12 kVA Mgbanwe nkesa Akọrọ-11 / 0.22 kV|United Arab Emirates 2025
Ike: 12kVA
Voltaji: 11000/220V
Njirimara: ya na mkpuchi: IP20

Ike a pụrụ ịdabere na ya n'ụdị kọmpat - ihe ngbanwe nkesa akọrọ gị tụkwasịrị obi
01 Izugbe
1.1 Nkọwa oru ngo
Nke a 12 kVA Cast Resin Dry-Type Transformer (CRT) bụ kọmpat na ngwọta a pụrụ ịdabere na ya maka nkesa ike dị ala-ikike atọ-. Emebere ya dị ka ụkpụrụ IEC siri dị, ọ nwere nnukwu ọka - gbakwasara silicon steel core na windings ọla kọpa, nwere ikuku jụrụ oyi (AN), voltaji bụ isi nke 11 kV na voltaji nke abụọ nke 0.22 kV.
Ejiri otu Dy11 vector group na Mba -Load Tap Changer (NLTC) nwere nhazi ±2×2.5%, ihe ngbanwe a nwere obere enweghị-ibu na ibu mfu nke 0.09 kW na 0.39 kW. Ihe mkpuchi klaasị B na-eme ka ọrụ ntụkwasị obi na nchekwa dị n'okpuru ọnọdụ nkịtị.
A Cast Resin Transformer (CRT), nke a na-akpọkwa Epoxy Cast Resin Dry -Type Transformer, bụ ihe ntụgharị ọkụ ọkụ- ụdị. A na-eji resin epoxy kpuchie windings nke ọma. Ọ naghị eji mmanụ ma ọ bụ mmiri mmiri ndị ọzọ eme ihe maka mkpuchi. A na-eji ikuku mee ka ọ dị jụụ ma kpuchie isi na windings.
Resin epoxy na-enye ihe mkpuchi siri ike ma kwụsị ngbanwe ka ọ ghara ịmịkọrọ mmiri. Nke a na-ahapụ ya ka ọ rụọ ọrụ nke ọma n'ebe iru mmiri, uzuzu uzuzu ma ọ bụ ebe siri ike. A na-awụsa resin n'okpuru oghere. Nke a na-eme ka ọ hụ na ejiri mkpuchi mkpuchi kpuchie ma chekwaa ya kpamkpam. Igwe ngbanwe akọrọ nwere ikike 12 kVA yana ogo voltaji 11kV/0.22kV. Ọ na-enye ngwọta kwụsiri ike maka nkesa obere voltaji - ruo -.
1.2 Nkọwa nka nka
12 kVA Resin nkedo ụdị ihe ngbanwe ụdị akọrọ na mpempe data
|
Enyere ya
United Arab Emirates
|
|
Afọ
2025
|
|
Ụdị
Resin nkedo ụdị ngbanwe
|
|
Isi ihe
Mpempe akwụkwọ silicon na-adabere na ọka
|
|
Ọkọlọtọ
IEC
|
|
Enyere ike
12 kVA
|
|
Ugboro ugboro
50HZ
|
|
Usoro
Atọ
|
|
Otu vector
Dy11
|
|
Ụdị oyi
AN
|
|
Voltaji nke mbụ
11KV
|
|
Voltaji nke abụọ
0,22 kV
|
|
Ngwa ikuku
Ọla kọpa
|
|
Mgbochi
4%
|
|
Ngwa ikuku
NLTC
|
|
Mgbochi
2.5%
|
|
Pịa Changer
NLTC
|
|
Ọkụ aka
± 2 * 2.5% @ isi voltaji
|
|
Enweghị mfu ibu
0.09 kW
|
|
Na Ọnwụ Ebu
0.39kW
|
|
Ọkwa mkpuchi
B
|
|
Ngwa ngwa
Onye na-ahụ maka okpomọkụ, Mkpuchi
|
1.3 Eserese
12kVA resin nkedo akọrọ ụdị ihe ngbanwe eserese na aha aha
![]() |
![]() |
02 Nrụpụta
2.1 Isi
The silicon ígwè nwere ihe dị ka 3% silicon. Ọ nwere ezigbo magnetik arụmọrụ na obere ọnwụ. Nke a na-enyere aka ibelata ikuku mmiri ma na-arụ ọrụ nke ọma na ugboro dị elu. Mpempe akwụkwọ silicon ọla edo edobere nke ọma na-ebelata mfu dị ugbu a yana ndọta hysteresis, na-eme ka ike dị mma.
2.2 Ikuku

Ihe nkesa nkesa nkụ nke 12kVA na-eji ọla kọpa na-arụ ọrụ dị elu{{1} Igwe ikuku dị ala-voltaji na-eji nhazi foil iji hụ na nkesa otu dị ugbu a. Ihe ngbanwe ahụ na-eji mkpuchi Klas B (130 degrees) yana teknụzụ nkedo epoxy resin maka ezigbo mmiri na nguzogide uzuzu, ebe ọ na-enyekwa nchekwa mkpirisi mkpirisi a pụrụ ịdabere na ya.
2.3 IP20 ihe mkpuchi
Ụdị ngbanwe a dị n'ime ụlọ- nwere ihe mkpuchi nchekwa IP20 kwadoro, na-egbochi njikọ kpọmkwem n'etiti mkpịsị aka na ihe siri ike nke mba ọzọ yana ihe ndị dị ndụ, na-ahụ na nchekwa onye ọrụ. Ihe mkpuchi ahụ na-egbochikwa uzuzu, ịkpụcha ígwè, na ihe ndị ọzọ ịpụ apụ ịbanye na transformer, na-ebelata ihe ize ndụ nke ndakpọ mkpuchi na ikpo ọkụ na mpaghara. Ọzọkwa, ihe mkpuchi ahụ na-ebelata mkpọtụ ọrụ ma na-ebuli gburugburu ime ụlọ.

2.4 Mgbakọ ikpeazụ

A na-achịkọta isi ihe ndị a kpụrụ akpụ na ikuku, n'oge a na-eme njikọ eletriki, mkpuchi, na nhazi nhazi.
N'okpuru oghere, a na-awụsa resin epoxy n'etiti windings na isi, na-eme ka usoro siri ike, gwọọ.
Mgbe mgbakọ na ọgwụgwọ gasịrị, a na-eme usoro ule eletriki na ígwè ọrụ iji hụ na onye na-agbanwe agbanwe na-ezute ụkpụrụ nhazi na nchekwa.
03 Nnwale
Nnwale Ọkọlọtọ na Nnwale oge
IEC 60076-1-2011 Ndị na-agbanwe ike - Akụkụ 1: Ozuruọnụ
IEC 60076-3-2013 ndị na-agbanwe ike - Nkebi 3: ọkwa mkpuchi, ule dielectric na mkpochapụ mpụga na ikuku.
IEC 60076-11-2018 RLV ndị na-agbanwe ọkụ - Nkebi 11: ụdị ntụgharị ọkụ.
1. Ntụle nke winding iguzogide
2. Ntụle nke voltaji ratio na ịlele nke oge mbughari
3. Nleta nke mkpụmkpụ - ihe mgbochi okirikiri na mfu ibu
4. Ntụle nke enweghị ibu ibu na ugbu a
5. Nnwale voltaji etinyere
6. Nnwale ule na-eguzogide voltaji
7. Nnwale mwepụ nke akụkụ


Nsonaazụ ule
|
Mba. |
Nwale ihe |
Nkeji |
Ụkpụrụ nnabata |
Ụkpụrụ ndị atụtara |
Mmechi |
|
|
1 |
Ntụle nke winding iguzogide |
/ |
Ọnụego enweghị nguzozi kacha nguzogide Nguzogide ahịrị: Ihe na-erughị ma ọ bụ haha 2% |
HV (akara) |
LV (akara) |
Gafe |
|
0.68% |
0.53% |
|||||
|
2 |
Ntụle nke oke voltaji na nlele nke mbugharị oge |
/ |
Nkwenye nke oke voltaji na ọpịpị bụ isi: ± 1/10 Akara njikọ: Dy11 |
0.01% ~ 0.12% Dy11 |
Gafe |
|
|
3 |
Ntụnye nke Mkpirisi-Mkpirisi okirikiri na mfu ibu |
/ kW kW |
t:100 ogo Z%: uru tụrụ Pk: uru tụrụ Pt: uru tụrụ |
3.64% 0.259 0.317 |
Gafe |
|
|
4 |
Ntụle nke mba- ibu mfu na ugbu a na 90% na 110% nke voltaji e gosiri |
/ kW |
I0 :: nye uru a tụrụ atụ P0: nye uru a tụrụ atụ |
90% Uru |
2.88 0.083 |
Gafe |
|
100% Ur |
3.21 0.093 |
|||||
|
110% Ur |
3.53 0.102 |
|||||
|
5 |
Nnwale voltaji etinyere |
/ |
HV: 28kV 60s LV 3kV 60s |
Enweghị ọdịda nke voltaji ule a na-eme |
Gafe |
|
|
6 |
Nnwale Iguzogide Voltaji butere |
/ |
Voltaji etinyere (KV): 2 Ua Voltaji ebutere (KV): 0.44 Ogologo oge (s):40 Ugboro (HZ): 150 |
Enweghị ọdịda nke voltaji ule a na-eme |
Gafe |
|
|
7 |
Nnwale mgbapu akụkụ |
pC |
Ọkwa kacha nke mwepu akụkụ ga-abụ 10 pC |
<10 |
Gafe |
|
04 Mbukota na mbupu
![]() |
![]() |
05 Saịtị na nchịkọta
N'ụlọ ọrụ mmepụta ihe na nke azụmahịa, ọkụ ọkụ kwụsiri ike dị ezigbo mkpa. Scotech 12 kVA Cast Resin Dry-Type Transformer (CRT) na-enye nchekwa na arụ ọrụ nke ọma- ka ọ dị ala-voltaji.
Ọ nwere ikuku ọla kọpa na isi ihe nchara silicon. A na-ekpuchi ikuku ikuku nke ọma na resin epoxy na ikuku jụrụ{1}, yabụ na ọ nweghị mmanụ achọrọ. Resin na-echebe megide mmiri na uzuzu, na-enye ohere iji ogologo oge{3} na gburugburu ebe ọjọọ.
O nwere otu Dy11 vector na Mba-Load Tap Changer (NLTC) maka mmezi voltaji na-agbanwe agbanwe. Ọ dịghị obere - ibu na mfu ibu na-eme ka ọ dị mma. Ihe mkpuchi IP20 na-echebe ndị mmadụ ma kwụsị uzuzu ịbanye, ma na-ebelata mkpọtụ n'ime ụlọ.

Ihe nchịkọta dị ọkụ: akọrọ nkesa transformer, nrụpụta, soplaya, price, efu
You Might Also Like
250 kVA Dry Cast Resin Transformers-10/0.4 kV|Georgi...
1.25 MVA Nkedo Resin Ụdị Ntugharị-0.415 / 3.3 * 6.6 ...
3 MVA Dry Type Transformers-13.8 / 0.48 kV|Jamaica 2025
500 kVA Dry Resin Transformer-13.8 / 0.46 kV|South A...
2500 kVA Dry Transformer-10 / 0.4 kV|Georgia 2025
630 kVA Nkedo Resin Akọrọ Ụdị Ntugharị-66.6 / 0.55 k...
Zipu ozi