Power Transformer Installation and Operation Guide

 

 

 

1. Oke na ebumnuche

 

 

Ntuziaka a na-eje ozi dị ka akwụkwọ teknuzu zuru oke maka njem, nrụnye, nnabata, na ọrụ mbido mmanụ{0}} ihe ntụgharị ike imikpu. Ọ na-ekpuchi usoro ndụ zuru oke site na nnyefe ụlọ ọrụ ruo n'ịrụ ọrụ nke ọma, na-agụnye ma ndị nrụpụta{2} kpọmkwem chọrọ yana ụkpụrụ ụlọ ọrụ ọdabara. Ezubere akwụkwọ a maka ndị na-arụ ọrụ nrụnye, ndị injinia na-enye ọrụ, na ndị na-arụ ọrụ ọdụ ụgbọ mmiri na-etinye aka na ọrụ mgbanwe ọkụ.

Ụkpụrụ ndị dị:

  • GB 50148 -2010: Koodu maka iwu ụlọ na nnabata nke ndị na-agbanwe ike, igwe na-eme mmanụ, na mgbanwe ngwa.
  • GB 50150 -2016: Ọkọlọtọ maka Nnwale Aka Nleta nke Ngwa Eletriki
  • DL/T 572-95: Koodu ọrụ ntụgharị ike
  • GB 26860 -2011: Koodu nchekwa maka ụlọ ọrụ ọkụ eletrik - akụkụ nke osisi ọkụ na ọdụ ụgbọ mmiri.
  • GB/T 6451 -2015: Nka nka na ihe achọrọ maka ndị ngbanwe ike imikpu mmanụ

Maka ndị ntụgharị nke 110kV na karịa, a ga-enyocha ndekọ nyocha ụlọ ọrụ mmepụta ihe, ntuziaka ọrụ na akwụkwọ ọrụ aka ndị ọzọ dị ka akụkụ nke ebe nchekwa ọrụ.

 


 

 

 

2. Ụgbọ njem nke Transformer Main Isi

 

 

2.1 chọrọ ebuli

Mgbe ị na-ebuli isi ahụ, a ga-ebuli ụda niile na-ebuli elu na tankị n'otu oge. Akụkụ dị n'etiti eriri ọ bụla na-ebuli elu na perpendicular ga-abụ ihe na-erughị ma ọ bụ hà nhata na ogo 30. Ebe etiti ike ndọda ngwaahịa a ga-adakọrịrị na ebe a na-ebufe ụgbọ ala iji hụ na nkwụsi ike n'oge njem.

Transformer Main Body lifting
Transformer Main Isi ebuli
lifting the main body of power transformer
na-ebuli isi ahụ nke transformer ike

2.2 Ọnọdụ Ụgbọ njem okporo ụzọ

Ndị na-ewu ụlọ ga-achọpụta na ụzọ si n'okporo ụzọ ọha na eze na-aga ebe a na-etinye ya na-adaba adaba maka njem ntụgharị. A ghaghị imezu ọnọdụ ndị a:

  • Obosara okporo ụzọ kwụ ọtọ: Karịrị ma ọ bụ nhata na 3.5m
  • Obosara okporo ụzọ gbagọrọ agbagọ: Karịrị ma ọ bụ haha ​​na 18m
  • Mwepu ahịrị n'elu: Karịrị ma ọ bụ hà nhata 4.6m
  • gradient okporo ụzọ: Ihe na-erughị ma ọ bụ haha ​​na ogo 15
  • Elu okporo ụzọ ga-adị larịị n'enweghị mkpọda kwụ ọtọ
  • Ụzọ ga-enwerịrị ike ibu mkpokọta ibu njem.

2.3 Oke mmasị na ọsọ

N'oge njem okporo ụzọ ma ọ bụ njikwa akwụkwọ ntuziaka, akụkụ echiche nke axis vetikal Ihe na-erughị ma ọ bụ ha nhata ogo 15, na axis kwụ ọtọ Ihe na-erughị ma ọ bụ hà nhata na ogo 10. Ọsọ njikwa aka na-erughị ma ọ bụ ha nhata 5m/min, yana ọsọ ndọta ụgbọ okporo ígwè na-erughị ma ọ bụ ha nhata 5m/min. A ga-ewepụrịrị ngwaọrụ breeki tupu adọba ya n'ụgbọ okporo ígwè, na wiil agbakasịkwara mmanụ nke ọma.

Road Transport
Ụgbọ njem okporo ụzọ
Transformer Transportation
Ụgbọ njem transformer

2.4 Nitrogen - juru na mmanụ - Ụgbọ njem juru

Nitrogen -ebufe juputara:igirigi Nitrogen - akara <-40 ogo , nitrogen dị ọcha Karịrị ma ọ bụ ha nhata 99.9%, nrụgide tank dị n'ime Karịrị ma ọ bụ ha nhata 30kPa. N'oge njem, nrụgide tank ga-anọgide na-adị mma ma na-achịkwa ya karịa 10kPa na okpomọkụ nkịtị; a chọrọ imeju ya na gas tozuru oke ma ọ bụrụ na nrụgide daa.

Ụgbọ njem mmanụ - juru:Jupụta mmanụ tozuru etozu nke otu ika ahụ akọwapụtara na eserese ndepụta ahụ, na-edobe ahịrị mmanụ ihe dịka 100mm n'okpuru tank. A ghaghị iji efere kpuo ìsì mechie valvụ niile; Amachibidoro ntapu mmanụ nke ọma.

Achọrọ ihe ndekọ 2.5 mmetụta

Maka ndị na-agbanwe agbanwe nwere ihe ndekọ mmetụta, a ga-edekọ ọnụ ahịa osooso g: ọnụ ahịa kwụ ọtọ kachasị ukwuu agaghị agafe 4g, na ntụziaka ndị ọzọ agaghị agafe 3g. A ga-edobe akwụkwọ ndekọ ahụ n'ime ebe nchekwa onye ọrụ mgbe ndị otu abụọ bịanyere aka na ya wee kwado ya.

 

 


 

 

 

3. Nbudata na ọnọdụ

 

 

3.1 Nkwadebe saịtị

Tupu ụgbọ njem ahụ erute n'elu ikpo okwu, a ga-enyocha ike ibu ala. A ga-ewere usoro ndị dị mkpa iji gbochie nlegharị anya karịrị akarị mgbe a na-ebutu ya.

3.2 Na-ebuli maka nbudata

A ga-ejikọta ụdọ ebuli elu na ogwe aka ebuli elu maka ahụ dum; A machibidoro iwu ike ijikọ na akpa tankị. Ọ bụrụ na akụkụ ebuli elu gafere ogo 30, a ga-eji ọkụ na-ebuli elu mee ihe iji hụ na nchekwa. Ọ bụrụ na ị na-ebutu ya site na iji aka, jiri efere jakị na tankị, hụ na ala jakị ọ bụla na-enweta ike nha anya, wee welie ya n'otu oge.

3.3 Ọnọdụ

A ga-achịkwakwa ọsọ ọsọ na-aga n'ihu nke isi, ebe ịdị elu nke ọ bụla na-erughị ma ọ bụ hà nhata 30mm. Enwere 1.5% gradient chọrọ maka ọkpọkọ njikọ elu nke ihe ntụgharị; ọ dịghị shimming dị mkpa n'akụkụ conservator mgbe n'ọkwa.

Maka igwe mgbanaka- nwere ihe ngbanwe, chọpụta na oghere ndị ahụ dabara adaba na oghere nke epekele ndị etinyere n'okpuru tankị. Lelee oghere wheel megide oghere ụgbọ okporo ígwè tupu echichi, wee mezue ngwaọrụ breeki.

The transformer is unloaded to the installation site
A na-ebutu ihe ngbanwe ahụ na saịtị nrụnye
Transformer is arriving the positioning platform
Transformer na-abata n'elu ikpo okwu

 

 


 

 

 

4. Nyocha na nnabata mgbe ọ bịarutere

 

 

4.1 Nyocha nke Isi na Ngwa

Mgbe ị bịarutere, ụlọ ọrụ ntinye na onye ọrụ ga-enyocha isi ahụ na ngwa maka:

  • Nyocha nkọwapụta:Lelee nkọwapụta nke efere aha, ụdị, yana ọnụọgụ megide ihe achọrọ ịzụrụ.
  • Ọnọdụ anụ ahụ:Lelee maka mmebi, nrụrụ, mgbawa, ma ọ bụ mbugharị n'etiti gwongworo na transformer.
  • Ọnụọgụ ngwa:Nyochaa ngwungwu na ngwa ndị megidere ndepụta mbufe na ndepụta nkwakọ ngwaahịa, gụnyere temometa, bushes na ihe ndị ọzọ.
  • Akụkụ mapụtara:Lelee akụkụ mapụtara na ngwa ngwa megide ihe nkwekọrịta chọrọ.

A ga-edekọ mmebi ma ọ bụ adịghị ahụkebe ọ bụla na foto saịtị na{{0}. Nye foto, ndetu ntụpọ, na dekọọ ndị nrụpụta na ụlọ ọrụ ụgbọ njem ozugbo maka nyocha ihe kpatara yana mkpebi oge.

4.2 nnabata mmanụ mkpuchi

Nlele anya nke mmanụ mkpuchi mgbe ị bịarutere iji lelee maka ịgwakọta ihe ndị mba ọzọ. Nsonaazụ ule ga-enwerịrị:

  • Voltage mmebi: Karịrị ma ọ bụ hà 40kV / 2.5mm
  • Ọdịnaya mmiri: Ihe na-erughị ma ọ bụ hà nhata 20ppm

A ga-edokwa ụdị mmanụ transformer dị iche iche ma debe ya iche.

Transformer oil
Mmanụ ntụgharị
Isolation oil
Mmanụ iche

 

 


 

 

 

 

5. Nchekwa nke ngwaahịa na akụrụngwa

 

 

5.1 Nitrogen - Nchekwa ngwaahịa juru

Maka ngwaahịa nitrogen - juru, lelee ozugbo na nrụgide nitrogen na-emezu ihe achọrọ (Karịrị ma ọ bụ nhata 10kPa na okpomoku nkịtị). Ọ bụrụ na echekwara ya gafere ụbọchị iri na ise, a chọrọ ndochi mmanụ. Mmanụ fọdụrụnụ na tank tank ga-ezute voltaji mmebi nke ukwuu karịa ma ọ bụ hà 40kV / 2.5mm na ọdịnaya mmiri na-erughị ma ọ bụ hà nhata 20ppm.

N'oge nchekwa nitrogen - jupụtara, a ga-eme nyocha opekata mpe ugboro abụọ kwa ụbọchị, yana ndekọ nke nrụgide tank na mgbakwunye nitrogen. Ọ bụrụ na nrụgide na-ada ngwa ngwa, lelee maka ntanye wee dozie ya ozugbo iji gbochie mmiri ịbanye.

5.2 Mmanụ - Nchekwa ngwaahịa juru

Maka ngwaahịa mmanụ juru-, were ihe nlele mmanụ mgbe ị bịarutere wee nwalee. Arụmọrụ ga-ezute: voltaji mgbawa Karịrị ma ọ bụ hà 40kV/2.5mm. Ọ bụrụ na nlele mmanụ ada ada, chọpụta ma mmiri abanyela ma kpọtụrụ onye nrụpụta.

5.3 Nchekwa akụrụngwa

  • Akụkụ mwepụ (ihe nchekwa, radiator, igwe nju oyi):Chebe maka mmiri ozuzo, uzuzu na mmetọ. Ebe nchekwa ihe ga-esi ike na ihe dịka 100mm n'elu ala gbara ya gburugburu; ala kwesịrị ịdị elu ihe dịka 200mm iji gbochie nchara.
  • Bushings na ngwa (ngwa e ji atụ ihe, relays, igbe ọdụ, kabinet njikwa, na - usoro mgbanwe mgbata, eriri, akara, wdg):Chekwaa n'ime ụlọ kpọrọ nkụ, ikuku ikuku.

5.4 Mkpebi iru mmiri

A na-ewere na transformer adịghị mmiri mmiri ma ọ bụrụ na emezutere ọnọdụ ndị a (nwalere ma ọ gbachara mmanụ):

  • Uru nguzogide mkpuchi Karịrị ma ọ bụ haha ​​na 70% nke data ụlọ ọrụ
  • Isi - na{1}} nguzogide mkpuchi ala ≠0
  • Ọdịnaya mmiri dị na nitrogen erughi ma ọ bụ ha nha 100ppm
  • Ọdịnaya mmiri dị na mmanụ Ihe na-erughị ma ọ bụ hà nhata 20ppm

Ọ bụrụ na-enweghị ike imezu ihe ndị a chọrọ, a gaghị etinye ihe ngbanwe ma ọ bụ rụọ ọrụ. Kpọtụrụ onye nrụpụta maka nduzi.

 

 


 

 

 

6. Nkwadebe maka ntinye saịtị

 

 

 

6.1 Nyochaa - nwụnye

  • Nyochaa ngwa ngwa zuru oke yana ọ dị mma. Nnwale tupu - nwụnye gụnyere: ihe mgbasa mmanụ dielectric -akwụkwọ condenser bushings, polarity and ratio of bushing current transformers, nyocha na nhazigharị gas relay, na nyocha na nhazi nke onye na-ahụ maka okpomọkụ.
  • Kwadebe akụrụngwa na-ejuputa mmanụ, igbapu, na nzacha. Nyochaa oke na ịdịmma mmanụ transformer zuru oke.
  • Kwadebe ngwaọrụ nrụnye: vacuum oil filter (igwe mmanụ), tank mmanụ, tubes mmanụ, kreenu, na ngwaọrụ ndị ọzọ.

6.2 Akụrụngwa na Ngwa achọrọ

S/N

Aha akụrụngwa

Nkọwapụta & Nkọwa

1

Ngwa nyocha mmanụ

Mmanụ na-eguzogide voltaji, ọdịnaya mmiri, tgδ, wdg.

2

Ngwa na-ebuli elu (gụnyere èbè)

Ikike kwa eserese ọgbakọ izugbe

3

Vacuum oil filter (igwe mmanụ)

Maka ijuputa mmanụ ihe ntụgharị

4

Pipeline na tube njikọ

Njikọ/flanges iji kwekọọ nha valvụ maka eserese ọ bụla

5

Ebe nchekwa mmanụ

Ihe dị ka 1.1 × ihe ntụgharị mmanụ mmanụ

6

Ubube

25m na 3m

7

eriri nylon

Maka ebuli ohia, radiators, nchekwa nchekwa

8

Igwe na-ebuli elu

Maka radiators, conservator, wdg.

9

Ngwá ọrụ izugbe

Bolts, skru, na ngwaọrụ aka

10

Megameter (2500V)

Maka ịlele nguzogide mkpuchi

11

Ụlọ ọkụ

Maka nyocha nke tankị ime

12

akwa mmiri{0}

Nchedo site na ihu igwe

13

Ihe mgbanyụ ọkụ

Maka nchekwa ọkụ

6.3 chọrọ gburugburu ebe obibi maka nyocha ebuli isi

  • iru mmiri<65%: exposure time of active parts ≤16h
  • Iru mmiri 65%-75%: oge ​​ikpughe nke akụkụ ndị na-arụ ọrụ na-erughị awa 12 ma ọ bụ haha
  • Ambient okpomọkụ Karịrị ma ọ bụ hà nhata na ogo 5; Okpomọkụ ahụ kwesịrị ịdị ogo 5-10 karịa gburugburu
  • Ọ bụrụ na ọnọdụ okpomọkụ<0°C, raise active parts temperature above 10°C by hot oil circulation in advance
  • Iru mmiri karịrị 75% ma ọ bụ nhata: agaghị eme nyocha ebuli elu ma ọ bụ mmiri mmiri nitrogen.
Preparation for Site Installation
Nkwadebe maka nwụnye saịtị
Power Transformer Site Installation
Nwụnye saịtị ngbanwe ọkụ

 

 


 

 

 

 

7. Core Ebuli na Internal Inspection

 

 

7.1 Nkwadebe maka ebuli mkpuchi

Ọ bụrụ na nkwekọrịta ahụ akọwapụtaghị mkpa ebuli mkpuchi tankị, a gaghị arụ ọrụ a. Otú ọ dị, ọ bụrụ na transformer nwetara mmetụta ma ọ bụ ihe mberede a na-atụghị anya ya n'oge njem, a ga-eduzi nyocha mbuli elu n'agbanyeghị.

Tupu ịme nyocha mkpuchi mkpuchi ebuli elu:

  • Mezue usoro ọrụ niile na ihe achọrọ dịka ntuziaka nkwadebe
  • Tọpụ ma ọ bụ wepụ igwe njikọ dị n'etiti ahụ na tank mmanụ
  • Kwusaanụ na-mgbanwe ihe mgbata dị ka akwụkwọ ntuziaka ya siri dị

7.2 Usoro ebuli

Kwusasịa bolts njikọ nke ọnụ tank mmanụ. Dị ka eserese mgbakọ, họrọ èbè kwesịrị ekwesị ka a kpọgidere n'ime ihe nkedo nke mkpuchi na-ebuli elu. Mee nkwalite nnwale nwa oge iji dozie ọnọdụ nko ka etiti ike ndọda kwekọọ n'otu ahịrị kwụ ọtọ. Mgbe nnwale na-aga nke ọma, bulie tank mmanụ ma tinye ya na nkwado ndị a kpochara.

7.3 Ndepụta nyocha nke ime

  • N'ozuzu ọnọdụ:Ma ahụ nwere nchụpụ ma ọ bụ nnukwu mgbagha
  • Mpempe elu nke winding:Lelee maka mmegharị ọ bụla
  • Waya ndị ndu:Lelee maka welds mepere emepe ma ọ bụ nkwụsịtụ; gosi na mkpuchi waya ndu ka nọ n'ọnọdụ dị mma
  • Pịa bolts na skru:Lelee maka ịtọpụ ihe ọ bụla
  • Ọkọlọtọ fasteners:Lelee maka ịtọpụ ihe ọ bụla
  • Tank mmanụ na ime ahụ:Enweghị ihe mgbochi ma ọ bụ mmiri kwere
  • Pịa kọntaktị mgbanwe:Lelee kọntaktị na njikọ waya; hụ na tightening kwesịrị ekwesị
  • Isi ala:Nyochaa na isi gbadoro ụkwụ n'otu oge na mkpuchi dị n'ọnọdụ dị mma

7.4 Njikwa Ngwá Ọrụ n'oge nyocha nke ime

Ngwa niile nke ndị nyocha na-eji ga-enwerịrị ndebanye aha ID. A naghị ekwe ka akpa ndị mmadụ nwee ihe ọla. A machibidoro uzuzu na irighiri ihe ịbanye na tank. Mgbe emechara, ndị ọrụ na-arụ ọrụ ga-akwadorịrị na ọ nweghị irighiri ihe dị n'ime, a ga-enyocha ngwaọrụ niile megide ndebanye aha.

7.5 Mgbakọ tankị

Hichaa mmanụ fọdụrụnụ site na tankị dị ala wee chọpụta na ọ nweghị ngwaọrụ ma ọ bụ irighiri ihe fọdụrụ. Lelee na gasket mkpuchi ahụ adịghị emebi ma tinye ya nke ọma. Ebuli nke tank mmanụ ga-eguzosi ike; iweda ọsọ kwesịrị ịdị nwayọọ iji zere ndakpọ ụda na ahụ transformer. Ka tank mmanụ na-abịaru nso na gasket, jiri osisi na-eduzi nhazi bolt. Mgbe ị chọpụtachara ntinye gasket, fanye bolts niile wee kechie diagonally na nkebi iji nweta ọbụna tightness.

 

 


 

 

 

8. Ntinye nke Ngwa

 

 

8.1 Nkwanye nwụnye n'ozuzu

Gụọ ihe niile a ga-etinye (gụnyere bolts, akụ, washers). Jiri nlezianya nyochaa, hichaa ngwa, ma wepụ ihe mgbochi, unyi na uzuzu sitere na tubes nkwonkwo.

Akụkụ nwere akara nrụnye (elu -voltaji, ọkara-voltaji, obere-voltaji bushings, pedestals, ngwaọrụ ntọhapụ nrụgide) ga-agbaso ntuziaka maka ntinyeghachi, na-aṅa ntị na ọnọdụ ikwu na akụkụ nke tank.

Maka 110kV na n'elu, ndụmọdụ ndị na-achọsi ike ka a ga-etinyerịrị n'ime voltaji - na-ekerịta bọọlụ n'ọnụ ọhịa.

Mgbe ị na-agbakọta ọkpọkọ nkwonkwo conservator, malite n'akụkụ ikuku gas. Mechie bolts ezughị ezu ruo mgbe ejikọtala akụkụ niile, wee malite ịgbatị site na mpaghara relay gas.

Thermometer pedestals kwesịrị ejupụta na 2/3 mmanụ transformer.

Maka ihe ndị nwere plọg mmiri ikuku (LV bushing, gas relays, mmanụ nchekwa mmanụ, radiators, wdg), mepee oghere ikuku elu mgbe mmanụ mmanụ ga-ahapụ ikuku; emechila ruo mgbe mmanụ ga-ejupụta.

Tupu etinye gaskets akara, debe ebe igwe dị ọcha. Ebe a na-emechi ihe ga-abụrịrị griiz{1}} ejiri ihe mkpuchi akara ga-anọdụ ala nke ọma. Mechie bolts diagonally yana nrụgide otu.

8.2 Nwụnye Bushing

Isi echiche:

  • Ebe crane kwesịrị ikwado ibuli osisi na nrụnye
  • Jiri eriri naịlọn ma ọ bụ eriri waya nwere uwe nchebe; gbochie ịdaba na arịa nkwakọba ihe ma ọ bụ ihe ndị ọzọ
  • Lelee mgbapu mmanụ mgbe ị wepụsịrị bushes na igbe; nyochaa ọkwa mmanụ na mita mmanụ bụ ihe nkịtị
  • Jiri akwa ọcha dị ọcha hichaa elu na ime pedestal bushes tupu etinye ya
  • Nkuku dị nfe ga-adakọrịrịrịrị n'akụkụ pedestal slant

N'ihi 110kV na n'elu condenser bushing echichi:

  • Wepu ihe mgbochi elu na mkpuchi tupu ebuli
  • Mgbe etinyechara bushes n'obere ebe a na-arịgo, lelee site na oghere mgbidi tankị iji gosi na a na-agbanye ọnụ cone nke waya ndu n'ime voltaji -bọọlụ nkekọrịta
  • Gbaa mbọ hụ na waya ndu dị n'ime kwụ ọtọ n'enweghị mgbagha ma ọ bụ ịgbagọ
  • Zenarị ibuli nwụrụ anwụ mgbe ị na-agbazi waya ndu iji gbochie mmebi mkpuchi ma ọ bụ mkpọpụta osisi{0}
Transformer bushing
Transformer bushing
Bushing Installation
Nwụnye Bushing

8.3 Nwụnye akụrụngwa jụrụ oyi

Valvụ urukurubụba kwesịrị ịdị na steeti a na-apụ apụ mgbe ha na-akwatu efere akara ụgbọ njem. A na-enyocha ihe nju oyi maka mgbaze na nrụgide na mmanụ{1}}asachara tupu ọrụ ex{2}}. Mepee efere mkpuchi ụgbọ njem iji lelee ịdị ọcha ime; chọpụta ma mmanụ agbakwunyere - ịsacha ihe achọrọ. Wụnye ngwa nju oyi dabere na nọmba akụkụ yana akara nrụnye. Mgbe ị na-ebuli elu, dobe igwe nju oyi kwụ ọtọ ma bugharịa ya n'ọnọdụ, wee gbakọta na ọkpọkọ njikọ tank.

Cooling fans install
wụnye Fans oyi
Cooling fans
Fans jụrụ oyi

8.4 Nrụgide enyemaka Valve

Wepu ihe mkpuchi ụgbọ njem na mkpuchi oghere nrụnye. Jiri akwa ọcha hichaa mgbidi dị n'ime ruo mgbe ọ dịghị ihe furu efu. Wụnye na flange; chọrọ ezigbo akara na nrụnye a pụrụ ịdabere na ya. Ọ bụrụ na ejiri mkpuchi kpuchie ya, a ga-edobe mmanụ ahụ gaa n'ala mepere emepe. Ọ bụrụ na ejiri mmanụ - na-eduzi, tinye ya otu a.

8.5 Gas Relay Installation

Lelee ọdịdị dị mma ma nwalee kọntaktị mgbaàmà na kọntaktị njem maka ntụkwasị obi. Wepu efere mkpuchi ụgbọ njem ma kpochapụ flange nrụnye. Wepu eriri owu na-echekwa iko n'elu mmiri n'oge njem. Wụnye relay gas n'etiti tank mmanụ na onye nchekwa mmanụ, na-agbaso ntuziaka akụ na ngwaọrụ ahụ (akụ na-atụ aka na nchekwa mmanụ). Wụnye ọkpọkọ maka pedestal niile nke ahịhịa ka gas niile dị n'ime na-anakọta n'ime ọkpọkọ njikọ na gas relay.

Mara:Ihe mkpuchi elu nke ihe ngbanwe ga-enwe mkpọda nke 1.0%-1.5% n'akụkụ ụzọ ntụgharị ikuku gas iji kwado nchịkọta gas na ịgbalite mkpu.

8.6 Ntinye nchekwa na mmiri mmiri (ume).

Welie ihe nkwado nchekwa ma dozie ya na ihe mkpuchi tank na bolts. Wụnye ihe nchekwa na nkwado. Jikọọ pipeline ma wụnye relay gas na valvụ urukurubụba n'okpuru nchekwa nchekwa. Wụnye oghere gas, ntinye mmanụ, na ọkpọkọ mmanụ nwere valvụ nkwụsị na nsọtụ ala. Wụnye ọkpọkọ njikọ mmiri absorber, wee wụnye iku ume na njedebe ala. A ga-ewepụrịrị gasket mkpuchi maka nchekwa na njem. Jupụta igbe mkpuchi mmanụ na mmanụ transformer ka ọkwa mmanụ na-emikpu mgbanaka ikuku na-egbochi.

8.7 Thermometer nwụnye

Ihe njide temometa dị na mkpuchi tank mmanụ dị nso na nchekwa nchekwa. Jupụta obere mmanụ ngbanwe n'ime ihe njide tupu etinye temometa. Jiri nwayọọ gbanye temometa n'ime ihe njide. Maka temometa ihe nrụgide, eriri igwe anaghị arụ ọrụ dị ka tray ma dozie mgbidi tank.

Thermometer Installation
Ntinye temometa
Thermometer
Igwe ọkụ ọkụ

8.8 Na -Nwụnye mgbata mgbanwe

Mgbe ị wụnye tank mmanụ, lelee ma hichaa ụlọ mmanụ ihe ngbanwe nke nhọrọ ọzọ, wee wụnye ọkpọkọ mmanụ mmanụ. Jiri efere hanger pụrụ iche bulie onye na-agbanwe mgbata, jikọọ flange etiti yana flange nkwado, wee hụ na akara nke ọma. Jiri nlezianya tinye onye na-ahọrọ ihe ngbanwe n'ime ụlọ mmanụ, na-atụgharị axle mkpuchi ahụ nke ọma iji dozie njikọ ahụ ma hụ na ọnọdụ ziri ezi. Wụnye ihe ngosi ọnọdụ na efere mkpọchi, wee chịkọta bọọdụ mkpuchi isi mgba ọkụ. Jiri aka rụọ ọrụ dị mma wee tụgharịa mgbanwe iji chọpụta symmetry, wee jiri moto. Lelee ọnọdụ mgbata ọ bụla iji hụ na ihe ngosi mgbata na ihe ngosi ngwaọrụ dakọtara.

oltc of the transformer
oltc nke transformer
On-Load Tap Changer Installation
Na -Nwụnye mgbata mgbanwe

 

 

 

 


 

 

 

9. Na-ejuputa mmanụ maka mgbanwe (nkwụghachi mmanụ)

 

 

9.1 Mmanu mma chọrọ

A ga-asacha mmanụ transformer n'ụlọ ọrụ ahụ iji wedata na- ọrụ nnụcha saịtị. Maka ụgbọ njem ogologo{2}} ma ọ bụ ogologo oge -, a ga-eji ịgbà mmanụ. Tupu ịgba mmanụ, a ga-emerịrị nyocha nyocha mmanụ. Maka ịgba ọgwụ mgbochi, mmanụ ahụ ga-enwerịrị ụkpụrụ ndị a:

Oke

Ihe achọrọ

Voltaji ndakpọ

Karịrị ma ọ bụ hà nhata 70kV/2.5mm

Ọdịnaya mmiri

Ihe na-erughị ma ọ bụ hà nhata 8mg/L

Ọdịnaya gas

Ihe na-erughị ma ọ bụ hà nhata 0.8% (site na olu)

Ihe na-akpata ọnwụ dielectric tanδ (ogo 90)

Ihe na-erughị ma ọ bụ haha ​​0.5%

Ọnụọgụ urughuru (5μm-100μm)

≤1000 particles/100mL; no particles >100μm

Mara:Maka ndị ntụgharị 330kV-750kV, ọdịnaya mmiri agaghị agafe 10mg / L; maka 110 (66) kV, ọdịnaya mmiri agaghị agafe 20mg / l; maka 220kV, ọdịnaya mmiri agaghị agafe 15mg / L.

9.2 Usoro ndochi oghere

Tupu ndochi oghere, ebe akụrụngwa niile na ọkpọkọ njikọ ga-enwerịrị ntụkwasị obi. Ekwesịrị ịgbanye mmanụ site na valvụ mmanụ ala. A ga-edobe mgbapụta mgbapụta n'oge usoro njuputa, yana nrụgide fọdụrụ na-erughị ma ọ bụ nhata 20Pa. Okpomọkụ mmanụ ga-adị elu karịa okpomọkụ ahụ; Okpomọkụ ntinye mmanụ sitere na nzacha ga-abụ ogo 55 -65. Ọsọ njuputa agaghị agafe 100L / min. N'oge usoro a niile, a gaghị agbanye oghere ntinye na ọpụpụ ikuku na ọnọdụ ikuku mepere emepe{9}}.

9.3 Vacuum jide na ọkwa mmanụ

Kwụsị ijuputa mgbe ọkwa mmanụ dị 100-200mm n'okpuru tank n'elu. Nọgide na-enwe agụụ: maka 110kV transformers, jide agụụ maka opekata mpe awa 2; maka 220kV transformers, opekata mpe awa 4.

9.4 Bipute -Na-ejuputa mwepụ ikuku

Ka e mejuchara mmanụ, ikuku mepere emepe{0}} na-akụnye igwe nju oyi, osisi, relays gas, nchekwa nchekwa, na radiators iji hapụ ikuku tọrọ atọ. Emechiela plọg na-ekpofu ikuku ruo mgbe mmanụ ga-ejupụta. Maka igwe ngbanwe mmanye mmanye mmanye, bido ngwaọrụ niile jụrụ oyi wee kesaa ma ọ dịkarịa ala awa 4 iji wepụ ikuku fọdụrụnụ kpamkpam.

9.5 Mgbasa mmanụ ọkụ

Maka 330kV na n'elu ihe ngbanwe, mgbasa mmanụ na-ekpo ọkụ dị mkpa ka e mejupụta oghere. Usoro mgbasa mmanụ na-ekpo ọkụ na-eji ihe nzacha dị elu - na-ekpo ọkụ, na-enwe okpomọkụ mmanụ na-adịghị n'okpuru ogo 50 ma ọ bụ karịa ogo 80; okpomọkụ n'ime tank adịghị n'okpuru 40 degrees. Oge okirikiri: 220-330kV transformers ọ bụghị ihe na-erughị awa 24; 500kV transformers ọ bụghị ihe na-erughị awa 48. Oge mgbasa ozi n'ezie kwesịrị ikwe ka olu mmanụ dum gbasaa ma ọ dịkarịa ala ugboro abụọ.

9.6 Ndozi ọkwa mmanụ

Mgbe emejuchara, nyochaa ọkwa ọkwa mmanụ n'oge oge. Ọkwa mmanụ ga-adaba n'akara dị na nchekwa nchekwa dabara na ọnọdụ okpomọkụ . 1–2 awa ka emejuchara, lelee ọkwa mmanụ ọzọ. Ọ bụrụ na ịdị elu mmanụ agbadala nke ukwuu, tinye mmanụ ka ọ weta ya na ahịrị okpomọkụ dabara adaba.

9.7 Static idozi

Mgbe emejuchara, transformer ga-enweta oge nbibi ka mmanu wee dozie nke ọma ma wepụ ihe adịghị ọcha na afụ. N'ihi na 110kV transformers, static edozi oge karịrị ma ọ bụ hà 24 awa; maka 220kV transformers, ukwuu karịa ma ọ bụ hà 48 awa.

 

 


 

 

 

10. Nchekwa nchekwa

 

 

Mmanụ ntụgharị bụ mmiri mmiri na-ere ọkụ. A machibidoro ị smokingụ sịga na ọkụ mepere emepe na saịtị nrụnye. Ọ bụrụ na achọrọ ịgbado ọkụ gas ma ọ bụ ịgbado ọkụ eletrik, a ga-ahụrịrị usoro mgbochi ọkụ. A ga-edozi ngwa nchekwa ọkụ tupu echichi, yana ndị ọrụ a họpụtara ahọpụta. A ga-eji mmanụ ihe mkpofu ekpokọta akwụkwọ na akwa akwa a na-emikpu n'ime mmanụ transformer ma tụfuo ya n'otu oge mgbe echichichara ya.

Usoro nchekwa ndị ọzọ:

  • Tupu echichi, ọchịagha {{0}na- onye isi na nchekwa ga-akpọkọta ndị nrụnye niile maka nzukọ nchekwa ọrụ, nye nkuzi nchekwa, ma kwupụta iwu nchekwa.
  • Ndị ọrụ na-adịghị mkpa agaghị abanye n'ubi nwụnye
  • Ngwa na ihe ndị gafere na ala ga-ejikọta; enweghị atụba ekwe
  • Mgbe ị na-etinye ma ọ bụ wepụ akụkụ ndị nwere ike ịdaba na elu, mmadụ abụọ ga-arụkọ ọrụ ọnụ
  • Mgbe ị na-eji ọkụ mkpanaka, a gaghị ebuba oriọna 220V n'ime tank mmanụ, a gaghị etinyekwa ike nwa oge na ndị nduzi mkpuchi na-adịghị mma.

 

 


 

 

 

11. Nkwenye na ntinye aka

 

 

11.1 Tupu -Nlebanye anya n'ọrụ

Tupu etinye transformer n'ọrụ ikpe, a ga-eme nyocha zuru oke:

  • Isi ahụ na ngwa ejikọtara n'ụzọ zuru oke yana ọnọdụ dị mma; Ọkwa usoro na akara ziri ezi
  • A na-ehichapụ tank mmanụ na akụkụ niile dị ọcha, enweghị mgbapu mmanụ
  • Ngosipụta ọkwa ọkwa nchekwa nchekwa na ahịhịa ahịhịa doro anya na nke ziri ezi, yana ọdịiche dị na njehie nha
  • Ngwaọrụ jụrụ oyi na-arụ ọrụ nke ọma; nfuli mmanụ na fan na-agba ọsọ nke ọma; sekit njikwa na-arụ ọrụ nke ọma
  • Ntugharị gas arụnyere n'ụzọ ziri ezi; mmanụ larịị nkịtị; gas kpochapuru kpamkpam
  • Mmiri mmiri na-ekpo ọkụ jupụtara na allochroic silica gel; iko mmanụ nwere mmanụ doro anya na ọkwa kwesịrị ekwesị
  • Onye na-agbanwe mgbata na-arụ ọrụ nke ọma; nleba anya nke ọma; Ọkwa mgbatụ atọ- bụ otu
  • Ihe mgbakwasị ụkwụ ndị dị n'okpuru ala, ebe a na-adọba mmanụ mmanụ, ịkụ ala ahịhịa, na ọta ala zuru oke na ntụkwasị obi
  • Ọ dịghị - na-ebu ọnụ ọnụ nke ịhịa aka n'ahụ -ụdị ihe ngbanwe dị ugbu a dị mkpụmkpụ-ekesara ma gbadaa n'ala

Nyochaa usoro:Usoro ntụgharị na otu njikọ ikuku ga-ezute ihe achọrọ arụ ọrụ yiri ya tupu ikenye ike.

11.2 Nlele eletriki

A ga-eme ule eletrik niile kwa GB 50150-2016 tupu ịnye ọrụ. Ihe ule amanyere amanyere bụ:

Mba.

Nwale ihe

1

Nnwale mmanụ mkpuchi ma ọ bụ ule gas SF6

2

Nleta nke iguzogide DC nke windings yana bushes

3

Lelee oke voltaji na mgbata niile

4

Nleba otu - njikọ nkeji na nlele polarity (otu -usoro)

5

Nledo nguzogide mkpuchi nke isi na mkpọchi

6

Nnwale ndị na-abụghị{{0}poselin

7

Na -bue pịa-nleba anya na nnwale

8

Mgbochi mkpuchi, oke absorption, ma ọ bụ nha nha nha nha nke windings na bushes

9

Ihe na-akpata ọnwụ dielectric (tanδ) na nha ike nke windings na bushes

10

Nlere nrụrụ ikuku

11

AC na-eguzogide ule voltaji nke windings na bushes

12

Ogologo ogologo-Ac butere ule voltaji na nha mwepu akụkụ

13

Nnwale mmechi mmetụta na voltaji ewepụtara

14

Nyochaa usoro

15

Ntụnye mkpọtụ

N'ihi na 66kV na n'elu transformers, etisasịwo gas chromatographic analysis nke mmanụ ga-eme ugboro atọ: mgbe mmanụ ndochi na edozi, 24 awa mgbe iguzogide na ele mmadụ anya n'ihu ule ule, na 24 awa mgbe mmetụta mmechi na ọrụ na gosiri voltaji. Mkpokọta ọdịnaya hydrocarbon dị na mmanụ transformer ọhụrụ agaghị agafe 20μL/L, H₂ agaghị agafe 10μL/L, na C₂H₂ agaghị agafe 0.1μL/L.

11.3 Nnwale mmechi mmetụta

Transformer ga-agafe ugboro 5 nke enweghị mmechi mmechi mmetụta voltaji{1}juju{1}. Mgbe ike nke mbụ gasịrị, oge agaghị agafe nkeji iri. Igwe ndọta na-eme ihe ugbu a agaghị eme ka ngwaọrụ nchekwa ghara imebi. Maka nnọpụiche -isi -sistemụ gbadoro ụkwụ, ebe nnọpụiche ahụ ga-agbadarịrị n'oge mmechi mmetụta.

11.4 Ọrụ nnwale

Na-esochi mmechi mmechi nke ọma, a ga-etinye transformer ka ọ rụọ ọrụ nnwale, na-agba ọsọ na oke kachasị dị na sistemụ n'oge ahụ maka awa 24 na-aga n'ihu. Mgbe awa 24 gachara nke ọma n'enweghị ihe ọ bụla, a na-ewere ịgba ọsọ nnwale ahụ ka ọ zuo oke, enwere ike itinye transformer n'ụzọ ziri ezi.

11.5 Akwụkwọ a ga-enyefe

Mgbe anabatachara, a ga-ebufe akwụkwọ ndị a:

  • Ndekọ teknuzu nwụnye, ndekọ nyocha isi, ndekọ ihicha, mkpesa nyocha dị mma, na aka eletrik{0}maka mkpesa ule
  • Ihe osise ihe owuwu na akwụkwọ mgbanwe imewe
  • Akwụkwọ ntuziaka onye nrụpụta ngwaahịa, ndekọ nnwale, asambodo nnabata, na eserese nwụnye
  • Ndepụta nke akụkụ mapụtara, ngwa, ngwa pụrụ iche, na ngwa nnwale
The power transformer has been installed and is ready for use
E tinyela ihe ngbanwe ọkụ ma dị njikere maka ojiji
The power transformer is ready for putting into trial operation
Ihe ntụgharị ike dị njikere maka itinye n'ọrụ ikpe

 

 

 

12. Nrụnye Transformer emetụtara & Ntuziaka ọrụ

 

 

Ntuziaka a na-elekwasị anya na nnukwu mgbanwe ọkụ na ọdụ ụgbọ ala na ụlọ ọrụ mmepụta ihe. Maka nhazi ihe ngbanwe ndị ọzọ a na-ahụkarị na netwọk nkesa na n'èzí, biko lelee akwụkwọ kwekọrọ n'okpuru.

 

 


 

 

 

13. Nkwubi okwu

 

 

Nrụnye nke ọma na inye ọrụ dị oke mkpa maka ogologo oge dị ogologo{0}} nke ndị na-agbanwe ọkụ. Ntuziaka a na-ejikọta ihe ndị nrụpụta chọrọ yana ụkpụrụ mba dabara adaba. Ndị ọrụ niile metụtara kwesịrị ịgbasosi usoro ndị akọwara n'ime ya anya, debe akwụkwọ nke ọma n'oge usoro nrụnye, ma kpọtụrụ onye nrụpụta ya mgbe ejighị n'aka ọ bụla bilitere.

 