-emeziwanye nchekwa ọkụ na ibelata mmetụta gburugburu ebe obibi. Nhazi ya{3}} nhazi nri na anwụ anwụ- imewe ihu na-akwalite nchekwa na mgbanwe maka nrụnye na mmezi. Site na nkwụsị nke 5.75% na mfu ume dị ala, ọ na-eme ka ọ kwụsie ike, ịrụ ọrụ nke ọma n'ofe ọnọdụ chọrọ.

A na-anakọta ihe ntụgharị Scotech ọ bụla site na nlekọta na elu{0}} maka ịdịte aka. A na-enye ihe mmetụ aka na-adakọ - agba elu iji kwado ma nguzogide corrosion yana ngbanwe anya ka emechara.

Site na nlebara anya siri ike na ịdịmma na ịba uru{0}}ọkwa ọkwa, Scotech na-aga n'ihu na-ebunye pad a pụrụ ịdabere na ya{1}} n'agbanyeghi igwe ngbanwe maka sistemu ike ọgbara ọhụrụ n'ofe North America na gafee.

500 kva utility pad mounted transformer-front-view

 

Ihe nchịkọta dị ọkụ: Utility mpe mpe akwa arịọnụ transformer, nrụpụta, soplaya, price, efu

Zipu ozi